Smart Controller
•
Check all wiring connections to be sure they are correct and
tight.
•
On the condensing units
-
Check the low pressure switch setting on freezer
units. Refer to H-IM-CU (Available on website). On
some condensing units, the low pressure switch has
a fixed setting and cannot be adjusted
•
Turn power on.
•
On the MASTER evaporator
- DO NOT REMOVE the room sensor.
MULTIPLE SYSTEM CONNECTION
(See Smart Controller instruction manual for more details)
•
On the SLAVE evaporators. All Heatcraft Quick Response
Controller boards are shipped with the factory default as a
“
MASTER
”
evaporator.
-
Each SLAVE evaporator must be changed to identify it as a
SLAVE. Use the
“
PROGRAM REVIEW
”
button to scroll until
“
SLA
”
appears,then use the
“
SELECT
”
knob to select
“
YES
”
then press
“ENTER.”
•
Use the Smart Controller to set system parameters.
See Heatcraft Smart Controller installation instructions for
more details.
S
S
S
M
S
S
S
M
S
S
S
M
M
S
S
S
SMART
CONTROLLER
SYSTEM 1
SYSTEM 2
SYSTEM 3
SYSTEM 4
M
= Master Evaporator
S
= Slave Evaporator
If a remote interface is needed, the Quick Response Controller can be used with a Remote Refrigeration Controller (RRC) via Smart Controller
with the following limitations:
• Remote Refrigeration Controller (RRC) cannot directly turn off ON/OFF Demand Defrost. To set Demand Defrost remotely, set 'Smart
Defrost' to ON and remove all set defrost times.
• Compressor runtime and compressor cycles will not be accurate.
Wiring:
• Low voltage wiring must be 18 gauge minimum. For low voltage wiring, maximum distances from the Smart Controller to the Master
evaporator Quick Response Controller board is 1000ft.
Multiple Systems With Multiple Evaporators (Requires A Smart Controller)
Содержание H-IM-QRC
Страница 28: ...28 Wiring 24 VOLT CONNECTION WIRING HEATCRAFT QUICK RESPONSE CONTROLLER master with one slave connection ...
Страница 29: ...29 Wiring 24 VOLT CONNECTION WIRING HEATCRAFT QUICK RESPONSE CONTROLLER master with three slave connection ...
Страница 31: ...31 Wiring TYPICAL ELECTRIC DEFROST WIRING DIAGRAM ...
Страница 37: ...37 Notes ...
Страница 38: ...38 Notes ...
Страница 39: ...39 Notes ...