12
PREPARATION
MAX
8.00"
COLD IN
VALVE
SPARCO AQUAMIX SHOWN.
TANK
PHOENIX WITH AIR HANDLER
PREVENTER
EXPANSION
INLET
VALVE MANUFACTURER
COLD WATER
HOT WATER OUTLET
NOTES:
DRAIN
must install a spring check valve)
FOR OTHER VALVES, CONSULT
GAS
AUXILIARY
CONNECTION
WITHOUT a check valve, you
HOT OUT
BACKFLOW
BALL VALVE
CIRCULATOR WITH
INTREGAL CHECK VALVE
(if you are installing a circulator
AUXILIARY
CONNECTION
1. Minimum pipe size should match connection size on Phoenix. If you require greater flow, upsize the pipe accordingly.
2. A Thermal Expansion tank suitable for potable water must be sized and installed within this piping system between the
backflow preventer and the cold water inlet of the Phoenix.
3. Gas line must be rated to the maximum input capacity of the unit. Unit must have 10 feet of pipe after gas regulator.
4. All circulators shall have an integral flow check.
AIR HANDLER UNITS
MOUNTED TO CEILING
*
*
CHECK WITH AIR HANDLER MANUFACTURER
FOR PROPER SIZING.
LP-179-L
7/13/07
PHOENIX WITH AIR HANDLERS ABOVE
NOTE:
This drawing is meant to show system piping only. The installer is responsible for all
equipment and detailing required by local codes.