background image

1

W415-0244 / A / 05.15.03

INSTALLER: THESE INSTRUCTIONS MUST BE CONVEYED TO AND REMAIN WITH THE HOMEOWNER.

Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON L4M 4Y8 Canada • (705)721-1212 • fax(705)722-6031

www.napoleonfireplaces.com • [email protected]

CERTIFIED UNDER CANADIAN AND AMERICAN NATIONAL STANDARDS, CSA 2.22, AND ANSI Z21.50 RESPECTIVELY FOR VENTED GAS FIREPLACES.

DIRECT VENT MILLIVOLT SYSTEM

INSTALLATION AND OPERATION INSTRUCTIONS FOR

DIRECT VENT DECORATIVE GAS FIREPLACE

NATURAL GAS  MODEL

 

BGD38NT

PROPANE GAS  MODEL

 

BGD38PT

CERTIFIED FOR CANADA AND UNITED STATES USING ANSI / CSA METHODS

Installation and service must be performed by a qualified installer, service agency

or the gas supplier.

WARNING: 

 If the information in these instructions is not followed exactly, a fire or

explosion may result causing property damage, personal injury or death.

FOR YOUR SAFETY

Do not store or use gasoline or other flammable vapours and liquids in the vicinity of

this or any other appliance.

WHAT TO DO IF YOU SMELL GAS:

•  Do not try to light any appliance.
•  Do not touch any electrical switch.
•  Do not use any phone in your building.

•  Immediately call your gas supplier from

a neighbour's phone. Follow the gas
supplier's instructions.

•  If you cannot reach your gas supplier,

call the fire department.

Summary of Contents for BGD38NT

Page 1: ...ANADA AND UNITED STATES USING ANSI CSA METHODS Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING If the information in these instructions i...

Page 2: ...inspect the fireplace and to replace any part of the control system and any gas control which has been under water Do not operate the fireplace with the glass door removed cracked or broken Replaceme...

Page 3: ...prior approval of an authorized company official Labour costs to work however requires the prior approval of an authorized company official Labour costs to work however requires the prior approval of...

Page 4: ...35 BTU hr at an efficiency of 64 4 with the fan on and 17 212 BTU hr for propane at an efficiency of 66 2 with the fan on The maxi mum A F U E annual fuel utilization efficiency rating is 56 3 for nat...

Page 5: ...ength and number of elbows to a minimum The air terminal must remain unobstructed at all times Examine the air terminal at least once a year to verify that it is unobstructed and undamaged Purge all g...

Page 6: ...at open Clearance to permanently closed windows Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet from the centerline of the terminal Clearance...

Page 7: ...ing v ting ver er er er ertically tically tically tically tically the v the v the v the v the ver er er er ertical rise is a tical rise is a tical rise is a tical rise is a tical rise is a minimum 36...

Page 8: ...is less than is less than is less than is less than horizontal horizontal horizontal horizontal horizontal run run run run run horizontal horizontal horizontal horizontal horizontal run verti run ver...

Page 9: ...ne 90 elbow FIGURE5 See graph to determine the required vertical rise VT for the required horizontal run HT For vent configurations requiring more than one 90 el bow the following formulas apply Formu...

Page 10: ...ore than one 90 elbow the following formulas apply Formula 1 HT 4 2 VT Formula 2 HT VT 24 75 feet Example 2 Example 3 V1 4ft V2 1 5ft VT V1 V2 4 1 5 5 5 ft H1 2ft H2 1ft H3 1ft H4 1 5ft HR H1 H2 H3 H4...

Page 11: ...s vent configuration is ac ceptable when Ht Vt Simple venting configurations FIGURE10 FIGURE11 For vent configurations requiring elbows the following for mulas apply Formula 1 HT VT Formula 2 HT VT 40...

Page 12: ...figuration is unac ceptable and a new fireplace location or vent configuration will need to be established to satisfy both formulas Example 6 V1 1 5ft V2 5ft VT V1 V2 1 5 5 6 5 ft H1 1ft H2 1ft H3 1ft...

Page 13: ...installed in its final position apply sealant between the pipe liner and the firestop spacer FIGURE18 FORSAFEANDPROPEROPERATIONOFTHEFIREPLACE FOLLOW THE VENTING INSTRUCTIONS EXACTLY AHEATSHIELDMUSTBE...

Page 14: ...ts using the same procedure as described in points 2 and 3 The vent system must be sup ported approximately every 3 feet for both vertical and hori zontal runs Use Wolf Steel support ring assemblies o...

Page 15: ...uplers to the air terminal 3 Install the air terminal See item 3 of the Horizontal Air Terminal Installation Extend the 5 telescopic sleeve connect to the air terminal assembly Fasten with self tappin...

Page 16: ...ter edge of the of the outside sleeve of the air terminal Slip a 8 diameter coupler over the sleeve and secure as before FIG URE 27 Trim the 8 coupler even with the 5 coupler end 5 Thread the air term...

Page 17: ...and secure to the 2x4 framing The tabs will facilitate the installation of either a 3 4 or a 1 finished wall thickness The nailing tabs must not be removed Combustible mantle clearance can vary accor...

Page 18: ...he hinge screen into place and with the control door open secure to the firebox using three screws FIGURE35 LOUVRE BRACKET FIGURE36a UPPERLOUVREINSTALLATION A C B L38 LOUVRE INSTALLATION FIGURE 37 a c...

Page 19: ...op of the log should rest in the pocket on the back log LOG PLACEMENT 4 1 4 Position the notch located on the end of the center log 5 against the middle grate post with the other end of the log restin...

Page 20: ...h the connectors from the black and white wires to the thermodisc and se cure the thermodisc bracket to the securing stud at the bottom left of the unit using a lock washer and wing nut En sure that t...

Page 21: ...ed on becomes thermally activated and will automatically run approximately 15 30 minutes after the fireplace has been lit and for approximately 30 45 minutes after the fireplace has been turned off If...

Page 22: ...out any gas If you smell gas including near the floor Stop Follow B in the above safety information on this label If you don t smell gas go the next step 5 Turn gas knob counter clockwise to pilot 6 D...

Page 23: ...ir shutter remove the two screws that se cure the cover to the air housing taking care not to dam age the gasket Adjust the pilot screw to provide properly sized flame Turn in a clockwise direction to...

Page 24: ...W135 0187 MIDDLE CROSSOVER LOG 5 19 W135 0188 RIGHT CROSSOVER LOG 6 20 W010 0811 BLACK DOOR C W GLASS 21 W455 0040 41 NATURAL GAS ORIFICE 21 W455 0003 54 PROPANE GAS ORIFICE 22 W500 0028 FIRESTOP SPAC...

Page 25: ...25 W415 0244 A 05 15 03 WARNING This is a fast acting thermocouple It is an integral safety component Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd...

Page 26: ...gas valve has an interlock device which will not allow the pilot burner to be lit until the ther mocouple has cooled Allow ap proximately 60 seconds for the thermocouple to cool System is not correct...

Page 27: ...checked the same as above using screw B Gauge should read 3 5 water column for natural gas or 10 water column for propane Check that main burner is operating on HI AFTER TAKING PRESSURE READINGS BE SU...

Page 28: ...28 W415 0244 A 05 15 03 Wolf Steel Fireplace Service History This fireplace must be serviced annually depending on usage Date Service Technician Name Service Performed Special Concerns Dealer Name...