SERVICE
• The complete unit, including heat exchanger, combustion chamber and burner should be
cleaned from dust and dirt after every heating period, at a minimum of once per year.
-Removal of combustion chamber/heat exchanger:
For proper cleaning of the unit, manufacturer recommends removal of the access
panel of the heat exchanger. Clean combustion chamber and exchanger tube with
brush. Vacuum all loose ash and soot. Close all cleaning flanges carefully to avoid damage to
gasket material.
-Disassembling of burner:
1. Disassemble two tightening nuts on the combustion chamber flange and remove burner from
mounting flange. Take care not to damage the flange gasket.
2. Pull out the burner. Take care not to damage the burner head and power cable. Clean blower
wheel, ignitor electrode and flame sensor. Inspect the inside of the combustion
chamber.
8
Содержание VF600
Страница 10: ...9 REFERENCE CHARTS ...
Страница 11: ...10 Propane Orifice Kit PN BIE 3000886 Natural Gas Orifice PN BIE 3006703 ...
Страница 13: ...WIRING CHART 12 ...
Страница 14: ...13 PARTS BREAKDOWN ...
Страница 16: ...15 SPARE PARTS BREAKDOWN VG900 VG600 VG700 ...
Страница 18: ...17 RIELLO BURNER WIRING either 120V or 240V control systems ...
Страница 19: ...18 RIELLO BURNER COMBUSTION HEAD ...
Страница 20: ...19 RIELLO BURNER AIR GATE ...
Страница 21: ...20 RIELLO BURNER COMBUSTION CHAMBER ...
Страница 22: ...21 RIELLO BURNER START UP ...
Страница 23: ...22 RIELLO BURNER DIAGNOSTICS ...
Страница 24: ...23 RIELLO BURNER TROUBLESHOOTING ...
Страница 25: ...VF600 OIL FIRED BURNER ELECTRODE SETTING 24 ...
Страница 26: ...VF600 OIL FIRED BURNER AIR ADJUSTMENT 25 ...
Страница 27: ...VF600 OIL FIRED BURNER PARTS BREAKDOWN 26 ...
Страница 28: ...342 N Co Rd 400 East Valparaiso IN 46383 219 464 8818 Fax 219 462 7985 www heatwagon com ...