27

!

WARNING:  A 9.5 MM BEAD OF STOVE CE-
MENT MUST BE PLACED AROUND THE 127

MM FIREPLACE STARTING COLLAR BEFORE AT-
TACHING THE FIRST FLUE COMPONENT. FAILURE
TO SEAL THIS JOINT MAY CAUSE THE FIREPLACE
TO OPERATE IMPROPERLY. SEE THE DIAGRAM .

STARTING

COLLAR

STOVE

SEALANT

BEAD

1 INCH

(25.4mm)

 FIRST VENT

COMPONENT

!

WARNING: ENSURE THAT THE FIBER-
GLASS ROPE GASKET SUPPLIED WITH

THE FIREPLACE SEALS BETWEEN THE FIRST
FLUE COMPONENT AND THE OUTER FIREPLACE
WRAP.

If the installation is for a termination cap attached directly
to the fireplace, skip to the sections, 

Install Firestops

 and

Flue Termination

.

1.  Attach the First Flue Component to the
     Starting Collars

To attach the first flue component to the starting collars of
the fireplace:

• Apply a 9.5mm bead of stove cement around the 127mm

fireplace starting collar.

• Make sure that the fireplace rope gasket supplied with

the fireplace seals between the first 219mm flue compo-
nent and the outer fireplace wrap.

• Lock the flue components into place by sliding the con-

centric pipe sections with four (4) equally spaced interior
beads into the fireplace collar or previously installed com-
ponent end with four (4) equally spaced indented sections.

• When the internal beads of each 219mm outer pipe line

up, rotate the pipe section clockwise about one-quarter
(1/4) turn. The flue pipe is now locked together.

Figure 18.  Attaching the First Flue Component
                  to the Starting Collars

!

B.  Installing Flue Components

After determining which set of starting collars will be used
(top or rear), follow flueing instructions accordingly.

Flueing Out the Rear Flue

Remove the installed rear seal cap from the rear starting
collars by removing screws (see Figure 17). Follow the flue
configuration tables accordingly.

Remove the insulation from the 

REAR

 five inch flue, pull

the heat shield out from outside of the firebox.

WARNING: THE TOP HEAT SHIELD (INSIDE
THE FIREBOX) MUST REMAIN  ATTACHED IF
THE FLUE SYSTEM IS  ATTACHED TO THE
REAR STARTING COLLARS. SEE FIGURE 17.

Flueing Out the Top Flue

Remove the screws in the top flue collar seal cap and re-
move the top flue collar seal cap and insulation inside the
top starting collar (See Figure 17).

Remove the heat shield from inside the 

TOP

 127mm flue

from outside of the firebox.

The glass must be taken off again for positioning the logs
when the unit is finally installed in place and finished around
it. Re-install the glass door. Attach flue system to the top
starting collars.

WARNING:  THE REAR FLUE COLLAR SEAL
CAP  MUST REMAIN ATTACHED TO THE REAR
FLUE COLLARS IF THE FLUE SYSTEM IS AT-
TACHED TO THE TOP STARTING COLLARS.

WARNING: FAILURE TO REMOVE  INSULA-
TION IN THE SET OF COLLARS YOU ARE US-
ING COULD CAUSE A FIRE.

WARNING: YOU MUST LEAVE THE INSULATION
IN PLACE IN THE SET OF COLLARS YOU ARE
NOT USING.

If your vertical flueing component is over 3.1m, you may
want to install the vertical baffle (located in the bag containing
the install manual) to improve flame appearance. Center
the vertical baffle on the 127mm flue being used, and with
self tapping screws secure the baffle to the inside of the
firebox.

Figure 17

Flueing Out Rear

Flueing Out Top

!

!

!

HEAT

SHIELD

DISCARD

 INSULATION

and

HEAT SHIELD

HEAT

 SHIELD

DISCARD

and

HEAT SHIELD

INSULATION

SEAL 

CAP

SEAL

CAP

Содержание L-Corner-TRC-CE

Страница 1: ...t N Glo dealer with any questions or concerns For the number of your nearest Heat N Glo dealer please call 952 985 6000 Printed in U S A Copyright 2002 Heat N Glo a division of Hearth Technologies Inc 20802 Kensington Blvd Lakeville MN 55044 These instructions are only valid if the following country symbol is on the appliance If this symbol is not present on the appliance it is necessary to refer ...

Страница 2: ...the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the first firing of the fireplace READ the Using Your Fireplace section of the Users Guide DO NOT USE this appliance if any part has been under water Immediately CALL a qualified service technician to inspect the unit and to replace any part of the control sys...

Страница 3: ...ing the Flue System 20 A Flue System Approvals 20 B Installing Flue Components 27 C Flue Termination 30 Step 4 Positioning Leveling and Securing the Fireplace 32 Step 5 The Gas Control System 33 Step 6 The Gas Supply Line 33 Step 7 Gas Pressure Requirements 33 Step 8 Wiring the Fireplace 34 Step 9 Finishing 35 Step 10 Installing Trim Logs and Ember Material 36 Installing the Trim 36 Positioning th...

Страница 4: ...4 PIER TRC CE Exploded Parts Diagram Part number list on following page 2 3 3 5 6 4 7 1 8 Log Assembly Service Parts 10 11 12 9 11 ...

Страница 5: ...lass Door Assembly End GLA PTRC E 3 Glass Door Assembly Side GLA PIER 4 Burner Assembly NG 501 272A 4 Burner Assembly LP 501 273A 5 Log Grate 501 364 6 Base Refractory SRV504 738 UM 7 Refractory Rear SRV504 737 UM 8 Log Set Assembly sold as complete log set only LOGS MS 9 Flex Assembly 302 330A 10 Tube Assembly 567 301A 11 Door Assembly Side 418 240A 12 Door Assembly End 501 141A Piezo Ignitor 418...

Страница 6: ...6 ST TRC CE Exploded Parts Diagram Part number list on following page 7 Log Assembly 1 2 4 5 6 3 2 Service Parts 8 10 10 9 ...

Страница 7: ...06 800 1 Burner Orifice LP 446 801 2 Glass Door Assembly GLA PIER 3 Burner Assembly NG 501 272A 3 Burner Assembly LP 501 273A 4 Log Grate 501 364 5 Base Refractory SRV504 738 UM 6 Refractory Rear SRV504 737 UM 7 Log Set Assembly sold as complete log set only LOGS MS 8 Flex Assembly 302 330A 9 Tube Assembly 567 301A 10 Door Assembly 418 240A Piezo Ignitor 418 513 Valve NG 060 524 Valve LP 060 526 P...

Страница 8: ...8 L CORNER TRC CE Exploded Parts Diagram Part number list on following page 9 Log Assembly 1 2 5 6 4 3 7 8 15 Service Parts 12 11 10 ...

Страница 9: ...embly End GLA PTRC E 3 Glass Door Assembly Side GLA PIER 4 Burner Assembly NG 501 272A 4 Burner Assembly LP 501 273A 5 Log Grate 501 364 6 Base Refractory SRV504 738 UM 7 Refractory Rear SRV504 737 UM 8 Refractory Back SRV504 736 UM 9 Log Set Assembly sold as complete log set only LOGS MS 10 30 Gas Tube SRV570 302 11 Door Assembly Side 418 240A 12 Door Assembly End 501 141A Flex Assemlby 302 320A ...

Страница 10: ...10 R CORNER TRC CE Exploded Parts Diagram Vue éclatée des pièces Part number list on following page 1 3 7 8 4 6 5 2 9 Log Assembly Service Parts 10 13 12 11 ...

Страница 11: ...mbly End GLA PTRC E 3 Glass Door Assembly Side GLA PIER 4 Burner Assembly NG 501 272A 4 Burner Assembly LP 501 273A 5 Log Grate 501 364 6 Base Refractory SRV504 738 UM 7 Refractory Rear SRV504 737 UM 8 Refractory Back SRV504 736 UM 9 Log Set Assembly sold as complete log set only LOGS MS 10 Flex Assembly 302 320A 11 Tube Assembly 567 301A 12 Door Assembly Side 418 240A 13 Door Assembly End 501 141...

Страница 12: ...RATORY Advantica TYPE Gas Fireplace STANDARD 90 396 EEC 1 Heat N Glo Quality Systems registered by SGS ICS Approval Regulations Installation Regulations Before installation check that local distribution conditions nature of gas and pressure and adjustment of the appliance are compatible This appliance must be installed with the rules in force and used only in a sufficiently ventilated space Consul...

Страница 13: ...nd benefit Failure to follow these instructions will void the own er s warranty and may present a fire hazard The Heat N Glo Warranty will be voided by and Heat N Glo disclaims any responsibility for the following actions Installation of any damaged fireplace or flue system com ponent Modification of the fireplace or flue system Installation other than as instructed by Heat N Glo Improper position...

Страница 14: ...AR COLLARS GAS CONTROLS LABELS BOTTOM GRILLE SIDE GLASS DOOR END GLASS DOOR TOP STANDOFFS TOP GRILLE TOP VENT COLLARS FRONT RIGHT SIDE LEFT SIDE 331mm 616mm 308mm VENT COLLARS 1086mm 735mm ELECTRICAL ACCESS 64mm 102mm 102mm GAS LINE ACCESS 64mm 937mm 1035mm 937mm 1043mm 616mm ...

Страница 15: ...P VENT COLLARS REAR VENT COLLARS ELECTRICAL ACCESS GAS LINE ACCESS GAS CONTROLS LABELS BOTTOM GRILLE TOP GRILLE TOP STANDOFFS GLASS DOOR 1143mm 330mm 308mm VENT COLLARS 616mm 733mm 64mm GAS LINE ACCESS 102mm 102mm 64mm ELECTRICAL ACCESS 1093mm 918mm 937mm 1042mm 616mm ...

Страница 16: ...T COLLARS ELECTRICAL ACCESS GAS LINE ACCESS GAS CONTROLS LABELS BOTTOM GRILLE SIDE GLASS DOOR TOP GRILLE END GLASS DOOR TOP STANDOFFS TOP VENT COLLARS 1086mm 330mm VENT COLLARS 308mm 642mm GAS LINE ACCESS ELECTRICAL ACCESS 64mm 64mm 102mm 102mm 918mm 1034mm 733mm 937mm 1041mm 616mm ...

Страница 17: ...s set in place Framing should be positioned to accommo date wall coverings and fireplace facing material The dia grams on the following pages show framing reference di mensions CAUTION MEASURE FIREPLACE DIMENSIONS AND VERIFY FRAMING METHODS AND WALL COVERING DETAILS BEFORE FRAMING Minimum Clearances from the Flue Pipe to Combustible Materials Vertical Sections 26 mm Horizontal Sections Top 77 mm B...

Страница 18: ...4 591 1143 759 L R CORNER TRC CE 1099 1023 1054 591 1143 759 Figure 5 Framing Dimensions NOTE DIMENSIONS SHOWN IN MILLIMETERS Shows center of 305mm x 305mm flue framing holes for top and rear flueing The center of the hole is one inch 26mm above the center of the horizontal flue pipe B C A PIER TRC CE A C B ST TRC CE A C B L CORNER TRC CE R CORNER TRC CE D E ...

Страница 19: ... Figure 6 D Series Direct Flue Component Specifications 127mm inner pipe 219mm outer pipe DV 36D 146mm 222mm 298mm DV 12D DV 09D DV 06D DV 48D DV 90D 187mm 156mm 295mm 303mm 149mm 220mm 216mm 164mm DV 45D 281mm 165mm 216mm 129mm 220mm 908mm 1 2m ...

Страница 20: ...and the flueing configuration used Identifying Flue Components The flue systems installed on this gas fireplace may in clude one two or three 90 elbow assemblies The rela tionships of vertical rise to horizontal run in flue configura tions using 90 elbows MUST BE strictly adhered to The rise to run relationships are shown in the flueing drawings and tables Refer to the diagrams on the next several...

Страница 21: ...21 Figure 8 Straight Up Vertical Flueing STRAIGHT UP VERTICAL FLUEING V MAX RUN 12 2 m STRAIGHT OUT HORIZONTAL FLUEING H MAX RUN 610 mm Figure 9 Straight Out Horizontal Flueing H V CAP ...

Страница 22: ... MIN 1 22m MAX 3 6m MIN 1 5m MAX 4 5m MIN 1 86m MAX 5 1m MAX 5 1m V H MAX 11 3m Figure 11 Flueing with One 90 Elbow V H MIN 305mm MAX 610mm MIN 610mm MAX 1 22m MIN 914mm MAX 1 86m MIN 1 22m MAX 2 4m V H MAX 11 3m H MAX 2 4m Figure 10 Flueing with One 90 Elbow FLUEING WITH ONE 1 90 ELBOW V H H V ...

Страница 23: ...m MAX 2 7m MIN 1 22m MAX 3 6m MIN 1 5m MAX 4 5m MIN 1 86m MAX 5 1m MAX 5 1m V H H1 MAX 11 3m Figure 12 Flueing with Two 90 Elbows FLUEING WITH TWO 2 90 ELBOWS V H MIN 305 mm MAX 914 mm MIN 610 mm MAX 1 86 m MIN 914 mm MAX 2 7 m MIN 1 22 m MAX 3 6 m MAX 5 1 m V V1 H MAX 11 3m V H H1 H V V1 ...

Страница 24: ...MAX 1 86 m MAX 2 7 m MIN 1 22 m MAX 2 48 m MAX 3 6 m MAX 2 48 m MAX 5 1 m V H H1 MAX 11 3m Figure 13 Flueing with Two 90 Elbows Figure 14 Flueing with Two 90 Elbows FLUEING WITH TWO 2 90o ELBOWS V H H1 MIN 305mm MAX 610mm MIN 610mm MAX 1 22m MIN 914mm MAX 1 86m MIN 1 22m MAX 2 4m MAX 2 4m V H H1 MAX 11 3m V H1 H V H1 H ...

Страница 25: ... m MAX 2 7 m MIN 1 22 m MAX 2 48 m MAX 4 5 m MAX 2 48 m MAX 5 1 m V H H1 H2 MAX 11 3m FLUEING WITH THREE 3 90 ELBOWS V H H H1 H2 MIN 305 mm MAX 610 mm MAX 914 mm MIN 610 mm MAX 1 22 m MAX 1 86 m MIN 914 mm MAX 1 86 m MAX 2 7 m MIN 1 22 m MAX 2 48 m MAX 3 6 m MAX 2 48 m MAX 5 1 m V V1 H H1 MAX 11 3m FLUEING WITH THREE 3 90 ELBOWS V1 V H1 H H V H1 H2 V H H H1 ...

Страница 26: ...N 914mm MAX 2 7m MIN 1 22m MAX 3 6m MAX 5 1m H H1 MAX 5 1m V V1 H H1 MAX 11 3m FLUEING WITH THREE 3 90 ELBOWS V H H1 MIN 305mm MAX 914m MIN 610mm MAX 1 86m MIN 914mm MAX 2 7m MIN 1 22m MAX 3 6m MAX 5 1m V V1 H H1 MAX 11 3m Figure 16 Flueing with three 90 elbows V1 H1 H V H1 H V1 V ...

Страница 27: ...r follow flueing instructions accordingly Flueing Out the Rear Flue Remove the installed rear seal cap from the rear starting collars by removing screws see Figure 17 Follow the flue configuration tables accordingly Remove the insulation from the REAR five inch flue pull the heat shield out from outside of the firebox WARNING THE TOP HEAT SHIELD INSIDE THE FIREBOX MUST REMAIN ATTACHED IF THE FLUE ...

Страница 28: ...un through the firestops Figure 21 12 x 12 Hole and Flue Pipe Figure 22 Heat Shield Interior Exterior Firestops VENT PIPE 25 4 mm 305mm 305mm TRIM HEAT SHIELD IF TOO LONG ADD TO SHIELD IF TOO SHORT EXTERIOR FIRESTOP INTERIOR FIRESTOP HEAT SHIELD 3 Install Support Brackets For Horizontal Runs The flue system must be supported every 1 5m of horizontal run by a horizontal pipe support To install supp...

Страница 29: ...ing using the centerpoint previously marked Frame the hole with framing lumber the same size as the ceiling joists Figure 24 Ceiling Firestop Ceiling Side If the area above the ceiling is NOT an attic position and secure the ceiling firestop on the ceiling side of the previously cut and framed hole Figure 23 Hole New Framing Members If the area above the ceiling IS an attic position and secure the...

Страница 30: ...ndcap termination kits Use the exterior pipelock hole on the round flange of the wall firestop to secure the flue pipe in place For trapezoidal cap termination kits Using screws secure the cap to the exterior wall through the flanges in the cap Figure 26 Trapezoid Termination Cap WARNING THE BOTTOM OF THE FLUE TERMINATION CAP MUST BE A MINIMUM OF 305 MM ABOVE GROUND LEVEL GRADE THE TOP OF THE CAP ...

Страница 31: ...CES FROM GAS TERMINALS AND PLACEMENT OF GAS TERMINAL NOTE This also pertains to vertical flue systems installed on the outside of the building Roof Pitch H min cm flat to 6 12 30 5 6 12 to 7 12 38 over 7 12 to 8 12 45 7 over 8 12 to 9 12 61 over 9 12 to 10 12 76 2 over 10 12 to 11 12 99 over 11 12 to 12 12 122 over 12 12 to 14 12 152 4 over 14 12 to 16 12 183 over 16 12 to 18 12 213 4 over 18 12 t...

Страница 32: ...e diagram below shows how to properly position level and secure the fireplace Figure 29 Proper Positioning Leveling and Securing of a Fireplace Step 5 The Gas Control System WARNING THIS UNIT IS NOT FOR USE WITH SOLID FUEL Standing Pilot Ignition System This system includes millivolt control valve standing pilot thermopile thermocouple flame sensor and piezo ignitor WARNING 230 VAC MUST NEVER BE C...

Страница 33: ...gas line hole and connect it to the shut off valve When attaching the pipe support the control so that the lines are not bent or torn After the gas line installation is complete use a soap solution to carefully check all gas connections for leaks WARNING DO NOT USE AN OPEN FLAME TO CHECK FOR GAS LEAKS Step 7 Gas Pressure Requirements Pressure requirements for Heat N Glo gas fireplaces are shown in...

Страница 34: ...LVE WILL BE DESTROYED Optional Accessories Optional fan and remote control kits require that 230 VAC be wired to the factory installed junction box before the stove is permanently installed Remote Wall Switch Position the remote wall switch in the desired position on a wall Run a maximum of 7 8 m or less length of 1 02 mm diameter minimum wire and connect it to the stove ON OFF switch pigtails CAU...

Страница 35: ...E FINISHED WALLS AND THE FIREPLACE SURROUND TOP AND SIDES ARE SEALED A 150 C MINIMUM SEALANT MATE RIAL MUST BE USED THESE JOINTS ARE NOT RE Figure 34 Sealant Material ST TRC TOP EDGE SIDE EDGE PIER TRC CORNER TRC TOP EDGE SIDE EDGE 13mm GAP 13mm GAP TOP EDGE OF FIREPLACE 13mm 305mm CEILING 788mm QUIRED TO BE SEALED ONLY NON COMBUSTIBLE MATERIAL USING 150 C MINIMUM ADHESIVE IF NEEDED CAN BE APPLIED...

Страница 36: ...rim Logs Ember Material Placing the Ember Material The bag labeled Glowing Ember 050 721 is standard glow ing ember material To place the ember material Remove the wing nuts and glass clips or tension springs around the glass door Remove the glass door from the unit Place dime size pieces of ember material about 13 mm apart near port holes in burner top Do NOT press em bers into burner ports Cover...

Страница 37: ... front grilles for obstructions Before lighting the fireplace double check the unit for possible obstructions that could be blocking the flue ter minations or the front grilles Double check for faulty components Any component that is found to be faulty MUST BE re placed with an approved component Tampering with the fireplace components is DANGEROUS and voids all war ranties A small amount of air w...

Страница 38: ... flame patterns Make sure the flames are steady not lifting or floating See Figure 37 The thermopile thermocouple tips should be covered with flame See Figure 30 Figure 37 Burner Flame Patterns MAKE SURE THE FLAMES ARE STEADY NOT LIFTING OR FLOATING Checking Flue System Frequency Before initial use and at least annually thereafter more frequently if possible By Qualified service technician Home ow...

Страница 39: ...d the valve knob in If the millivolt reading is less than 15mV replace the thermocouple b Defective valve If the thermocouple is producing more than 15 millivolts replace faulty valve 3 The pilot is burning there is no gas burner the valve knob is in the ON position and the ON OFF switch is in the ON position a ON OFF switch or wires defective Check the ON OFF switch and wires for proper connectio...

Страница 40: ...age Tighten the corner e Bad thermopile or thermocouple Replace if necessary f Improper flue cap installation Check for proper installation and freedom from debris or blockage 6 Glass soots a Flame impingement Adjust the log set so that the flame does not excessively impinge on it b Improper venturi setting Adjust the air shutter at the base of the burner c Debris around venturi Inspect the openin...

Отзывы: