WIRING THE 4–20MA REMOTE SETPOINT
WIRING AUX INPUTS—SENSORS OR SWITCHES (OPTIONAL)
1
Run the 4–20mA Setpoint wires through a knockout located on the bottom of the ETS-LT
Control Module enclosure.
2
Connect the positive (+) wire to terminal 26 on the ETS-LT Control module.
3
Connect the negative (–) wire to terminal 27 on the ETS-LT Control module.
•
No voltage can be applied to terminals 22 and 23 or terminal 24 and 25.
•
Auxiliary inputs can be configured as temperature sensors or as switch sensors.
When configured as a switch sensor, it must be connected to a device that
provides an open or close (short) only.
•
Standard brass tube sensors (Heat-Timer P/N 904220–00) can be used in a well
if the temperature sensor is only monitoring the temperature. However, the
standard brass tube sensor in a well is not recommended when using the
Feed Forward function
(refer to “Return Comp.” on page 27)
. The use of
Probe Sensor (Heat Timer p/n 904222-00) is strongly recommended for the
Feed Forward function.
1
To connect an Auxiliary temperature sensor:
a
Run the sensor wires through a knockout located on the bottom of the ETS-LT
Control Module enclosure.
NOTE:
The sensor wires can be extended up to 500 feet (152.5 meters)
using an 18 AWG shielded 2-conductor cable (Heat-Timer P/N 703001–01 or
equivalent #18/2 cable).
b
Connect the sensor wires to terminal 22 and 23 on the ETS-LT Control Module.
c
Connect the shield to terminal 23 on the ETS-LT Control Module.
NOTE:
Do not connect the shield at the sensor end.
NOTE
The ETS-LT Control Module does not source power to the 4–20mA terminals. The EMS system must
provide the excitation voltage.
EMS SOURCE
VOLTAGE
SHIELD
+
–
Содержание ETS-100
Страница 1: ...INSTALLATION AND OPERATION MANUAL 059327 00 REV C ETS LT ELECTRONIC TEMPERING STATION...
Страница 7: ...HEAT TIMER CORP 7 03 SPECIFICATIONS FIGURE 3 ETS LT DIMENSIONS...
Страница 43: ...HEAT TIMER CORP 43 ETS LT 07 PIPING DIAGRAMS...
Страница 46: ...46 HEAT TIMER CORP 059327 00 REV C 09 NOTES...
Страница 48: ...20 NEW DUTCH LANE FAIRFIELD NJ 07004 PHONE 973 575 4004 FAX 973 575 4052 HEAT TIMER COM...