B.  IntelliFire Ignition System

Symptom

Possible Cause

Corrective Action

1. Pilot won’t light. 

The ignitor/module 
makes noise, but no 
spark.

A. Incorrect wiring.

Verify “S” wire (white) for sensor and “I” wire (orange) for ignitor are 
connected to correct terminals on module and pilot assembly.

B.  Loose connections or electrical 

shorts in the wiring.

Verify no loose connections or electrical shorts in wiring from mod-
ule to pilot assembly. Verify connections underneath pilot assembly 
are tight; also verify connections are not grounding out to metal 
chassis, pilot burner, pilot enclosure, mesh screen if present, or any 
other metal object. 

C. Ignitor gap is too large.

Verify gap of igniter to right side of pilot hood. The gap should be 
approximately .17 in. or 1/8 in. (3 mm).

D. Module.

Turn ON/OFF rocker switch or wall switch to OFF position. Remove 
ignitor wire “I” from module. Place a grounded wire about 3/16 in. (5 
mm) away from “I” terminal on module. Place ON/OFF rocker switch 
or wall switch in ON position. If there is no spark at “I” terminal module 
must be replaced. If there is a spark at “I” terminal, module is fi ne. 
Inspect pilot assembly for shorted sparker wire or cracked insulator 
around electrode. Replace pilot if necessary.

2. Pilot won’t light, 

there is no noise or 
spark.

A. No power or transformer installed 

incorrectly.

Verify that transformer is installed and plugged into module. Check 
voltage of transformer under load at spade connection on module 
with ON/OFF switch in ON position. Acceptable readings of a good 
transformer are between 3.2 and 2.8 volts AC.

B. A shorted or loose connection in 

wiring confi guration or wiring har-
ness.

Remove and reinstall the wiring harness that plugs into module. 
Verify there is a tight fi t. Verify pilot assembly wiring to module. Re-
move and verify continuity of each wire in wiring harness.  Replace 
any damaged components.

C. Improper wall switch wiring.

Verify that 120/VAC power is “ON” to junction box.

D.  Module not grounded.

Verify black ground wire from module wire harness is grounded to 
metal chassis of appliance.

E.  Module.

Turn ON/OFF rocker switch or wall switch to OFF position. Remove 
ignitor wire “I” from module. Place ON/OFF rocker switch or wall 
switch in ON position. If there is no spark at “I” terminal module 
must be replaced. If there is a spark at “I” terminal, module is fi ne. 
Inspect pilot assembly for shorted sparker wire or cracked insulator 
around electrode.

3. Pilot sparks, but 

Pilot will not light.

A.  Gas supply.

Verify that incoming gas line ball valve is “open”. Verify that inlet 
pressure reading is within acceptable limits, inlet pressure must not 
exceed 14 in. W.C.

B. Ignitor gap is too large.

Verify gap of igniter to right side of pilot hood. The gap should be 
approximately .17 in. or 1/8 in. (3 mm).

C.  Module is not grounded.

Verify module is securely grounded to metal chassis of appliance.

D.  Module voltage output / Valve/Pilot 

solenoid ohms readings.

Verify battery voltage is at least 2.7 volts. Replace batteries if volt-
age is below 2.7.

Содержание NDI30-C

Страница 1: ...e is only for use with the type s of gas indicated on the rating plate Installation and service of this appliance should be performed by qualified personnel Hearth Home Technologies suggests NFI certi...

Страница 2: ...ouble free enjoyment Welcome to the Heatilator family of fireplace products We recommend that you record the following pertinent information about your fireplace Gas and Electric Information Serial Nu...

Страница 3: ...iance System 15 B Design and Installation Considerations 16 C Tools and Supplies Needed 16 D Inspect Appliance and Components 16 5 Fireplace Size Requirements A Minimum Fireplace Opening 17 B Mantel a...

Страница 4: ...the date of original purchase In the case of new home construction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independen...

Страница 5: ...QLVKHV DV D UHVXOW RI QRUPDO XVH V D KHDWLQJ DSSOLDQFH VRPH FKDQJHV LQ FRORU RI LQWHULRU DQG H WHULRU VXUIDFH ILQLVKHV PD RFFXU 7KLV LV QRW D IODZ DQG LV QRW FRYHUHG XQGHU ZDUUDQW DPDJH WR SULQWHG SOD...

Страница 6: ...uced these rules do not apply Check with your local gas utility or authorities having jurisdiction When installing above 2000 feet elevation In the USA Reduce input rate 4 for each 1000 feet above 200...

Страница 7: ...nologies if the barrier is not present or help is needed to properly install one HOT SURFACES Glass and other surfaces are hot during operation AND cool down Hot glass will cause burns DO NOT touch gl...

Страница 8: ...structions supplied with the control installed to operate your fireplace For safety Install a switch lock or a wall remote control with child protection lockout feature Keep remote controls out of rea...

Страница 9: ...smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance DO NOT touch any electric switch do not use any...

Страница 10: ...fireplaces com A This appliance has a pilot which must be lighted by hand When lighting the pilot follow these in structions exactly B BEFORE LIGHTING smell all around the appliance area for gas Be su...

Страница 11: ...or 20 to 40 minutes Odor from appliance When first operated this appliance may release an odor for the first several hours This is caused by the curing of the paint and the burning off of any oils rem...

Страница 12: ...ce ap pointment More frequent cleaning may be required due to lint from carpeting or other factors Control compartment burner and circulating air passageway of the appliance must be kept clean CAUTION...

Страница 13: ...sed to heat Confirm there is no damage to glass or glass frame Replace as necessary Verify that fixed glass assembly is properly retained and attachment components are intact and not damaged Replace a...

Страница 14: ...ies have been removed from battery back up IPI systems to prevent premature battery failure or leaking For optimal battery life locate the battery pack outside of the control cavity on the hearth This...

Страница 15: ...rations diagrams are not drawn to scale Actual product may vary from pictures in manual VERTICAL TERMINATION CAP SECTION 8 F VENT PIPE SECTION 8 GAS LINE SECTION 9 ACCESS THROUGH EXISTING MASONRY OR W...

Страница 16: ...ronts may be shipped in separate packages If packaged separately the log set and appliance grate must be installed Report to your dealer any parts damaged in shipment particularly the condition of the...

Страница 17: ...arts of the fireplace in which the gas fireplace insert is to be installed is prohibited except the floor as tested for and as noted above and in Figure 5 1 A minimum 1 2 inch gap from the bottom of t...

Страница 18: ...34 5 8 879 30 1 2 775 C Glass Opening Width 31 9 16 802 27 7 16 697 D Glass Opening Height 15 11 16 398 12 13 16 325 E Height Front 24 610 20 1 2 521 F Height Rear 21 1 16 535 17 5 8 448 G Unit Depth...

Страница 19: ...bove combustible material or outer wrap of factory built firebox Combustible facings must not extend behind the insert surround For non combustible material specifications refer to Section 1 E Figure...

Страница 20: ...Over 18 12 to 20 12 7 5 Over 20 12 to 21 12 8 0 Figure 6 1 Minimum Height From Roof To Lowest Discharge Opening 3 foot minimum in snow regions HORIZONTAL OVERHANG VERTICAL WALL GAS DIRECT VENT TERMIN...

Страница 21: ...as no gas access hole provided an access hole of 1 inch 25 mm diameter or less may be drilled through the lower sides or bottom of the firebox in a proper workmanship like manner This access hole must...

Страница 22: ...NOT connect this gas appliance to a chimney flue serving a separate solid fuel or gas burning appliance May impair safe operation of this appliance or other appliances connected to the flue Vent this...

Страница 23: ...Aminimum 1 2 inch gap from the bottom of the appliance to a metal surface is RECOMMENDED for optimal fan performance See Figure 5 1 Position any excess flexible vent pipe back up into chimney without...

Страница 24: ...24 E Remote Control The receiver for the remotes may be installed BETWEEN the base pan of the insert and the firebox of the wood burning fireplace or in the control cavity of the insert See Figure 8...

Страница 25: ...hing on cap by removing 3 screws Connect both the LINK ZC ADPB to Class A Pipe and the termination cap to the LINK ZC ADPB with the self tapping screws provided OPTIONAL LINK ZC ADPB FOR USE WITH CLAS...

Страница 26: ...mmercially available leak check solution DO NOT use open flame Fittings and connections could have loos ened during shipping and handling WARNING Risk of Fire DO NOT change valve settings This valve h...

Страница 27: ...e protected with ground fault circuit interrupter protection in compliance with the applicable electrical codes when it is installed in locations such as in bathrooms or near sinks Low voltage and 120...

Страница 28: ...GNITOR I S GROUND TO FIREPLACE CHASSIS BATTERY PACK ORG WHT WALL SWITCH OR REMOTE CONTROL BRN BRN ON OFF ON OFF NOTE 1 4 IN FEMALE SPADE CONNECTORS CONNECT TO THE REMOTE WIRE ASSEMBLY REMOTE WIRE ASSE...

Страница 29: ...for a wiring diagram for a blower or remote Wiring for optional Hearth Home Technologies approved accessories should be done now to avoid reconstruction Follow instructions that come with those acces...

Страница 30: ...ed Remove the four screws on the cover plate see Figure 10 6 Install and wire the fan per instruction shipped with the fan Figure 10 5 also shows a wiring diagram Models NDI30 C NDI30 SP NDI35 C and N...

Страница 31: ...e board etc Clearance to combustible material under the insert is 1 4 inch 6 mm Clearance from top of fireplace opening for combustibles extending 12 inches max is 12 inches Use leveling legs to raise...

Страница 32: ...ly placed embers interfere with proper burner operation Ember material is shipped with this gas appliance To place the ember material Embers CANNOT be placed directly over ports Care should be taken n...

Страница 33: ...ails Mate the slot located on the bottom of Log 2 with the log pin located on the right side of the burner Move the right end of Log 2 forward until it comes into contact with the grate tine GRATE GRA...

Страница 34: ...ot of Log 2 Position the back end of the log on the flat spot of Log 1 Figure 10 shows the log set properly installed LOG TOUCHES LOG TOUCHES GRATE TINE GRATE TINE PLACE TOP END OF PLACE TOP END OF LO...

Страница 35: ...706 Position Log 2 as shown in Figure 4 Refer to Figure 2 and Figure 5 for additional details Mate the slot located on the bottom of Log 2 with the left log pin located on the burner top Rotate the l...

Страница 36: ...g 6 BASE TINE BASE TINE GROOVE GROOVE 4 4 5 5 Figure 6 Log 3 Figure 7 Log 3 Log 3 SRV2224 702 Position Log 3 as shown in Figure 6 Refer to Figure 2 and Figure 7 for location of reference points Mate t...

Страница 37: ...for cracks chips or scratches DO NOT strike slam or scratch glass DO NOT operate fireplace with glass removed cracked broken or scratched Replace as a complete assembly Removing Fixed Glass Assembly...

Страница 38: ...ocouple connection at the gas valve is fully in serted and tight hand tighten plus 1 4 turn Verify proper voltage output from the thermocouple to the valve Place one millivolt meter lead wire on the t...

Страница 39: ...tank Refill the fuel tank B Improper gas inlet pressure Natural gas should be 5 14 in w c LP should be 10 14 in w c Verify pressure with manometer C Inner vent pipe leaking exhaust gases back into th...

Страница 40: ...led and plugged into module Check voltage of transformer under load at spade connection on module with ON OFF switch in ON position Acceptable readings of a good transformer are between 3 2 and 2 8 vo...

Страница 41: ...ot orifice is installed and gas inlet is set to pressure specifications Polish flame sensing rod with fine steel wool to remove any contaminants that may have accumulated on flame sensing rod C Module...

Страница 42: ...30 1 2 775 C 31 9 16 802 27 7 16 697 D 15 11 16 398 12 13 16 325 E 24 610 20 1 2 521 F 21 1 16 535 17 5 8 448 G 15 7 8 403 14 5 8 372 H 11 3 4 298 10 1 8 257 I 20 3 8 518 17 432 J 1 3 4 44 1 3 4 44 M...

Страница 43: ...udes two liners termination cap flashing and link adapter Figure 14 2 Direct Vent Flex Liner Kits Figure 14 3 Direct Vent Flex Liner Accessory Kits Direct Vent Flex Liner Accessory Kits see Figure 14...

Страница 44: ...6 Log 6 SRV2206 704 7 Termination Plate Assembly 2206 012 Flex Pipe Handle 438 351 Gasket 2206 401 8 Grate Assemby 2226 016 9 Burner Assembly 2226 008 Y 10 Base Pan 2206 127 11 Valve Assembly Refer t...

Страница 45: ...224 702 4 Log 4 SRV2224 703 5 Log 5 SRV2224 704 6 Log 6 SRV2224 705 7 Fireplace Termination Assembly 2205 012 Flex Pipe Handle 438 351 Gasket 2206 401 8 Grate Assemby 2224 016 9 Burner Assembly 2224 0...

Страница 46: ...I30 C 582 835 Y Orifice LP 51C 582 851 Y Orifice NG 33C NDI35 C 582 833 Y Orifice LP 50C 582 850 Y 11 5 Flexible Gas Connector 530 302A Y 11 6 Control Panel Bracket 2205 128 11 7 Valve Bracket 2205 14...

Страница 47: ...embly LP 2103 011 Y Pilot Tube SRV485 301 Y Thermocouple 446 511 Y Thermopile 2103 512 Y 11 4 Orifice NG 33C NDI35 SP 582 833 Y Orifice LP 50C 582 850 Y Orifice NG 35C NDI30 SP 582 835 Y Orifice LP 51...

Страница 48: ...s Set Only NDI30 BRICK NDI30 NDI35 BRICK NDI35 Rheostat Temp Sensor Assembly SRV2206 800 Y Temp Sensor Assembly 046 018A Y Touch up Paint TUP GBK 12 Wire Assembly SP Only 2020 069 Y Standing Pilot Con...

Страница 49: ...______________________________________________________ ________________________________________________________________________________ ________________________________________________________________...

Отзывы: