SELECTING A LOCATION FOR THE ETS-LT ASSEMBLY
Select an appropriate location to install the ETS-LT assembly. The location must meet the following
minimum requirements:
•
The ETS-LT assembly is not intended for outdoor installation.
•
Keep the distance between the ETS-LT assembly and the water heating source to a minimum. This reduces
piping heat loss and provides minimal friction loss.
•
The ETS-LT assembly location should be where leakage from the piping field connections will not cause
damage to the surrounding area.
•
Consider the location of new or existing piping and electrical.
RECOMMENDED CLEARANCE
To ensure serviceability of the ETS assembly, the following minimum clearances must be met:
•
Left and Right Sides: 18 inches
•
Front: 24 inches
•
Top: 24 inches
•
Rear: 0 inches
GENERAL ELECTRICAL GUIDELINES
All assemblies require a 120Vac line voltage dedicated circuit with a 12 Amp circuit breaker.
MOUNTING THE ETS-LT ASSEMBLY
The ETS-LT should be wall mounted using the unistrut frame that the valve, control module and piping
components are mounted on. When mounting the ETS-LT assembly ensure it is level and plumb to the wall.
04
INSTALLATION INSTRUCTIONS
WARNING
•
The wall used for mounting the ETS-LT assembly must be vertically plumb and capable of supporting a
minimum of 100 lbs. Failure to comply with this requirement can result in substantial property damage
or personal injury.
•
The ETS-LT is too heavy and bulky for a single individual to lift and attempt to mount. It is recommended
that a minimum of 3 people are needed. The ETS-LT assembly should be support by 2 individuals while
the 3rd individual does the mounting. Failure to comply with this requirement can result in substantial
property damage or personal injury.
•
DO NOT mount or attempt to mount the ETS-LT assembly to hollow sheet rock/drywell or lath walls
using wall anchors. Only install the ETS-LT assembly to studs, equivalent wood structure or solid wall.
Failure to comply with this requirement can result in substantial property damage or personal injury.
Содержание ETS-100
Страница 1: ...INSTALLATION AND OPERATION MANUAL 059327 00 REV C ETS LT ELECTRONIC TEMPERING STATION...
Страница 7: ...HEAT TIMER CORP 7 03 SPECIFICATIONS FIGURE 3 ETS LT DIMENSIONS...
Страница 43: ...HEAT TIMER CORP 43 ETS LT 07 PIPING DIAGRAMS...
Страница 46: ...46 HEAT TIMER CORP 059327 00 REV C 09 NOTES...
Страница 48: ...20 NEW DUTCH LANE FAIRFIELD NJ 07004 PHONE 973 575 4004 FAX 973 575 4052 HEAT TIMER COM...