31

Heatilator • FL92 Installation Manual • 4012-081 • Rev C • 10/03/13

C. Non-Combustible Sealant Material

  After  completing  the  framing  and  applying  the  facing 

materials over the framing, a bead of noncombustible 

sealant must be used to close off any gaps at the top 

and sides between the fireplace and hearth.

 WARNING! 

Risk of Fire!

  Hearth & Home Technologies is not responsible for 

discoloration,  cracking  or  other  material  failures  of 

finishing materials due to heat exposure or smoke.

  •  Choose finishing materials carefully. 

D. Mantel and Wall Projections

A combustible mantel may be positioned no lower than 

42 1/2 in. (1080 mm) from the base of the fireplace (Fig-

ure 7.10).
The combustible mantel may have a maximum depth of 

12 in. (305 mm). Combustible trim pieces that project no 

more than 1 1/2 in. (38 mm) from the face of the fireplace 

can be placed no closer than 6 in. (152 mm) from the top 

or side of the decorative front. Combustible trim must not 

cover:

•  the metal surfaces of the fireplace

•  where  the  non-combustible  board  is  placed  over  the 

metal surfaces

•  the space between the metal face of the fireplace and 

framing members

7 ft (2134 mm)

minimum

base of fireplace

to ceiling

Combustible Wall

2 x 4 stud wall

Standoffs

Measured from top of fireplace opening

12 in./305 mm

Mantel

1 1/2 in./38 mm

maximum

6 in./152 mm

minimum

14 1/4 in./362 mm

minimum

12 in./305 mm

minimum

Combustible 

Decorative Facing

Non-combustible 

Decorative Facing

such as: Steel, iron,

brick, tile, concrete,

slate, tile, plasters

Seal joint with

non-combustible

sealant

Grid represents 1 in. squares

Figure 7.10  Mantel Specifications

11.92 in.

[303 mm]

FLUSH

FRONT

40 in.

[1016 mm]

36 in.

[914 mm]

(fireplace opening)

12 in.

[305 mm]

50° angle

9 3/4 in.

[248 mm]

4 in.

[102 mm]

BRICK

FRONT

40 in.

[1016 mm]

36 in.

[914 mm]

(fireplace opening

12 in.

[305 mm]

39° angle

Figure 7.11  Mantel Leg, Surround or Wall Projection (acceptable on both sides of opening)

E. Sidewalls/Surrounds

•  Locate  adjacent  combustible  sidewalls  a  minimum  of 

12 in. (305 mm) from fireplace opening.

•  Mantle  leg,  surround,  stub  wall,  whether  combustible 

or non-combustible, may be constructed as shown in 

Figure 7.11.

Содержание FL92

Страница 1: ...ch glass Keep children away CAREFULLY SUPERVISE children in same room as fireplace Alert children and adults to hazards of high temperatures High temperatures may ignite clothing or other flammable ma...

Страница 2: ...ireplace 12 F Protective Metal Hearth Strips 13 G Install Outside Air Kit 14 AK14 AK18 Installation 14 4 Chimney and Termination Requirements A Chimney Requirements 15 B Offsets Returns 16 C Terminati...

Страница 3: ...s with diagrams Chimney installed locked and secured in place with proper clearance Chimney air kit installed Firestops installed Hearth Home Technologies recommends the following Comments communicate...

Страница 4: ...ted as passing ASTM E 136 Standard Test Method for Behavior of Metals in a Vertical Tube Furnace at 750 C C Combustible Materials Materials made of or surfaced with any of the following materials Wood...

Страница 5: ...cap Chimney penetrates roof preferably without affecting roof rafters Offset Return with hanger straps Framing headed off in ceiling joists Enclosed space above and around fireplace Mantel and surrou...

Страница 6: ...uilding codes prior to installation Installation MUST comply with local regional state and national codes and regulations Consult insurance carrier local building inspector fire officials or authoriti...

Страница 7: ...k Location NOT recommended Not the highest point of the roof Wind loading possible Multi level Roofs Windward Leeward Recommended Location Above peak Recommended Insulated exterior chase in cooler cli...

Страница 8: ...fireplace and components from packaging and inspect for damage Vent system components and doors are shipped in separate packages Report to your dealer any parts damaged in shipment Read all the instr...

Страница 9: ...n 76 mm 7 in 178 mm 5 3 8 in 137 mm Gas Knockout Outside Air Cover Plate Electrical Knockout 12 in 305 mm 44 in 1118 mm 47 1 8 in 1197 mm 8 1 4 in 206 mm 42 1 2 in 1080 mm 36 in 914 mm 40 in 1016 mm 2...

Страница 10: ...fire Figure 3 2 Clearances to Combustible Materials Minimum Clearances to Combustibles WITHIN ENCLOSURE AREA Fireplace to backwall 1 2 in 13 mm Top standoffs to header 0 in 0 mm Door opening to sidewa...

Страница 11: ...bs False Ceiling False Ceiling Insulation Insulation Figure 3 3 Chase Assembly 1 2 1 Chimney offset through exterior wall and enclosed in chase 2 Chase constructed on roof Figure 3 4 Chase Constructio...

Страница 12: ...across the top of the fireplace must be above the level of the top standoffs No recess above standoffs Caution Risk of Cuts Abrasions Wear protective gloves and safety glasses during installation She...

Страница 13: ...e of fireplace Overlap strips in the middle of fireplace opening by 1 in 25 mm minimum Metal strips must extend beyond the front and sides of the fireplace opening by at least 2 in 51 mm Figure 3 6 Pr...

Страница 14: ...prevent air infiltration Caution Risk of Fire or Asphyxiation Do not draw outside combustion air from wall floor or ceiling cavity or enclosed spaces such as an attic or garage Do not place outside a...

Страница 15: ...ngth between the offset and return 6 ft 1 83 m Maximum unsupported chimney height above the fireplace 35 ft 10 67 m Maximum unsupported chimney above roof 6 ft 1 83 m Warning Risk of Fire You must mai...

Страница 16: ...m OVERLAP Figure 4 2 Chimney Offset Return Table 4 3 Offset Dimensions Example Your A dimension from Figure 4 2 is 14 1 2 in 368 mm Using Table 4 3 the dimension closest to but not less than 14 1 2 in...

Страница 17: ...lustration above B Gas Termination Cap A Perpendicular Wall If using decorative cap cover s this distance may need to be increased Refer to the installation instructions supplied with the decorative c...

Страница 18: ...chimney sections together firmly to resist movement Ceiling firestops are required where chimney passes through ceiling or floor Support straps for offsets not shown must be secured to adequate frami...

Страница 19: ...to chimney sections Insert the screws provided through the predrilled holes Do NOT penetrate inner flue Secure chimney returns with hanger straps provided fasten to studs or joists Vertical straight r...

Страница 20: ...e same dimensional lumber for framing ceiling firestop and joists 2 in 51mm clearance 2 in 51mm clearance Warning Risk of Fire Do NOT seal area between firestop opening and chimney pipe except where t...

Страница 21: ...ulation Shield F Install Attic Insulation Shield Warning Risk of Fire You MUST install an attic insu lation shield when there is any possibility of insulation or other combustible material coming into...

Страница 22: ...26 ga min Galvanized Chase Top Figure 5 9 Chase Top Construction H Install Chase Chase Top You MUST use a chase top in a chase installation Chase tops are available from your Heatilator dealer or may...

Страница 23: ...pe and storm collar chase top Do NOT block air holes 3 clip brackets Slip over chase collar and attach with screws provided Termination cap pipe and chimney section must overlap 1 1 2 in 38 mm Assembl...

Страница 24: ...m above top of chase and 7 in 178 mm below top of chase 2 in 51 mm 7 in 178 mm Figure 5 13 Installing a TCT1175 Terra Cotta Cap Storm Collar Chimney Pipe Chase Top Termination Cap not shown Chase 14 1...

Страница 25: ...d shroud designs have been tested for HHT fireplace systems and termination caps 3 in 76 mm minimum Min Base Dim Min Base Dim Min Top Dim Min Top Dim Min Opening Width Min Opening Width Radiation Shie...

Страница 26: ...nation Cap Chase Top Radiation Shield 3 in 76 mm Radiation Shield Height Termination Cap Figure 6 5 Roofed Style Shroud Dimensions 3 Roofed Style Shroud Radiation shield required 2 Mailbox Style Shrou...

Страница 27: ...facing to prevent cold air leaks Large gaps can be bridged with fiberglass rope gasket Only non combustible materials may be used to cover the metal fireplace front Metal strips are placed 2 in 51 mm...

Страница 28: ...uctivity of heat Refer to the formula in Table 7 1 to convert a k value to an R value Refer to Table 7 2 for hearth extension insulation alternatives Warning Risk of Fire Hearth extensions are to be i...

Страница 29: ...on Raised to Bottom of Firebox Opening Non combustible flooring a minimum of 20 in 508 mm in front of and 12 in 305 mm to each side of the fuel opening is required The hearth framing must be construct...

Страница 30: ...ng Material 20 in minimum Hearth Extension 1 2 in Micore or equivalent insulation Note The bottom of the grill is 5 3 4 in 146 mm above the bottom of the fireplace Finished hearth must NOT extend abov...

Страница 31: ...urfaces of the fireplace where the non combustible board is placed over the metal surfaces the space between the metal face of the fireplace and framing members 7 ft 2134 mm minimum base of fireplace...

Страница 32: ...tion A Gas Log Lighter Provision Warning Fire and or Asphyxiation Risk Use with solid wood fuel or decorative gas appliance only Gas fire generates fumes DO NOT install unvented gas logs Damper must b...

Страница 33: ...eiling Firestop 30 deg AS10 Straight Attic Insulation Shield 24 in 610 mm JB577 Chimney Joint Band CB576 Chimney Bracket RF570 Roof Flashing Flat to 6 12 Pitch RF571 Roof Flashing 6 12 to 12 12 Pitch...

Страница 34: ...3 in 330 mm JB577 Chimney Joint Band 2 in 51 mm 13 in 330 mm A B 17 in 432 mm RF570 Roof Flashing RF571 Roof Flashing 39 7 8 in 1013 mm 28 in 711 mm 15 1 4in 387 mm 25 1 4 in 641 mm 29 in 737 mm 15 1...

Страница 35: ...8 in 822 mm 34 3 8 in 873 mm 23 in 584 mm 19 in 483 mm 15 5 8 in 397 mm 9 3 8 in 238 mm 10 1 4 in 260 mm 17 in 432 mm 20 in 508 mm 31 3 4 in 806 mm 34 5 8 in 879 mm TV11T Round Termination Cap B A C B...

Страница 36: ...3 Hearth Extension B Optional Components A B C D LDS33 LDS46 Decorative Shroud E D A C B LDS BV Decorative Shroud Catalog A B C D in mm in mm in mm in mm LDS33 36 914 36 914 8 5 216 11 279 LDS46 48 12...

Отзывы: