22
|
059705–00 REV. B
11
INSTALLATION
The Genesis Heat-Timer
®
control consists of three primary enclosure
components.
•
The Enclosure Display Module:
Contains the display, buttons,
LEDs and electric wiring terminals. It has two screws to hold
it to the base. A By-Pass switch, used to place the boiler in
manual operation, is located above the terminals. Wiring
terminals are of the plug-in type to ease installation
and removal.
•
The Enclosure Base:
Contains the holes to mount and hold the
control against the wall or any flat surface. All other enclosure
components mount on the base. The bottom section of the
Enclosure Base contains the wiring chamber with knockouts on
the bottom to easy installation.
•
The Enclosure Wiring Cover:
Seals the wires from the external
environment. It has two screws to hold it the base and a hole
to secure a lock on the wiring enclosure. A plastic plate that
separates the wiring chamber into high and low volt sections
has been provided.
MOUNTING THE ENCLOSURE
•
Select a location near the equipment to be controlled.
•
The surface should be flat and sufficiently wide and strong to
hold the Genesis Heat-Timer
®
control.
•
Keep the control away from extreme heat, cold, or humidity.
Ambient operating temperature is from 20 to 120°F.
•
Remove the Enclosure Wiring Cover from the control enclosure
by removing the two bottom screws.
•
Remove the Enclosure Display Module by removing the middle
2 screws.
•
Screw the Enclosure Base to the surface through the upper and
lower mounting holes on the back of the enclosure.
Enclosure Display Module
Enclosure Wiring
Cover
Enclosure Base
Hole for optional lock
Mounting Holes
Display
Mounting Holes
Wiring Cover