Heat Controller
HEV-HEH SEriES
Design Guide
11
11
Heat Controller, LLC
HEV/H SERIES
Engineering Design Guide
Performance Data
HEV/H 030 - Part Load
750 CFM Rated Air
ow
Performance capacities shown in thousands of Btuh
EWT
°F
GPM
WPD
Cooling - EAT 80/67°F
Heating - EAT 70°F
PSI FT
TC
SC
KW
HR
EER HWG
HC
KW
HE
LAT
COP HWG
20
Operation Not
Recommended
Operation Not Recommended
Operation Not Recommended
6.0
4.3
9.9
15.7
1.5
10.6
87.3
3.1
2.1
30
3.0
1.7
4.0
27.1
17.7
0.9
30.0
31.9
0.8
17.2
1.5
12.0
89.1
3.3
2.1
4.5
2.7
6.3
27.3
17.7
0.8
30.0
34.5
0.8
17.8
1.5
12.6
89.9
3.4
2.2
6.0
3.8
8.9
27.3
17.8
0.8
29.9
35.7
0.9
18.2
1.5
13.0
90.4
3.5
2.2
40
3.0
1.3
3.0
26.5
17.4
1.0
29.8
27.7
1.0
19.5
1.5
14.2
92.0
3.7
2.3
4.5
2.2
5.0
26.9
17.6
0.9
30.0
30.5
0.9
20.3
1.6
14.9
92.9
3.8
2.3
6.0
3.1
7.3
27.1
17.7
0.9
30.0
31.9
0.8
20.7
1.6
15.3
93.5
3.9
2.4
50
3.0
0.9
2.0
25.7
17.1
1.1
29.4
23.6
1.3
21.8
1.6
16.4
94.9
4.0
2.4
4.5
1.6
3.6
26.3
17.3
1.0
29.7
26.3
1.1
22.7
1.6
17.3
96.0
4.2
2.5
6.0
2.4
5.6
26.5
17.4
1.0
29.8
27.7
1.0
23.2
1.6
17.7
96.6
4.2
2.6
60
3.0
0.8
1.9
24.6
16.6
1.2
28.8
19.9
1.8
24.2
1.6
18.6
97.8
4.4
2.6
4.5
1.5
3.4
25.3
16.9
1.1
29.2
22.3
1.5
25.2
1.6
19.6
99.1
4.5
2.7
6.0
2.3
5.3
25.6
17.1
1.1
29.4
23.6
1.3
25.8
1.7
20.2
99.8
4.6
2.8
70
3.0
0.8
1.8
23.4
16.1
1.4
28.2
16.7
2.5
26.6
1.7
20.9
100.7
4.7
2.9
4.5
1.4
3.2
24.2
16.4
1.3
28.6
18.7
2.0
27.7
1.7
22.0
102.2
4.8
3.0
6.0
2.2
5.0
24.5
16.6
1.2
28.8
19.8
1.8
28.4
1.7
22.6
102.9
4.9
3.0
80
3.0
0.8
1.8
22.1
15.5
1.6
27.5
13.9
3.3
29.0
1.7
23.2
103.7
5.0
3.1
4.5
1.4
3.2
22.9
15.9
1.5
27.9
15.5
2.8
30.2
1.7
24.4
105.3
5.2
3.2
6.0
2.1
4.9
23.3
16.1
1.4
28.1
16.5
2.5
30.9
1.7
25.1
106.1
5.3
3.3
90
3.0
0.8
1.8
20.7
14.9
1.8
26.8
11.5
4.3
31.3
1.7
25.4
106.6
5.3
3.4
4.5
1.4
3.2
21.5
15.3
1.7
27.2
12.9
3.7
32.8
1.7
26.8
108.3
5.5
3.5
6.0
2.1
4.8
21.9
15.5
1.6
27.4
13.6
3.4
33.5
1.8
27.5
109.3
5.6
3.6
100
3.0
0.7
1.7
19.3
14.3
2.0
26.3
9.5
5.5
Operation Not Recommended
4.5
1.3
3.0
20.1
14.7
1.9
26.6
10.6
4.8
6.0
2.0
4.6
20.5
14.8
1.8
26.8
11.3
4.4
110
3.0
0.7
1.5
18.0
13.7
2.3
25.8
7.9
6.8
4.5
1.2
2.8
18.8
14.0
2.1
26.1
8.8
6.0
6.0
1.9
4.4
19.2
14.2
2.1
26.2
9.3
5.6
120
3.0
0.6
1.4
4.5
1.1
2.6
17.5
13.5
2.4
25.7
7.3
7.5
6.0
1.8
4.1
17.9
13.6
2.3
25.8
7.7
7.0
†ARI/ASHRAE/ISO 13256-1 (WLHP applications) certi
ed conditions are 86°F EWT, 80.6°F DB / 66.2°F WB
EAT in cooling and 68°F DB / 59°F WB EAT in heating.
Interpoaltion is permissable, extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling and 70°F DB in heating
All performance data is based upon the lower voltage of dual voltage rated units
See performance correction tables for operating conditions other than those listed above.
Operation below 60°F EWT requires optional insulated water circuit.
Operation below 40°F EWT is based upon 15% antifreeze solution.