DHW Energy Saver Installation and Configuration Manual
HT# 059106-00C
Platinum Control Menu Settings
------ SETTINGS ------
Shift
<System Settings>
<Schedules>
<Maintenance>
<System Startup>
- MAINTENANCE MENU-
System Trim
+0 F
Outdoor Trim +0 F
Password
<DHW Settings>
--- DHW SETTINGS ----
<Supply Settings>
<Return Settings>
Demand Schedule
Copy Schedule
DHW Settings
DHW SUPPLY SETTINGS
Use Sensor?
Yes
Setpoint
140 F
Peak Diff
20 F
Light Diff
40 F
DHW RETURN SETTINGS
Use Sensor?
Yes
Setpoint
120 F
Peak Diff
20 F
Light Diff
40 F
- DHW DEMAND SCHED -
MON#1
Peak Time
6:00Am
Light Time 10:00Pm
ICMS Web Menu Settings
DHW Mode = Peak
Supp 165 F Ret OPEN
DISABLED
Press the BACK button twice
from the Main Display to show
DHW Status