Installation Manual 

15

ENGLISH

Installation

1. Route the indoor tubing and the drain hose to

the required piping hole position.

2. Insert the piping, drain hose, and the

connecting cable into the piping hole.

3. Insert the connecting cable into the indoor unit.

• Don't connect the cable to the indoor unit.
• Make a small loop with the cable for easy

connection later.

4. Tape the drain hose and the connecting

cables.

5. Indoor unit installation

• Hang the indoor unit from the hooks at the

top of the installation plate.

• Insert the spacer etc. between the indoor

unit and the installation plate and separate
the bottom of the indoor unit from the wall.

Connecting the piping to the indoor unit and
the drain hose to drain pipe.

1. Align the center of the pipes and sufficiently

tighten the flare nut by hand.

2. Tighten the flare nut with a wrench.

3. When extending the drain hose at the indoor

unit, install the drain pipe.

For left rear piping 

Drain pipe

Connecting

cable

Installation plate

Spacer

Indoor unit

8cm(3.15in)

Indoor unit tubing

Flare nut

Pipes

Wrench

Indoor unit tubing

Connection pipe

Flare nut

Open-end wrench (fixed)

Vinyl tape

Adhesive

Drain hose

Indoor unit drain hose

(narrow)

mm

inch

kg.m

lb.ft

Ø6.35

1/4

1.8~2.5

13~18

Ø9.52

3/8

3.4~4.2

24.6~30.4

Ø12.7

1/2

5.5~6.6

39.8~47.7

Ø15.88

5/8

6.3~8.2

45.6~59.3

Outside diameter

Torque

Содержание VMC09SB-1 Service

Страница 1: ...Wall Mounted Inverter Mini Split System VMH09SB 1 VMC09SB 1 VMH12SB 1 VMC12SB 1 VMH18SB 1 VMC18SB 1 VMH24SB 1 VMC24SB 1 ...

Страница 2: ...ir purging 24 Test running 26 Installation guide at the seaside 28 Four type A screws plastic anchors Connecting cable Installation guide map Pipes Gas side Liquid side Insulation materials Additional drain pipe Outer diameter 15 5mm 0 61in Two type B screws Level gauge Screw driver Electric drill Hole core drill ø70mm 2 76in Horizontal meter Flaring tool set Specified torque wrenches 1 8kg m 4 2k...

Страница 3: ...se a power cord a plug or a loose socket which is damaged Otherwise it may cause a fire or electrical shock For installation of the product always contact the service center or a professional installation agency Otherwise it may cause a fire electrical shock explosion or injury Securely attach the electrical cover to the indoor unit and the service panel to the outdoor unit If the electrical cover...

Страница 4: ...rp and may cause injury Do not share the outlet with other appliances It will cause an electric shock or a fire due to heat generation Do not use the damaged power cord Otherwise it may cause a fire or electrical shock Do not modify or extend the power cord randomly Otherwise it may cause a fire or electrical shock Take care so that the power cord may not be pulled during operation Otherwise it ma...

Страница 5: ...ct Keep level parallel in installing the product Otherwise it may cause vibration or water leakage Avoid excessive cooling and perform ventilation sometimes Otherwise it may do harm to your health Use a soft cloth to clean Do not use wax thinner or a strong detergent The appearance of the air conditioner may deteriorate change color or develop surface flaws Do not use an appliance for special purp...

Страница 6: ...This symbol alerts you to hazards that may cause harm to the air conditioner This symbol indicates special notes NOTICE Introduction Symbols used in this Manual Features Air Inlet Front Panel Air Filter Signal Receptor Air Intake Vents Base Plate Air Outlet Vents Connecting Wires Drain Hose ...

Страница 7: ...pe B screw Remote control holder Remote control holder Type 1 Type 2 Installation plate Installation plate Figure Figure Name Screw driver Electric drill Measuring tape Knife Hole core drill Spanner Torque wrench Ohmmeter Hexagonal wrench Ammeter Gas leak detector Thermometer Horizontal meter Flaring tool set Name Installation Parts Installation Tools ...

Страница 8: ...arrying out a drainage test To carry out the drainage test remove the air filters and pour water into the heat exchanger Saddle Gas side piping Optional Parts Liquid side piping Optional Parts Additional drain pipe Vinyl tape Narrow Drain Hose Base Plate Air Outlet Vents Air Inlet Vents Connecting cable Optional Parts Installation plate Sleeve Bushing Sleeve Putty Gum Type Sealer Bend the pipe as ...

Страница 9: ...f an awning is built over the unit to prevent direct sunlight or rain exposure make sure that heat radiation from the condenser is not restricted 2 Ensure that the space around the back and sides is more than 30cm 11 8in The front of the unit should have more than 70cm 27 6in of space 3 Do not place animals and plants in the path of the warm air 4 Take the weight of the air conditioner into accoun...

Страница 10: ...ed on standard length and maximum allowance length is on the basis of reliability Oil trap should be installed every 5 7 meters 16 4 23 0ft 9k 12k 9 52 3 8 6 35 1 4 7 5 25 7 23 15 49 20 0 22 18k 12 7 1 2 6 35 1 4 7 5 25 7 23 15 49 20 0 22 24k 15 88 5 8 9 52 3 8 7 5 25 15 49 30 98 30 0 33 Pipe Siz e Capacity Btu h GAS LIQUID Max Length A m ft Additional Refrigerant g m oz ft Max Elevation B m ft St...

Страница 11: ...must be done safely 3 Install after removing one of the indicated cutting phase according to the installation location of the indoor unit s piping Fixing Installation Plate Drill the piping hole with a ø70mm 2 76in hole core drill Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side Drill a Hole in the Wall 5 7mm 3 16 5 16 Indoor WALL Outdoor A B...

Страница 12: ...e in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing Putting nut on Remove flare nuts attached to indoor and outdoor unit then put them on pipe tube having completed burr removal not possible to put them on after flaring work Flaring work 1 Firmly hold copper pipe in a Bar in the dimension shown in the table below 2 Carry out flaring work with the flaring ...

Страница 13: ...oor unit through the piping hole Do not connect the cable to the indoor unit Make a small loop with the cable for easy connection later 3 Tape the tubing drain hose and the connecting cable Be sure that the drain hose is located at the lowest side of the bundle Locating at the upper side can cause drain pan to overflow inside the unit If the drain hose is routed inside the room insulate the hose w...

Страница 14: ...nd the connecting portion 1 Overlap the connection pipe insulation material and the indoor unit pipe insulation material Bind them together with vinyl tape so that there may be no gap 2 Wrap the area which accommodates the rear piping housing section with vinyl tape 3 Bundle the piping and drain hose together by wrapping them with vinyl tape for enough to cover where they fit into the rear piping ...

Страница 15: ...installation plate and separate the bottom of the indoor unit from the wall Connecting the piping to the indoor unit and the drain hose to drain pipe 1 Align the center of the pipes and sufficiently tighten the flare nut by hand 2 Tighten the flare nut with a wrench 3 When extending the drain hose at the indoor unit install the drain pipe For left rear piping Drain pipe Connecting cable Installati...

Страница 16: ...o the rear piping housing section Reroute the pipings and the drain hose across the back of the chassis Indoor unit installation 1 Remove the spacer 2 Ensure that the hooks are properly seated on the installation plate by moving it left and right 3 Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots clicking sound Plastic bands In...

Страница 17: ...Best Practice Press on the upper side of clamp and unfold the tubing to downward slowly Worst Practice Following bending type from right to left may cause damage to the tubing Installation Information For left piping Follow the instruction below ...

Страница 18: ...ks When tightening the flare nut with torque wrench ensure the direction for tightening follows the arrow on the wrench Outdoor unit Liquid side piping Smaller diameter Gas side piping Bigger diameter Torque wrench mm inch kg m lb ft Ø6 35 1 4 1 8 2 5 13 18 Ø9 52 3 8 3 4 4 2 24 6 30 4 Ø12 7 1 2 5 5 6 6 39 8 47 7 Ø15 88 5 8 6 3 8 2 45 6 59 3 Ø19 05 3 4 9 9 12 1 71 6 87 5 Outside diameter Torque ...

Страница 19: ...t the wires firmly so that not to be pulled out easily Connect the wires according to color codes by referring to the wiring diagram Provide a circuit breaker between power source and the outdoor unit as shown below The power cord connected to the outdoor unit should be complied with the following specifications ETL recognized and CSA certified The power connecting cable connected to the indoor an...

Страница 20: ...rical wiring capable of withstanding temperature up to 75 C 167 F 3 Use outdoor and waterproof connection cable rated more than 300V for the connection between indoor and outdoor unit For example Type SJO WA Be sure to comply with local codes while running the wire from the indoor unit to the outdoor unit size of wire and wiring method etc Every wire must be connected firmly No wire should be allo...

Страница 21: ... inside of control cover 2 The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation Check them and make sure that they are all tightly fastened If they are loose it could cause burn out of the wires 3 Specification of power source 4 Confirm that electrical capacity is sufficien...

Страница 22: ...y leakage and goes out the drain exit Drain piping 1 The drain hose should point downward for easy drain flow 2 Do not make drain piping like the following Drain pan Drain hose Leakage checking Connecting area drain hose Leakage checking Downward slope Do not raise Accumulated drain water Tip of drain hose dipped in water Air Kinking Water leakage Water leakage Ditch Less than 50mm gap Water leaka...

Страница 23: ...se and connecting cable from down to up 2 Secure the tapped piping along the exterior wall using saddle or equivalent In cases where the Outdoor unit is installed above the Indoor unit perform the following 1 Tape the piping and connecting cable from down to up 2 Secure the taped piping along the exterior wall Form a trap to prevent water entering the room 3 Fix the piping onto the wall by saddle ...

Страница 24: ...h pressure gauges and dry nitrogen gas cylinder to this service port with charge hoses Be sure to use a manifold valve for air purging If it is not available use a stop valve for this purpose The Hi knob of the manifold valve must always be kept close Pressurize the system to no more than 150 P S I G with dry nitrogen gas and close the cylinder valve when the gauge reading reached 150 P S I G Next...

Страница 25: ...hed close the Lo and Hi knob of the manifold valve and stop the vacuum pump Finishing the job 1 With a service valve wrench turn the valve stem of liquid side valve counter clockwise to fully open the valve 2 Turn the valve stem of gas side valve counter clockwise to fully open the valve 3 Loosen the charge hose connected to the gas side service port slightly to release the pressure then remove th...

Страница 26: ...en installing on the wall roof or rooftop anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake 3 If the vibration of the unit is transmitted to the hose secure the unit with an anti vibration rubber Evaluation of the performance Operate the unit for 15 20 minutes then check the system refrigerant charge 1 Measure the pressure of the gas side service v...

Страница 27: ...of refrigerant Be sure to perform Pump Down procedure in the cooling mode Pump Down Procedure 1 Connect a low pressure gauge manifold hose to the charge port on the gas side service valve 2 Open the gas side service valve halfway and purge the air in the manifold hose using the refrigerant 3 Close the liquid side service valve all the way 4 Turn on the unit s operating switch and start the cooling...

Страница 28: ...atment on the heat exchanger Periodic more than once year cleaning of the dust or salt particles stuck on the heat exchanger by using water Selecting the location Outdoor Unit 1 If the outdoor unit is to be installed close to the seaside direct exposure to the sea wind should be avoided Install the outdoor unit on the opposite side of the sea wind direction 2 In case to install the outdoor unit on...

Страница 29: ...Specifications and performance data subject to change without notice HEAT CONTROLLER INC 1900 WELLWORTH AVENUE JACKSON MICHIGAN 49203 THE QUALITY LEADER IN CONDITIONING AIR Jan 2008 P No MFL39817304 ...

Отзывы: