Heatcraft H-IM-SCU Скачать руководство пользователя страница 11

11

© 2015 Heatcraft Refrigeration Products, LLC

Check Out and Start Up

1.  After the installation has been completed, the following points should be 

covered before the system is placed in operation: 

2.  Check all electrical and refrigerant connections.  

Be sure they are all tight.

3.  Check compressor mounting fasteners for tightness.
4.  Check microprocessor for operation of high and low pressure controls, 

pressure regulating valves, oil pressure safety controls, and all other safety 
controls, and adjust if necessary.

5.  Wiring diagrams, instruction bulletins, etc., attached to the  

 

 

condensing units should be read and filed for future reference. 

6.  All fan motors should be checked for proper rotation. Fan  

 

 

motor mounts should be carefully checked for tightness and  

 

 

proper alignment. 

7.  Electric evaporator fan motors should    

 

 

be temporarily wired for continuous operation until    

 

 

the room temperature has stabilized.

8.  Observe system pressures during charging and initial operation.    

 

Do not add oil while the system is short of refrigerant  

 

 

unless oil level is dangerously low.

9.  Continue charging until system has sufficient refrigerant for  

 

 

proper operation. Do not overcharge.  

 

 

 

 

Remember that bubbles in a sight glass may be caused by  

 

 

a restriction as well as a shortage of refrigerant.

10.  Do not leave unit unattended until the system has    

 

 

reached normal operating conditions and the oil  

 

 

 

charge has been properly adjusted to maintain the oil 
within lower sight glass range.

11.  Make sure all Schrader valve caps are in place and tight.
12.  Make sure ALL service valves are properly back-seated and tighten  

 

valve packing if necessary.

Operational Check Out

After the system has been charged and has operated for at least two hours at normal 
operating conditions without any indication of malfunction, it should be allowed to 
operate overnight on automatic controls. Then a thorough recheck of the entire system 
operation should be made as follows:

1.  Check compressor discharge and suction pressures. If not within system 

design limits, determine why and take corrective action.

2.  Check liquid line sight glass and expansion valve operation. If there are 

indications that more refrigerant is required, leak test all connections and 
system components and repair any leaks before adding refrigerant. 

3.  Observe oil level in compressor crankcase sight glass. Add oil as   

 

within lower sight glass range. 

4.  Thermostatic expansion valves must be checked for proper superheat settings. 

Feeler bulbs must be in positive contact with the suction line and should  

 

be insulated. Valves set at high superheat will lower refrigeration capacity. Low 
superheat promotes liquid slugging and compressor bearing washout.

5.  Using suitable instruments, carefully check line voltage and amperage at the 

compressor terminals. Voltage must be within 10% of that indicated on the 
condensing unit nameplate. If high or low voltage is indicated, notify the power 
company. If amperage draw is excessive, immediately determine the cause    
and take corrective action. On three phase motor compressors,    

 

check to see that a balanced load is drawn by each phase. 

6.  The maximum approved settings for high pressure controls on    

 

our air cooled condensing equipment is 425 psig. On air cooled    

 

systems, check as follows:  
Disconnect the fan motors or block the condenser inlet air. Watch  

 

high pressure gauge for cutout point. Recheck all safety and  

 

 

operating controls for proper operation and adjust if necessary. 

7.  Check drain pan for proper drainage.
8.  Check winter head pressure controls for pressure setting.
9.  Check oil sump heater operation

10.  Install instruction card and control system diagram for use of building manager 

or owner.

System Balancing - Compressor Superheat

IMPORTANT:  

In order to obtain the maximum capacity from a system, and to ensure 

trouble-free operation, it is necessary to balance each and every system.

This is extremely important with any refrigeration system.
The critical value which must be checked is suction superheat.
Suction superheat should be checked 

at the compressor

 as follows:

1.  Measure the suction pressure at the suction service valve of the compressor 

and determine the saturation temperature corresponding to this pressure from 
a “Temperature-Pressure” chart.

2.  Measure the suction temperature of the suction line about one foot back from 

the compressor using an accurate thermometer.

3.  Subtract the saturated temperature from the actual suction line temperature. 

The difference is superheat.

Too low a suction superheat can result in liquid being returned to the compressor. This 
will cause dilution of the oil and eventual failure of the bearings.

Too high a suction superheat will result in excessive discharge temperatures which 
cause a break down of the oil and results in wear, and damage. 

It should also be remembered that the system capacity decreases as the suction 
superheat increases. For maximum system capacity, suction superheat should be 
kept as low as is practical. We recommend that the superheat 

at the compressor

 be 

between 5˚F and 15˚F.

If adjustments to the suction superheat need to be made, the expansion valve at the 
evaporator should be adjusted.

CAUTION:

 

Check phase rotation with phase meter prior to first start.  

Warranty will be denied if damage is a result of reverse rotation. Extreme care 

must be taken in starting compressors for the first time after system charging. 

At this time, all of the oil and most of the refrigerant might be in the compressor 

creating a condition which could cause compressor damage due to slugging. 

Activating the crankcase heater for 24 hours prior to start-up is required. 

NOTE:

 All adjustable controls and valves must be field adjusted to meet 

desired operation. There are no factory preset controls or valve adjustments. 

This includes low pressure, high pressure, adjustable head pressure systems 

and expansion valves.

Содержание H-IM-SCU

Страница 1: ...actices 5 Refrigeration Pipe Supports 5 Suction Lines 6 Liquid Lines 6 Unit Cooler Piping 6 Line Sizing Tables 7 9 Evacuation and Leak Detection 10 Refrigerant Charging Instructions 10 Field Wiring 10...

Страница 2: ...above except that motor compressor replacements or exchanges shall be made through the nearest authorized wholesaler of the motor compressor manufacturer not at SELLER s factory and no freight shall b...

Страница 3: ...mum distance between units is the width of the largest unit If units are placed end to end the minimum distance between units is 4 feet Units in Pits The top of the unit should be level with the top o...

Страница 4: ...ntroduced above the liquid in the receiver tank The receiver discharge is regulated by the ORI valve Operation and Adjustment Condensing units with dual valves require sufficient charge to partially f...

Страница 5: ...he system as supplied by Heatcraft Refrigeration Products was thoroughly cleaned and dehydrated at the factory Foreign matter may enter the system by way of the evaporator to condensing unit piping Th...

Страница 6: ...runs to provide superheat at the compressor Pipe size example Given 30 F Cooler with one system having 2 evaporators One condensing unit rated at 350 000 BTUH s 20 F SST R404A refrigerant Two evapora...

Страница 7: ...0 09 0 13 1 2 R507 404A R407C 6 4 0 58 0 16 0 24 5 8 R507 404A R407C 10 3 0 93 0 25 0 35 7 8 R507 404A R407C 21 2 1 92 0 51 0 72 1 1 8 R507 404A R407C 36 1 3 27 0 86 1 24 1 3 8 R507 404A R407C 55 0 4...

Страница 8: ...3 8 1 3 8 1 3 8 7 8 1 1 8 1 1 8 1 1 8 1 3 8 1 3 8 1 3 8 7 8 1 1 8 1 1 8 1 1 8 1 3 8 1 3 8 1 3 8 72000 7 8 1 1 8 1 1 8 1 1 8 1 3 8 1 3 8 1 3 8 7 8 1 1 8 1 1 8 1 1 8 1 3 8 1 3 8 1 3 8 7 8 1 1 8 1 1 8 1...

Страница 9: ...8 1 5 8 1 5 8 1 5 8 1 5 8 1 1 8 1 3 8 1 3 8 1 5 8 1 5 8 1 5 8 1 5 8 120000 1 3 8 1 3 8 1 5 8 1 5 8 1 5 8 2 1 8 2 1 8 1 3 8 1 5 8 1 5 8 1 5 8 2 1 8 2 1 8 2 1 8 150000 1 3 8 1 5 8 1 5 8 1 5 8 2 1 8 2 1...

Страница 10: ...er evacuation Do not turn off vacuum pump when connected to an evacuated system before closing shut off valve The vacuum pump should be operated until a pressure of 1 500 microns absolute pressure is...

Страница 11: ...n the condensing unit nameplate If high or low voltage is indicated notify the power company If amperage draw is excessive immediately determine the cause and take corrective action On three phase mot...

Страница 12: ...ns to keep the condensing unit s within the control zone d If the supply air temperature is below the control zone and if the Supply Air Temp Rate of Change ROC is not indicating the supply air temper...

Страница 13: ...correct the problem and reset the unit using the Lckout RST from the Menu on the MAGNUM s key pad 10 If the compressor relay output is turned on either by computer or manual the compressor safeties a...

Страница 14: ...RATURE TEMPERATURE STATUS STATUS Page Up Page Down 09 55 CMP 1 45 54 CMP OFF READY 000 00 42 SST SSH SCT DSH 38 16 9 97 79 2 PG PG HH MM CIRCUIT LEV ENT CURRENT CONTROL STATE TIME IN CURRENT STATE SAT...

Страница 15: ...ts menu option shows the first 4 Sensor Inputs Pressing the Page Down button shows the next 4 Relay Outputs ACTUAL DISPLAY GETTING STARTED MANUAL REVISION 2 4 Pressing the Page Down button shows the f...

Страница 16: ...option shows the first 4 setpoints Selecting the Graphs menu option shows the following Continue pressing the Page Down or Page Up buttons to scroll through all the Alarm screens GRAPHS Selecting the...

Страница 17: ...menu Selecting the Lckout RST menu option shows the following Pressing the down arrow shows the rest of the submenu options ACTUAL DISPLAY GETTING STARTED MANUAL REVISION 2 4 Pressing the Page Down bu...

Страница 18: ...excess 3 Open valve 4 Check electrical circuit 5 Adjust 6 Clean Low discharge pressure 1 Faulty condenser temperature regulation 2 Suction shutoff valve partially closed 3 Insufficient refrigerant in...

Страница 19: ...t option Press enter 1st SI and offset appears i e Suction 1 0 0 Scroll using increase decrease keys to find sensor to calibrated Press enter use the increase decrease keys to change calibration value...

Страница 20: ...hat was installed cannot be initialized and therefore cannot be used Replace the Compact Flash card with one that works BATTERY FAILED Generated when Magnum is not getting power from the Battery User...

Страница 21: ...lgorithm incorporates a number of safety checks based on setpoints preventing unsafe conditions that could potentially cause damage to the system When a safety trips the circuit will be in a SAFETY TR...

Страница 22: ...CHECKED If the discharge temperature analog input rises above the value of the setpoint or the digital input turns ON for the time specified in the Time sec field the compressor will be Locked Out and...

Страница 23: ...nections are secure tighten if necessary Check operation calibration of all fan cycle and defrost controls when used Look for abnormal accumulation of ice patterns and adjust defrost cycles accordingl...

Страница 24: ...5V GRD GRD 5V S1 5V 5V GRD GRD S1 S1 5V GRD 5V 5V S1 GRD GRD S1 5V 5V S1 GRD GRD S1 5V WHITE BLACK SHIELD TEMP 1 SHIELD BLK TRANSDUCER WHITE DISCHARGE 1 RED GRD M1 ANALOG T1 100 M2 ANALOG T1 500 M3 AN...

Страница 25: ..._________________________________________________________________________________ _______________________________________________________________________________________ ______________________________...

Страница 26: ...s should be obtained from your local InterLink wholesaler Replacement parts which are covered under the terms of the warranty statement on page 2 of this manual will be reimbursed for total part cost...

Отзывы: