2. Continue Adding Vent Components
WARNING: FOR 7000TR ONLY: INSTALLA-
TION OF THIS FIREPLACE REQUIRES THE
USE OF HEAT SHIELD 570-290 ABOVE THE FIRST
90
0
ELBOW IN THE VENTING SYSTEM.
Figure 17
To Install the Heat Shield:
1. Determine if the heat shield is required. Do so by mea-
suring the vertical distance between the top horizontal
surface of the elbow to any combustible surface above.
If the distance is more than 4 inches, the heat shield is
NOT
required. If it is 4 inches or less, the heat shield
IS
REQUIRED
. Install per the following steps. See Figure 17.
!
Continue adding vent components, locking each succeed-
ing component into place.
Ensure that each succeeding vent component is secure-
ly fitted and locked into the preceding component in the
vent system.
90° elbows may be installed and rotated to any point
around the preceding components vertical axis. If an el-
bow does not end up in a locked position with the pre-
ceding component, attach with a minimum of two (2)
sheet metal screws.
Figure 18
CORRECT
INCORRECT
2. Fasten the shield in place using the four pilot holes pro-
vided in the part. The shield should be oriented such that
the 13 1/8 inch dimension (longest dimension) is run-
ning in the same direction the elbow is pointing. The
shield should be centered directly above the elbow, and
positioned so that it creates a 1/2 inch airspace between
the shield and the combustible surface. See Figure 18.
3. Install Support Brackets
For Horizontal Runs -
The vent system must be supported
every five (5) feet of horizontal run by a horizontal pipe support.
To install support brackets for horizontal runs:
Place the pipe supports around the vent pipe.
Nail the pipe supports to the framing members.
Figure 19. Adding Venting Components
HEAT
SHIELD
3” MIN.
(76mm)
COMBUSTIBLE
SURFACE
COMBUSTIBLE SURFACE
DIRECTION
UP
HEAT SHIELD
90 ELBOW
0