C.   Bedroom Installation in Canada

This model 

MUST NOT

 be vented into a vent system in-

stalled exterior to a building.  The part of the vent system

above the roof line can be exterior to the building.

D.  Vent Termination

WARNING: MAJOR U.S. BUILDING CODES

SPECIFY MINIMUM CHIMNEY AND/OR VENT

HEIGHT ABOVE THE ROOF TOP. THESE MIN-

IMUM HEIGHTS ARE NECESSARY IN THE IN-

TEREST OF SAFETY.  FIGURE 6 AND TABLE

SHOW MINIMUM HEIGHTS, PROVIDED THE

TERMINATION CAP IS AT LEAST 8-FEET

FROM A VERTICAL WALL.

!

ROOF PITCH

H (MIN.) FT.

FLAT TO 6/12

1.0

6/12 TO 7/12

1.25

OVER 7/12 TO 8/12

1.5

OVER 8/12 TO 9/12

2.0

OVER 9/12 TO 10/12

2.5

OVER 10/12 TO 11/12

3.25

OVER 11/12 TO 12/12

4.0

OVER 12/12 TO 14/12

5.0

OVER 14/12 TO 16/12

6.0

OVER 16/12 TO 18/12

7.0

OVER 18/12 TO 20/12

7.5

OVER 20/12 TO 21/12

8.0

       Figure 6. Vent Termination

VENT

CAP

12

X

ROOF PITCH

IS  X/ 12

LOWEST 

DISCHARGE 

OPENING

H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING

Step 5.  Positioning, Leveling, and

               Securing the Fireplace

To properly position, level, and secure the fireplace:
• Place the fireplace into position (see Figure 7).
• Level the fireplace from side to side and from front to

back.

• Shim the fireplace with non-combustible material, such

as sheet metal, as necessary.

• Secure the fireplace to the framing by nails or screws us-

ing nailing tabs.

!

Figure 7.  Proper Positioning, Leveling,

    and Securing of a Fireplace

Step 6. The Gas Control Systems

WARNING:  THIS UNIT IS NOT FOR USE WITH

SOLID FUEL.

This model uses a 

Direct Spark Ignition (DSI) gas control

system.

Direct Spark Ignition (DSI) System

The DSI system includes a 110VAC control valve, electron-

ic module, and spark ignitor/flame sensor.

WARNING: 110-120 VAC MUST BE WIRED TO

THE FIREPLACE JUNCTION BOX IN A DSI

SYSTEM.

!

NON-COMBUSTIBLE

BOARD PROVIDED

WITH THE UNIT.

See Figures

3 and 11.

Содержание CFX-TV36B

Страница 1: ...derwriters Laboratories Listed 592 900F 5 00 READ THIS MANUAL BEFORE INSTALLING OR OPERATING THIS APPLIANCE THIS INSTALLERS GUIDE MUST BE LEFT WITH APPLIANCE FOR FUTURE REFERENCE Please contact your H...

Страница 2: ...he installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the first firing of the fireplace READ the Using Your Firepla...

Страница 3: ...tem 11 A Vent System Approvals 11 B System Components 11 C Bedroom Installation in Canada 12 D Vent Termination 12 Step 5 Positioning Leveling and Securing the Fireplace 12 Step 6 The Gas Control Syst...

Страница 4: ...FX TV36B DSI NG LP Exploded Parts Diagram Vue clat e des pi ces Part number list on following page La liste des num ros de pi ce se trouve la page suivante 3 4 2 9 7 Log Set Assembly 5 8 13 12 11 10 6...

Страница 5: ...ssembly Jeu de B ches LOGS TV36B 8 Log 1 B che 1 SRV446 701 9 Log 2 B che 2 SRV446 702 10 Log 3 B che 3 SRV446 703 11 Log 4 B che 4 SRV540 704 12 Log 5 B che 5 SRV560 702 13 Log 6 B che 6 SRV446 706 J...

Страница 6: ...es current edition The Uniform Mechanical Code current edition and local Building Officials for the options allowed in obtaining an effective bedroom volume of unconfined space This model natural gas...

Страница 7: ...ese instructions will void the owner s warranty and may present a fire hazard WARNING IF THERE IS ANY NOTICEABLE DAMAGE TO THE FIBER FIREBOX PLEASE CONTACT YOUR DEALER FOR FURTHER INSTRUCTIONS The Hea...

Страница 8: ...8 Figure 1 Diagram of the CFX TV36B...

Страница 9: ...to be measured from the unit outer wrap surface to the combustible construction NOT from the screw heads that secure the unit together Minimum Clearances from the Class B Chimney Vent Pipe to Combust...

Страница 10: ...the structure where the fireplace is located It is recommended that all natural venting non air tight gas fireplaces have outside air connected to them It is also recommended that the building be mech...

Страница 11: ...outlet collar Look at the vent pipe through the holes in the 10 5 8 ring to check that the vent pipe is attached NOTE It is always better to first attach a straight section of vent to the unit before...

Страница 12: ...nt Termination VENT CAP 12 X ROOF PITCH IS X 12 LOWEST DISCHARGE OPENING H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING Step 5 Positioning Leveling and Securing the Fireplace To properly p...

Страница 13: ...hole and connect it to the shut off valve When attaching the pipe support the control so that the lines are not bent or torn After the gas line installation is complete use a soap solution to carefull...

Страница 14: ...nal Accessories Optional remote control kits require that 110 120 VAC be wired to the fireplace junction box WARNING TOAVOID POTENTIAL OVERHEAT ING TO THE REMOTE CONTROL RECEIVER IT MUST BE PLACED ON...

Страница 15: ...aterial Installing the Trim Combustible materials may be brought up to the specified clearances on the side and top front edges of the fireplace but MUST NEVER overlap onto the front face The joints b...

Страница 16: ...ed for faulty components Now you re ready to light the fireplace WARNING PLEASE REFER TO THE USER S MANUAL FORALL CAUTIONS SAFETY AND WARNING INFORMATION PERTAINING TO THE LIGHTING AND OPERATION OF TH...

Страница 17: ...vacuum the control compartment fireplace logs and burner areas surrounding the logs Checking Flame Patterns Flame Height Frequency Periodically By Qualified service technician Home owner Task Make a...

Отзывы: