MPCQ Platinum Installation and Operation Manual
35
BACnet Communication
(Requires BAC Package)
•
The MPCQ platinum BAC is designed to communicate over a BACnet IP network.
•
If the MPCQ Platinum was purchased with a BACnet communication package, some of the
following settings must be configured to guarantee proper communication.
BACnet Communication Option
SELECT:
MENU/<System Settings>/<more Settings>/Remote Interface/Network Settings
• After connecting the MPCQ Platinum to the BACnet network, see Wiring the BACnet
Communication on page 13, the user must set the following parameters according the BACnet
Network Administrator's instructions.
--NETWORK SETTINGS-
BACnet ID:
0
IP:
---.---.---.---
Msk:
---.---.---.---
Gwy:
---.---.---.---
BACnet Device ID
• This is a unique ID within the BACnet network. It must be provided by the BACnet Network
Administrator and entered into the
BACnet ID
field. The value must not be 0.
IP, Mask, and Gateway Address
• These fields are either left blank if the IP information is automatically provided by the network (DHCP server assigns IPs).
Otherwise, fill in these information as per the Network Administrator instructions
ALERT
A MPCQ Platinum that is BACnet capable will display -- NETWORK PANEL --
on the 2nd row of the display when it is in screen saver mode.
MPCQ Platinum BACnet Variable List
The following is the BACnet variable list that can be used to communicate with the MPCQ Platinum.
OBJ ID
OBJECT NAME
DESCRIPTION
TYPE*
UOM
RANGE
READ
ONLY
0
BOOSTADJ
Vari-Boost
Adjustment
AV
none (95)
0.1 - 6.4
100
BOOSTMODE
Boost Mode
MV
1=Disabled, 2=Manual, 3=Vari, 4=Vari+ESD
200
BOOSTTIME
Manual Boost Time
AV
Minutes(72)
0 – 120
300
BPTIME
Bypass Time
AV
Minutes(72)
0 - 2,147,483,647
X
400 through
431
BSTATUS
Boiler Status
MV
1=Off, 2=On1=Off, 2=Low, 3=High1=Off,
2=Low, 3=Med, 4=High1=Off, 2=Low, 3=MLow,
4=MHigh
X
500
BTYPE
Boiler Type
MV
1=On/Off, 2=2-Stage3=3-Stage, 4=4-Stage
600
BYPASSMODE
Bypass Mode
BV
0=AUTO, 1=ON
700
CLENGTH
Cycle Length
AV
Minutes(72)
10 - 240
800 through
831
COMERR00 through
COMERR31
Communication
Error
BV
0=“”, 1=C/E
X
900
DADJUST
Day Heat
Adjustment
MV
1=A, 2=B, 3=C, 4=D, 5=E, 6=F, 7=G, 8=H, 9=I,
10=J, 11=K, 12=L,13=M, 14=N, 15=O, 16=P
1000
DCUTOFF
Outdoor Day
Cutoff
AV
°C(62), °F(64)
-6 - 38, 20 - 100
1100
DLS
Day Light Saving
BV
0=Enable, 1=Disable
1200
FAULTMODE
Sensor Fault Mode
BV
0=OutputOn,1=OutputOff
1300
INMODE
Sensor Mode
BV
0=°F, 1=°C
1400
LEAD
Lead Boiler
MV
(Refer to Table 2)
1500 through
1531
LOCK00 through
LOCK31
Lockout Input
BV
0=(inactive),1=L/O,
X
1600
LOGIC
Logic Mode
BV
0-PID
1700
LSTHOLD
Last Stage Hold
AV
psi(56)
0 – 5 psi