For Vertical Runs -

 One ceiling firestop is 

REQUIRED 

at

the hole in each ceiling through which the vent passes.
To install firestops for vertical runs that pass through ceilings:
• Position a plumb bob directly over the center of the verti-

cal vent component.

• Mark the ceiling to establish the centerpoint of the vent.
• Drill a hole or drive a nail through this centerpoint.
• Check the floor above for any obstructions, such as wir-

ing or plumbing runs.

• Reposition the fireplace and vent system, if necessary,

to accommodate the ceiling joists and/or obstructions.

• Cut an 11-inch X 11-inch (280mm X 280mm) hole through

the ceiling, using the centerpoint previously marked.

• Frame the hole with framing lumber the same size as the

ceiling joists.

Figure 18.  Ceiling Firestop (Ceiling Side)

If the area above the ceiling is 

NOT

 an attic, position and

secure the ceiling firestop on the ceiling side of the previously

cut and framed hole.

Figure 17.  11" x 11" Hole & New Framing Members

If the area above the ceiling 

IS

 an attic, position and secure

the firestop on top of the previously framed hole.

NOTE: Keep insulation away from the vent pipe at least

1 inch (25mm).

Figure 19.    Attic Firestop

JOIST

CEILING FIRESTOP

CEILING

NAILS (4 REQUIRED)

CEILING

CEILING FIRESTOP

RAFTER

NAILS (4 REQUIRED)

CEILING

NEW
FRAMING
MEMBERS

EXISTING CEILING 
JOISTS

CHIMNEY
HOLE

11" (280 mm)
 

11" (280mm) 

Содержание 6000XLTB

Страница 1: ...ITH APPLIANCE FOR FUTURE REFERENCE 1 This appliance may be installed in an af termarket permanentlylocated manufac tured mobile home wherenotprohibited by local codes 2 Thisapplianceisonlyfor usewiththetype of gas indicated on the rating plate This appliance is not convertible for use with other gases unless a certified kit is used Please contact your Heat N Glo dealer for any questions or concern...

Страница 2: ...the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the first firing of the fireplace READ the Using Your Fireplace section of the Owners Guide DO NOT USE this appliance if any part has been under water Immediately CALL a qualified service technician to inspect the unit and to replace any part of the control sy...

Страница 3: ... System 14 A Vent System Approvals 14 B Installing Vent Components 18 C Vent Termination 22 Step 4 Positioning Leveling and Securing the Fireplace 25 Step 5 The Gas Control Systems 25 Step 6 The Gas Supply Line 26 Step 7 Gas Pressure Requirements 26 Step 8 Wiring the Fireplace 27 Step 9 Finishing 28 Step 10 Installing Trim Logs and Ember Material 29 Installing the Trim 29 Positioning the Logs 29 P...

Страница 4: ...CSAC22 1 Canadian Electric Code in Canada These models may be installed in a bedroom or bed sitting room in the U S A and Canada 1Approvals and Codes High Altitude Installations U L Listed gas fireplaces are tested and approved for elevations from 0 to 2 000 feet in the U S A and from 0 to 4 500 feet in Canada When installing this fireplace at an elevation above 2 000 feet in the United States it ...

Страница 5: ...benefit Failure to follow these instructions will void the owner s warranty and may present a fire hazard The Heat N Glo Warranty will be voided by and Heat N Glo disclaims any responsibility for the following actions Installation of any damaged fireplace or vent system component Modification of the fireplace or direct vent system Installation other than as instructed by Heat N Glo Improper positi...

Страница 6: ...10 Figure 1 Diagram of the 7000XLT and 6000XLTB TOP VENT COLLARS GAS LINE ACCESS ELECTRICAL ACCESS GAS CONTROLS RATING PLATE AND LABELS TRIM DOOR HOOD TOP STANDOFFS ...

Страница 7: ...elbow as the first vent com ponent an area 3 above the horizontal vent the entire width and depth of the firebox must be free of combustibles See Figure 3 Step 2 Framing the Fireplace Fireplace framing can be built before or after the fireplace is set in place Framing should be positioned to accommo date wall coverings and fireplace facing material The dia gram below shows framing reference dimens...

Страница 8: ...e 3 Framing Dimensions Framing should be constructed of 2 X 4 lumber or heavier Shows center of 12 x 12 vent framing hole for top and rear venting The center of the hole is one inch 25 4mm above the center of the horizontal vent pipe ...

Страница 9: ...LAP 1 3 8 INCHES 34 93mm AT EACH JOINT DV 36D 5 3 4 146mm 8 3 4 222mm 11 3 4 298mm DV 12D DV 09D DV 06D DV 48D DV 90D 7 3 8 187mm 6 5 32 156mm 11 5 8 295mm 11 15 16 303mm 5 7 8 149mm 8 5 8 220mm 8 1 2 216mm 6 7 16 164mm DV 45D 11 1 16 281mm 6 1 2 165mm 8 1 2 216mm 5 1 16 129mm 8 5 8 220mm 35 3 4 908mm 47 3 4 1 2m ...

Страница 10: ... one two or three 90 elbow assemblies The relationships of vertical rise to horizontal run in vent configurations using 90 elbows MUST BE strictly adhered to The rise to run relation ships are shown in the venting drawings and tables Refer to the diagrams on the next several pages NOTE Two 45 elbows may be used in place of one 90 elbow Rise to run ratios in the vent system must be followed if 45 e...

Страница 11: ...H 40 MAX 12 4MM 20 MAX 6 2m Figure 7 Venting with One 90 Elbow NOTE IF A 90o ELBOW IS FIRST AT TACHED TO THE UNIT THE MAXIMUM HORIZONTAL RUN IS 3 FEET 914mm NOTE For corner installations A 6 inch 152mm MINIMUM length of straight pipe must be attached to the fireplace before 90o elbow This will allow the vent pipe to clear the top standoffs ...

Страница 12: ...H TWO 2 90o ELBOWS V FT H H1 FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m V H H1 40 MAX 12 4m 20 MAX 6 2m V V1 H 40 MAX 12 4m Figure 8 Venting with Two 90 Elbows ...

Страница 13: ...mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m NOTE H H1 20 MAX 6 2m V V1 H H1 40 MAX 12 4m VENTING WITH THREE 3 90 ELBOWS V FT H H1 FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m 20 MAX 6 2m NOTE V V1 H H1 40 MAX 12 4m Figure 9 Venting with three 90 elbows ...

Страница 14: ...mm outer pipe line up rotate the pipe section clockwise about one quarter 1 4 turn Theventpipeisnowlockedtogether The first 90 elbow installed in the vent system of a rear venting fireplace MUST BE in a vertical position Figure 10 Attaching the First Vent Component to the Starting Collars WARNING A 3 8 INCH 9 5 MM BEAD OF STOVE CEMENT MUST BE PLACED AROUND THE 5 INCH 127 MM FIREPLACE STARTING COL ...

Страница 15: ...nt system 90 elbows may be installed and rotated to any point around the preceding component s vertical axis If an el bow does not end up in a locked position with the pre ceding component attach with a minimum of two 2 sheet metal screws Figure 12 CORRECT INCORRECT 2 Fasten the shield in place using the four pilot holes pro vided in the part The shield should be oriented such that the 13 1 8 inch...

Страница 16: ...ombustible wall To install firestops for horizontal runs that pass through either interior or exterior walls Cut a 12 inch by 12 inch 305mm X 305mm hole through the wall NOTE The center of the hole is one 1 inch 25 4mm above the center of the horizontal vent pipe Position the firestops on both sides of the hole previ ously cut and secure the firestops with nails or screws The heat shields of the f...

Страница 17: ... 11 inch 280mm X 280mm hole through the ceiling using the centerpoint previously marked Frame the hole with framing lumber the same size as the ceiling joists Figure 18 Ceiling Firestop Ceiling Side If the area above the ceiling is NOT an attic position and secure the ceiling firestop on the ceiling side of the previously cut and framed hole Figure 17 11 x 11 Hole New Framing Members If the area a...

Страница 18: ... of the wall firestop to secure the vent pipe in place For trapezoidal cap termination kits Using screws secure the cap to the exterior wall through the flanges in the cap Figure 20 Round Trapezoid Termination Caps WARNING THE BOTTOM OF THE VENT TERMINATION CAP MUST BE A MINIMUM OF 12 INCHES 305 MM ABOVE GROUND LEVEL GRADE THE TOP OF THE CAP MUST BE A MIN IMUM OF 18 INCHES 457 MM BELOW COMBUS TIBL...

Страница 19: ...door that may be opened C 9 U S A 12 Canada clearance to permanently closed window D 18 vertical clearance to ventilated soffit located above the termi nal within a horizontal distance of 2 feet 60 cm from the cen ter line of the terminal E 18 clearance to unventilated soffit F 9 clearance to outside corner G 6 clearance to inside corner H 3 ft Canada not to be installed above a gas meter regulato...

Страница 20: ...E FOLLOWING DIAGRAM FOR MINIMUM HEIGHTS PROVIDED THE TERMI NATION CAP IS AT LEAST TWO 2 FEET FROM A VERTICALWALLAND 2 FEET BELOWA HORIZON TAL OVERHANG NOTE This also pertains to vertical vent systems in stalled on the outside of the building Roof Pitch H min ft flat to 6 12 1 0 6 12 to 7 12 1 25 over 7 12 to 8 12 1 5 over 8 12 to 9 12 2 0 over 9 12 to 10 12 2 5 over 10 12 to 11 12 3 25 over 11 12 ...

Страница 21: ...sition level and secure the fireplace Figure 23 Proper Positioning Leveling and Securing of a Fireplace Figure 24 Gas Control System STANDING PILOT Step 5 The Gas Control System WARNING THIS UNIT IS NOT FOR USE WITH SOLID FUEL The type of gas control system used with this model is Stand ing Pilot Ignition Standing Pilot Ignition System This system includes millivolt control valve standing pilot th...

Страница 22: ... fireplace lower grille insert the gas supply line through the gas line hole and connect it to the shut off valve When attaching the pipe support the control so that the lines are not bent or torn After the gas line installation is complete use a soap solution to carefully check all gas connections for leaks WARNING DO NOT USE AN OPEN FLAME TO CHECK FOR GAS LEAKS Step 7 Gas Pressure Requirements P...

Страница 23: ...witch in the desired position on a wall Run a maximum of 25 feet 7 8 m or less length of 18 A W G minimum wire and connect it to the fireplace ON OFF switch pigtails WARNING DO NOT CONNECT 110 120 VAC TO THE REMOTE WALL SWITCH OR THE CONTROL VALVE WILL BE DESTROYED CAUTION LABEL ALL WIRES PRIOR TO DISCONNEC TION WHEN SERVICING CONTROLS WIRING ERRORS CANCAUSEIMPROPERANDDANGEROUSOPERATION VERIFY PRO...

Страница 24: ...zontal Dimensions of Combustibles above Fireplace CAUTION IF JOINTS BETWEEN THE FINISHED WALLS AND THE FIREPLACE SURROUND TOP AND SIDES ARE SEALED A 300 F MINIMUM SEALANT MATE RIAL MUST BE USED THESE JOINTS ARE NOT RE QUIRED TO BE SEALED ONLY NON COMBUSTIBLE MATERIAL USING 300 F MINIMUM ADHESIVE IF NEEDED CAN BE APPLIED AS FACING TO THE FIRE PLACE SURROUND SEE THE DIAGRAM BELOW Hearth Extensions A...

Страница 25: ... might need to be repositioned slightly to avoid excessive flame impingement Step 10 Installing Trim Logs and Ember Material Placing the Ember Material Ember material is shipped with this gas fireplace The bag labeled Glowing Ember 050 721 is standard glowing ember material To place the ember material Pull the four glass latches out of the groove on the glass frame Lift trim door up and out of the...

Страница 26: ...te normally NOTE The fireplace should be run for 8 hours on the initial start up This will help to cure the chemicals used in the paint and logs Subsequent lightings of the fireplace will not require this purging of air from the gas supply lines unless the gas valve has been turned to the OFF position in which case the air would have to be purged Step 12 Lighting the Fireplace You ve reviewed all ...

Страница 27: ...ency Once annually By Qualified service technician Task Brush or vacuum the control compartment fireplace logs and burner areas surrounding the logs Checking Flame Patterns Flame Height Frequency Periodically By Qualified service technician Home owner Task Make a visual check of your fireplace s flame patterns Make sure the flames are steady not lifting or floating See Figure 33 The thermopile the...

Отзывы: