Heat & Glo LifeStyles Collection • Montana US-CAN • 4039-156 Rev D • 10/08
20
2 in. (51 mm) min. collar
6 in. (152mm) min.
2 in. (51 mm) min.
Storm Collar
Flashing Collar
Minimum 1-1/2 in. (38 mm) overlap of cap over pipe
Figure 6.4 Installing a TR11/TR444 Round Termination Cap
Storm Collar
Flashing Collar
Top of Pipe
14-1/2 in. (368mm) max.
1-1/2 in. (38 mm) min.
overlap
2 in. (51 mm) min.
Figure 6.5 Installing a TR11T/TR442 Round Telescoping Termina-
tion Cap
Note:
To protect against the effect of corrosion on those
parts exposed to the weather, the termination cap can be
painted with a rust-resistant paint.
Fire Risk
• The minimum overlap of cap to pipe
MUST be met or chimney may separate
from cap.
Separation allows sparks, heat and embers
to escape.
WARNING
C. Install the Termination Cap
•
For installations utilizing a TR11T/TR442 Round
Telescoping Termination Cap, the uppermost chimney
section must be below the top of the chase top, but not
more than 14-1/2 in. (368 mm) below the top of the chase
top. Minimum overlap of chimney and termination cap
must be 1-1/2 in. (38 mm). See Figure 6.5.
•
Install the chimney sections up through the chase
enclosure. When using a TR11/TR444 Round Termination
Cap, the uppermost top section of pipe must extend 6 in.
(152 mm) above the top of the
fl
ashing collar to allow
installation of the storm collar and termination cap. See
Figure 6.4.
2 in. (51 mm) min.
4-1/2 in.
(114 mm)
max.
1-1/2 in.
(38 mm) min.
overlap
Cap Standoff
Top of Pipe
Flashing Collar
Figure 6.6 Installing an ST1175 Square Termination Cap
The last section of pipe
must stop between the
distances given below.
2 in. (51 mm) above top
of the chase.
7 in. (178 mm) below top
of the chase.
{
Top of Pipe
1-1/2 in. (38 mm)
min. overlap
Figure 6.7 Installing a TCT1175 Terra Cotta Cap (available in US
only)
•
For installations utilizing an ST1175 Square Termination
Cap the last chimney section must not be more than
4-1/2 in. (114 mm) below the chase top. See Figure 6.6.
•
For installations utilizing an TCT1175 Terra Cotta Cap the
last chimney section must be between 7 in. (178 mm) below
the chase top and 2 in. (51 mm) above. See Figure 6.7.
•
For chase installations you can use a TR11/TR444 Round
Termination Cap, a TR11T/TR442 Round Telescoping
Termination Cap, an ST1175 Square Termination Cap, or
a TCT1175 Terra Cotta Termination Cap.
•
Install termination caps following instructions provided
with them.