12
Multi-MOD Platinum with Space and Scheduling Installation and Operation Manual
HT# 059299-00
A
INSTAllATION
MOuNTING THe eNClOSuRe
• Select a location near the equipment to be
controlled .
• The surface should be flat, sufficiently wide, and
strong enough to hold the Multi-MOD .
• Installation location should be away from extreme
heat, cold, or humidity .
• Remove the control from its enclosure by removing
the top center screw and loosening the two bottom
screws .
• Screw the enclosure to the surface through the
mounting holes in the back of the enclosure .
• Return the panel to the enclosure . Replace the top
screw and tighten the bottom two screws .
WARNING
Use existing the Enclosure Knockouts .
DRILLING HOLES THROUGH THE CONTROL
ENCLOSURE VOIDS CONTROL WARRANTY .
Mounting Holes
Communication
Knockout
Wiring
Knockouts
Enclosure
Lock
ACTIVATe THe BATTeRY
• Turn the Multi-MOD Platinum panel over to reveal the
piggyback circuit board (CPU board) .
• Remove the plastic strap the covers the battery . The contacts
should be touching the battery .
AleRT
Do not install the battery unless you plan to power the control at once .
If the control is not powered, the battery will lose its charge in 100 days .
N
5V
8V
CPU Board
Battery
Ethernet
RS485
Main Board
Control Stages
A & B
Control Stages
C & D
A1
G1
B1
A2
G2
B2
RS485
Communication Board
(HT# 900234-20-XXX)
ReMOTe COMMuNICATION WIRING
• If a control is ordered as a standard control, it can be field
upgraded to have communication by adding the appropriate
upgrade kit . A new CPU board and a communication board will
be included in any of the Upgrade Kits .
Communication upgrade kit
Part #
Multi-MOD Internet Upgrade Kit
900204-20-RINet
Multi-MOD BACnet IP or MSTP Upgrade Kit
900204-20-BAC
Multi-MOD Modbus Upgrade Kit
900204-20-BUS
BACNeT MSTP OR MODBuS RS485 WIRING
• All Communication to Modbus RTU or BACnet MSTP must use
the RS485 on the control's Communication Board .
N
5V
8V
CPU Board
Battery
Ethernet
RS485
Main Board
Control Stages
A & B
Control Stages
C & D
A1
G1
B1
A2
G2
B2
RS485
Communication Board
(HT# 900234-20-XXX)
Connect to BACnet MSTP
Network
or MODBUS R
TU Network
RS485 Cable