3.6 Commissioning the Appliance
3.6.1 Pilot Ignition Check
1. Ignite the pilot light as described in the User Instructions
2. Check that the pilot flame stays alight
3. Extinguish the pilot light
3.6.2 Main Burner Check
1. Ignite the pilot light as described in the User Instructions
2. Turn on the main burner as described in the User Instructions
3. Check that the pilot smoothly cross-lights to the main burner and that the main burner and pilot stay alight
4. Extinguish the appliance fully
3.6.3 Pressure Check
The appliance is preset to give the correct heat inputs as listed in the technical details. No further adjustment is
necessary. Always check the inlet pressure and burner pressure.
1. Turn off the gas valve on the appliance
2. Release the screw on the Inlet Pressure test point on the gas valve and connect a pressure guage Manometer
3. Check that the measured pressure is as the prescribed supply pressure
4. Perform the test when the appliance is burning on full and with only the pilot alight
5. If the pressure is low, check the gas supply pipes are to a correct sizing
6. If the pressure is too high (more than 5 mbar over) the appliance may be installed, but the gas supply company
should be contacted
7. Release the screw on the Burner Pressure test point on the gas valve and connect a manometer
8. Check that the measured pressure is as detailed in the Technical details
9. The measured value should be /- 10% of the described value. If this is not the case, please contact the
supplier.
Note: After checking the pressures and removing the manometers, the screws in the Pressure Test points must be
closed, and the system must be checked for gas-tightness.
Содержание Iconic 500
Страница 3: ...IE GB 3 Iconic 500 Top Flue Iconic 500 Rear Flue...
Страница 5: ...IE GB 5 Iconic 600 Top Flue Iconic 600 Rear Flue...
Страница 9: ...IE GB 9...
Страница 10: ...IE GB 10...
Страница 11: ...IE GB 11...
Страница 12: ...IE GB 12...
Страница 16: ...IE GB 16 3 3 3 Mantel Clearances 3 3 3 Combustible Mantel Side view...