3.6 Commissioning the Appliance 

3.6.1 Pilot Ignition Check 

1.  Ignite the pilot light as described in the User Instructions 

2.  Check that the pilot flame stays alight 

3.  Extinguish the pilot light 

3.6.2 Main Burner Check 

1.  Ignite the pilot light as described in the User Instructions 
2.  Turn on the main burner as described in the User Instructions 
3.  Check that the pilot smoothly cross-lights to the main burner and that the main burner and pilot stay alight 
4.  Extinguish the appliance fully 
 

3.6.3 Pressure Check 

The appliance is preset to give the correct heat inputs as listed in the technical details. No further adjustment is 
necessary. Always check the inlet pressure and burner pressure. 
 
1.  Turn off the gas valve on the appliance 
2.  Release the screw on the Inlet Pressure test point on the gas valve and connect a pressure guage Manometer 
3.  Check that the measured pressure is as the prescribed supply pressure 
4.  Perform the test when the appliance is burning on full and with only the pilot alight 
5.  If the pressure is low, check the gas supply pipes are to a correct sizing 
6.  If the pressure is too high (more than 5 mbar over) the appliance may be installed, but the gas supply company 
should be contacted 
7.  Release the screw on the Burner Pressure test point on the gas valve and connect a manometer 
8.  Check that the measured pressure is as detailed in the Technical details 
9.  The measured value should be /- 10% of the described value. If this is not the case, please contact the 
supplier. 
 
Note: After checking the pressures and removing the manometers, the screws in the Pressure Test points must be 
closed, and the system must be checked for gas-tightness. 
 

 

Содержание Iconic 500

Страница 1: ...ta However to install appliance in other countries modification of the appliance and its method of installation may be necessaryin order to use the appliance safely and correctly The manual for the lo...

Страница 2: ...IE GB 2 This Manual covers models Iconic 500 and Iconic 600 Iconic 500 a Please Note Flue size 100 mm b Please Note the Adjustable Legs could be adjusted from 17 50mm...

Страница 3: ...IE GB 3 Iconic 500 Top Flue Iconic 500 Rear Flue...

Страница 4: ...IE GB 4 Iconic 600 a Please Note Flue size 100 mm b Please Note the Adjustable Legs could be adjusted from 17 50mm...

Страница 5: ...IE GB 5 Iconic 600 Top Flue Iconic 600 Rear Flue...

Страница 6: ...hour or F 12 hour clock 10 Setting the Time 10 To Turn OFF the appliance 11 Adjusting the Flame setting 11 2 6 Cleaning and Maintenance 13 3 Installation instructions 14 3 1 Gas Connection 14 3 2 Ven...

Страница 7: ...this appliance may be used This appliance is rated at 6 9kW and as such needs no additional ventilation However an adequate supply of fresh air to maintain temperatures and a comfortable environment...

Страница 8: ...r the Receiver instead of the 4 AA batteries Only an AC Mains Adapter supplied by Heat Design may be used The Mains Adaptor is plugged into the DC 6V socket on the end of the receiver Note if the AC M...

Страница 9: ...IE GB 9...

Страница 10: ...IE GB 10...

Страница 11: ...IE GB 11...

Страница 12: ...IE GB 12...

Страница 13: ...ensure that the appliance is working correctly and safely It is advisable to clean the appliance of any dust and debris before and regularly during the heating season and especially if the appliance h...

Страница 14: ...length The appliance should be fitted with a minimum clearance of 100mm from any combustible objects or materials this includes any combustible materials used for the fireplace construction This clea...

Страница 15: ...IE GB 15 3 3 2 Built In Fireplace Sizing assuming a Cement Board Lining is used Appliance A min B min C min D min E min F min Iconic 500 563 365 715 351 149 663 Iconic 600 680 302 832 351 149 600...

Страница 16: ...IE GB 16 3 3 3 Mantel Clearances 3 3 3 Combustible Mantel Side view...

Страница 17: ...specified parts 3 4 2 Timber Frame Construction Whilst it is possible to install room sealed appliances in timber frame properties great care needs to be taken to ensure that the flue assembly does n...

Страница 18: ...burner to the first slot inside the fence of the pilot shield When commissioning or servicing the Appliance Cross Lighting must be checked to ensure smooth lighting of the main burner from the Pilot F...

Страница 19: ...ut Scatter the Embers over the top of the burner as shown KEEPING THE PILOT AREA CLEAR Position the 8 logs as shown Lay the glow strands amongst the logs in the flames to create an enhanced Glow 1 2 3...

Страница 20: ...IE GB 20 5 6 8 4 7 Position the Log 8 as shown in the diagram Finaly Check the appliance for Pilot ignition and cross lighting ensuring that no material is impinging the opertion of the Pilot...

Страница 21: ...2 Scatter the Embers over the top of the burner as shown KEEPING THE PILOT AREA CLEAR Position the 8 logs as shown Lay the glow strands Embers amongst the logs in the flames to create an enhanced Glow...

Страница 22: ...IE GB 22 4 5 6 7 8 Position the Log 8 as shown in the diagram Finaly Check the appliance for Pilot ignition and cross lighting ensuring that no material is impinging the opertion of the Pilot...

Страница 23: ...iance 2 Release the screw on the Inlet Pressure test point on the gas valve and connect a pressure guage Manometer 3 Check that the measured pressure is as the prescribed supply pressure 4 Perform the...

Страница 24: ...est setting pressures P Check the safe operation of the appliance 4 1 Cleaning the Ceramics Remove the ceramics as detailed in A E above Gently clean the ceramics in the open air using a soft brush an...

Страница 25: ...ZP2 312 ODS Pilot Assembly LPG G30 ZP2 271 ODS Electrode Lead G60 ZKIS1 ODS Injector Natural EG05177 320 EG05177 400 Complete Burner Assembly Natural 2A01105 2A01105 6 Complete Burner Assembly LPG 2A0...

Страница 26: ...30 mbar GR Greece I2H G20 at 20 mbar I3 G31 G31 at 28 37 mbar I3P 37 G31 at 37 mbar I3B P 30 G30 G31 at 30 mbar HU Hungary I3B P 30 G30 G31 at 30 mbar HR Croatia I2H G20 at 20 mbar I3P 37 G31 at 37 m...

Страница 27: ...Burner Pressure hot mbar 17 17 23 23 17 5 28 28 36 29 Injector Marking 320 120 Pilot SIT ODS OP9043 SIT ODS OP9288 Efficiency Class 1 Nox Class 5 Gas type G20 G20 G25 G25 G20 G25 G30 G31 G31 I2H I2E I...

Страница 28: ...IE GB 28 60 Hawthorn Road Western Industrial Estate Dublin 12 D12 E2WF Ireland Tel 353 1 4089192 Fax 353 1 4089193 Web www heatdesign ie Email technical heatdesign ie...

Отзывы: