10
The most important consideration which must be taken into account when deciding
upon the location of air-cooled equipment is the provision for a supply of ambient
air to the condenser, and removal of heated air from the condensing unit or remote
condenser area. Where this essential requirement is not adhered to, it will result in
higher head pressures, which cause poor operation and potential failure of equipment.
Units must not be located in the vicinity of steam, hot air or fume exhausts. Corrosive
atmospheres require custom designed condensers.
Another consideration which must be taken is that the unit should be mounted away
from noise sensitive spaces and must have adequate support to avoid vibration
and noise transmission into the building. Units should be mounted over corridors,
utility areas, rest rooms and other auxiliary areas where high levels of sound are
not an important factor. Sound and structural consultants should be retained for
recommendations.
Space and Location Requirements for Condensing Units and Remote Condensers
Units in Pits
The top of the unit should be level with the top of the pit, and side distance
increased to “2W”.
If the top of the unit is not level with the top of pit, discharge cones or stacks
must be used to raise discharge air to the top of the pit. This is a minimum
requirement.
Decorative Fences
Fences must have 50% free area, with 1 foot undercut, a “W” minimum
clearance, and must not exceed the top of unit. If these requirements are
not met, unit must be installed as indicated for “Units in pits”.
Walls or Obstructions
The unit should be located so that air may circulate freely and not be
recirculated. For proper air flow and access all sides of the unit should be a
minimum of “W” away from any wall or obstruction. It is preferred that this
distance be increased whenever possible. Care should be taken to see that
ample room is left for maintenance work through access doors and panels.
Overhead obstructions are not permitted. When the unit is in an area where it is
enclosed by three walls the unit must be installed as indicated for units in a pit.
Multiple Units
For units placed side by side, the minimum distance between units is
the width of the largest unit. If units are placed end to end, the minimum
distance between units is 4 feet.
Walls or Obstructions for Horizontal Air Flow
Multiple Units with Horizontal Air Flow
* “W” = Total width of the condensing unit or condenser.
Space & Location Requirements for Air Cooled Condensing Units and Remote Condensers
Condensing Unit Installation
Содержание Mohave
Страница 13: ...13 Piping The following are examples of proper piping layout for typical system configurations...
Страница 14: ...14 Piping...
Страница 38: ...38 Standard Independent Evaporator Power Supply with VFD Condenser Fans Wiring Diagram...
Страница 39: ...39 Standard Independent Evaporator Power Supply with VFD Condenser Fans Wiring Diagram...
Страница 45: ...45 Defrost Operation Black Piping Inactive Gray Piping Active Hot Gas Defrost Cycle Diagrams...
Страница 46: ...46 Defrost Operation Black Piping Inactive Gray Piping Active Hot Gas Defrost Cycle Diagrams...
Страница 75: ...75 Notes...