Heatilator • LEGACY42-IFT Installation Manual • 4095-901 Rev. A
• 12/17
20
A. Pipe Clearances to Combustibles
WARNING! Risk of Fire!
Maintain air space clearance
to vent.
DO NOT
pack insulation or other combustibles:
• Between ceiling firestops
• Between wall shield firestops
• Around vent system
Failure to keep insulation or other material away from
vent pipe could cause overheating and fire.
5
Vent Clearances and Framing
Figure 5.1 Horizontal Venting Clearances To Combustible
Materials
B. Wall Penetration Framing/Firestops
Combustible Wall Penetration
Whenever a combustible wall is penetrated, you must
frame a hole for the wall shield firestop(s). The wall shield
firestop maintains minimum clearances and prevents cold
air infiltration.
• The opening must be framed on all four sides using
the same size framing materials as those used in the
wall construction.
• The LEGACY appliance is supplied with a wall shield
specifically designed for use on the inside of the exte
-
rior wall in which the termination cap is to be located.
A minimum of 1-1/2 in. (38 mm) overlap of attached
heat shields must be maintained.
•
A wall shield (DVP-WS) must be placed on one side
of the interior walls. See Section 7.E for information
regarding the installation of a horizontal termination
cap.
Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by non-com-
bustible materials such as concrete, a hole with diameter
one inch greater than the pipe is acceptable.
Whenever a non-combustible wall is penetrated, the wall
shield firestop is only required on one side and no heat
shield is necessary.
3 in (76 mm)
top clearance
Heat
Shield
Heat
Shield
Wall
Shield
Firestop
1 in (25 mm)
clearance
bottom & sides
Wall
Note
: Heat shields MUST overlap by a minimum of
1-1/2 in. (38 mm).
• SLG heat shield
- designed to be used on a wall
4 in. to 7 in. (102 mm to 178 mm) thick.
•
If wall thickness is less than 4 in., the existing
heat shields must be field trimmed. If wall thick
-
ness is greater than 7 in. a DVP-HSM-B and
SLG-D-EXT will be required.
3 in (76 mm)
top clearance
1 in (25 mm)
clearance
bottom & sides
3 in (76 mm)
top clearance
Heat
Shield
Wall
Shield
Firestop
Wall
1 in (25 mm)
clearance
around
vertical pipe
sections
Exterior Wall Shield*
Slip Section
Termination Cap
*Exterior walls require the use of the wall shield/slip
section assembly supplied with the appliance termina-
tion cap for proper installation.
Use DVP-WS (wall shield) for all interior wall penetra
-
tions
Figure 5.2 Non-Combustible Wall Penetration