Mini-MOD & Mini-Extension Installation Manual 31
059040-00 C
temperature sensor chart
teMperature
value
(in ohms)
°
f
°
c
OPEN
150000
-30
-34
117720
-20
-29
82823
-10
-23
59076
0
-18
42683
10
-12
31215
20
-7
23089
25
-4
19939
30
-1
17264
35
2
14985
40
4
13040
45
7
11374
50
10
9944
55
13
8714
60
16
7653
70
21
5941
80
27
4649
90
32
3667
100
38
2914
110
43
2332
120
49
1879
130
54
1524
140
60
1243
150
66
1021
160
71
842
170
77
699
180
82
583
190
88
489
200
93
412
210
99
349
220
104
297
230
110
253
240
116
217
250
121
187
SHORT
100
troublesHootIng
sensor Inputs
display shows sensor open or sHort
When OPEN, Check the sensor is connected and the wires are continuous to the Mini-MOD. Finally follow the procedure for
Incorrect Temperature Display. When SHORT Remove the wires from the sensor terminals. The display should change to read
OPEN. If it does not, the Mini-MOD may be damaged.
display shows an Incorrect temperature
Remove the wires from the sensor terminals. The display should change to read OPEN. If it does not, the Mini-MOD may be
damaged. Take an ohm reading across the detached sensor wires. The ohm reading should correspond to the Temperature sensor
Table. If it does not, the sensor may be damaged.
control operatIon
no Heat
• Season
- Make sure that the Season is set to Winter. See "Display Messages" on page 28.
• Prove
- Even though, the system relay may be energized, the Mini-MOD will not energize and
stage relays unless the Prove is shorted. See "Display Messages" on page 28..
• Shutdown
- The Mini-MOD will only activate stage outputs when the Shutdown terminals are
opened. See "Display Messages" on page 28.
• Tstat
- The Mini-MOD will only activate stage outputs when the Tstat terminals are shorted.
See "Display Messages" on page 28.
• Sensor Fault
- When the Sensor Fault is set to All Off in the startup menu (See "Sensor Fault"
on page 19.), the System sensor fault (in all Sensor Type modes) or the Outdoor sensor fault (in
Reset mode) will de-energize all stage relays. Check the display for sensor values.
• System or Outdoor Sensor
- If the System or Outdoor sensor reading was higher that the actual
temperature, the Mini-MOD might not bring any stage on. Check "Display shows an Incorrect
Temperature" section.
too Much Heat
• Domestic Hot Water call
- The Mini-MOD will raise the temperature of the system to the DHW
Set Point on a DHW call, connected to terminals 29 and 30. Check to see if there is a call for
DHW and the length of time it lasts.
• Reset Ratio and Offset
- If excessive heat occurs only in certain weather conditions, adjust the
Reset Ratio and Offset. See "Understanding Operation Concept" on page 5. If excessive heat
occurs year round, reduce the Offset.
• Boiler Mode Settings
- The Mini-MOD will only modulate boilers with their mode set to Auto
or Standby. Check if any boiler stage is set to Manual or On. See "Mode" on page 29.
• Control Settings
- The Last Stage Hold will allow only the Lead boiler to stay on for an
additional number of degrees. If the setting is too high, and only the Lead boiler is on, the
system can over heat. Reduce the Last Stage Hold setting. See "Last Stage Hold" on page 24.
too little Heat
• Reset Ratio and Offset
- If reduced heat occurs only in certain weather conditions, adjust the
Reset Ratio and Offset. See "Understanding Operation Concept" on page 5. If reduced heat
occurs year round, increase the Offset.
• Setback and Day/Night Schedule
- If reduced heat occurs only during specific hours, check the
Day/Night Schedule and the Setback values. Then, reduce the Setback setting.
• Boiler Mode Settings
- The Mini-MOD will only modulate boilers with their mode set to Auto
or Standby. Check if any boiler stage is set to Manual, Off, or Standby. See "Mode" on page 29.
boilers are short-cycling
• Lag Delay
- Increase the Lag Delay only if all boilers tend to short-cycle.
• Last Stage Hold
- Increase the Last Stage Hold only if the lead boiler tends to short-cycle.
system is overshooting or undershooting
• Gain
- If the system is overshooting reduce the Gain.
• Gain
- If the system is undershooting increase the Gain.