Beacon II Troubleshooting Guide
Diagnostics
PROBLEM
Step ACTION ITEM
IF OK
IF NOT OK
1.
Check Primary Power Supply Disconnect
1. Check fuses and circuit breakers
2.
Check Voltage to Evaporator Transformer
Go to
2. Check field wiring for breaks
LED is not lit.
3.
Check Transformer Secondary Output Volts
next step
3. Replace if necessary
4.
Check Voltage at Control Board (24V and C)
4. Check factory wiring and connections
5.
Replace Control Board
1.
Check Compressor internal overloads
1. Wait for reset
LED shows Coo, but
Go to
compressor will not run.
2.
Check Compressor Contactor Coil Voltage
next step
2. Check internal condensing unit wiring
3.
Check Compressor Contactor “pulled in”
3.. Replace as needed
ERROR CODES:
E1 Room Sensor
Check Sensor and Board Connection
Replace as needed
E2 Defrost Sensor
Check Sensor and Board Connection
Replace as needed
E3 Suction Sensor
Check Sensor and Board Connection
Replace as needed
E4 Suction Transducer
Check Transducer and Board Connection
Replace as needed
E5 Outdoor Sensor
Check Sensor, wiring and Board Connection
Replace or remove
1.
Check Refrigerant Type
1. Compare board setpoint and refrigerant
2.
Check coil for ice
2. Defrost coil and check defrost cycle settings/
setpoints, defrost sensor and heater amps.
E6 Low Superheat
3.
Check Control Board step position from
3. Replace board if EEV steps not at 2.
During Cooling
board LED
Go to
4. Pumpdown system see if LPS opens or if it
(0°F for 2 minutes)
4.
Check Electric Expansion Valve Closure
next step
times out (EEV is bad or LPS is set incorrectly, if
times out) – See Pumpdown.
5.
Compressor Not Operating
5. Check overloads and contactor.
6.
Check Suction Temperature Sensor
6. Compare board sensor reading against actual
suction line temperature.
7.
Check Suction Pressure Transducer
7. Compare pressure reading against gauges.