Heat Controller H 006 Скачать руководство пользователя страница 23

CXM Control

For detailed control information, see CXM Electronic Heat 
Pump Control Application, Operation and Maintenance 
Guide.

Field Selectable Inputs

Test mode: Test mode allows the service technician to 
check the operation of the control in a timely manner. By 
momentarily shorting the test terminals, the CXM control 
enters a 0 minute test mode period in which all time 
delays are sped up 15 times. Upon entering test mode, 
the status LED will flash a code representing the last fault. 
For diagnostic ease at the thermostat, the alarm relay will 
also cycle during test mode. The alarm relay will cycle 
on and off similar to the status LED to indicate a code 
representing the last fault, at the thermostat. Test mode 
can be exited by shorting the test terminals for  seconds.
Retry Mode: If the control is attempting a retry of a fault, 
the status LED will slow flash (slow flash = one flash 
every  seconds) to indicate the control is in the process 
of retrying.

Field Configuration Options

Note: In the following field configuration options, jumper 
wires should be clipped ONLY when power is removed 
from the CXM control.

Air coil low temperature limit setting: Jumper  (JW-FP 
Low Temp) provides field selection of temperature limit 
setting for FP of 0°F or 10°F [-1°F or -1°C] (refrigerant 
temperature).  Note: This jumper should only be clipped 
under extenuating circumstances, as recommended by 
Heat Controller technical services.

Not Clipped = 0°F [-1°C]. Clipped = 10°F [-1°C].
Alarm relay setting: Jumper 1 (JW1-AL Dry) provides 
field selection of the alarm relay terminal AL to be 
jumpered to 4VAC or to be a dry contact (no connection).

Not Clipped = AL connected to R. Clipped = AL dry 

contact (no connection).

DIP Switches

Note: In the following field configuration options, DIP 
switches should only be changed when power is removed 
from the CXM control.
DIP switch 1: Unit Performance Sentinel Disable - 
provides field selection to disable the UPS feature.

On = Enabled. Off = Disabled.
DIP switch :

On = Always

DIP switch : Not Used.
DIP switch 4: DDC Output at EH - provides selection for 
DDC operation. If set to “DDC Output at EH,” the EH 
terminal will continuously output the last fault code of 
the controller. If set to “EH normal,” EH will operate as 
standard electric heat output.

On = EH Normal. Off = DDC Output at EH.

DIP switch 5: Factory Setting - Normal position is “On.” 
Do not change selection unless instructed to do so by  
the factory.

Description of Operation

LED

Alarm Relay

Normal Mode

On

Open

Normal Mode with UPS Warning

On

Cycle (closed 5 sec., Open 5 sec.)

CXM is non-functional

Off

Open

Fault Retry

Slow Flash

Open

Lockout

Fast Flash

Closed

Over/Under Voltage Shutdown

Slow Flash

Open (Closed after 15 minutes)

Test Mode - No fault in memory

Flashing Code 1

Cycling Code 1

Test Mode - HP Fault in memory Flashing Code

Cycling Code 

Test Mode - LP Fault in memory

Flashing Code

Cycling Code 

Test Mode - FP1 Fault in memory Flashing Code 4

Cycling Code 4

Test Mode - FP Fault in memory Flashing Code 5

Cycling Code 5

Test Mode - CO Fault in memory Flashing Code 6

Cycling Code 6

Test Mode - Over/Under
shutdown in memory

Flashing Code 7

Cycling Code 7

Test Mode - UPS in memory

Flashing Code 8

Cycling Code 8

Test Mode - Swapped Thermistor Flashing Code

Cycling Code 

CXM CONTROLS

Table 6: CXM LED And Alarm  
Relay Operations

CONTROLS - SAFETY FEATURES 

Safety Features – CXM Control

The safety features below are provided to protect 
the compressor, heat exchangers, wiring and other 
components from damage caused by operation outside of 
design conditions.

Anti-short cycle protection: The control features a 5 
minute anti-short cycle protection for the compressor.
Note: The 5 minute anti-short cycle also occurs at power up.
Random start: The control features a random start upon 
power up of 5-80 seconds.
Fault Retry: In Fault Retry mode, the Status LED begins 
slowly flashing to signal that the control is trying to 
recover from a fault input. The control will stage off the 
outputs and then “try again” to satisfy the thermostat 
input call. Once the thermostat input call is satisfied, 
the control will continue on as if no fault occurred. If  
consecutive faults occur without satisfying the thermostat 
input call, the control will go into “lockout” mode. The 
last fault causing the lockout will be stored in memory 
and can be viewed by going into test mode on the CXM 
board.  Note:  FP1/FP faults are factory set at only one 
try.
Lockout: In lockout mode, the status LED will begin fast 
flashing. The compressor relay is turned off immediately. 
Lockout mode can be “soft” reset by turning off the 
thermostat (or satisfying the call). A “soft” reset keeps 
the fault in memory but resets the control.  A “hard” reset 
(disconnecting power to the control) resets the control 
and erases fault memory.
Lockout with emergency heat: While in lockout mode, if W 
becomes active, emergency heat mode will occur.

-Slow Flash = 1 flash every  seconds
-Fast Flash =  flashes every 1 second
-Flash code  =  quick flashes, 10 second pause,  quick  

flashes, 10 second pause, etc.

-On pulse 1/ second; off pulse 1/ second

Содержание H 006

Страница 1: ...ns Commercial Water Source Heat Pumps HEAT CONTROLLER INC 1900 Wellworth Ave Jackson Michigan 49203 Ph 517 787 2100 Fax 517 787 9341 www heatcontroller com THE QUALITY LEADER IN CONDITIONING AIR Insta...

Страница 2: ...and High Static Z Straight and High Static Y Back and High Static 1 2 3 456 7 8 9 10 11 12 13 14 Table of Contents Model Nomenclature 1 Storage 3 Pre Installation 3 Physical Data 4 Dimensional Data 5...

Страница 3: ...ts as a source of heating or cooling during the construction process The mechanical components and filters will quickly become clogged with construction dirt and debris which may cause system damage W...

Страница 4: ...the unit and its operation Thoroughly check the system before operation Prepare units for installation as follows 1 Compare the electrical data on the unit nameplate with ordering and shipping inform...

Страница 5: ...x 24 610 x 610 24 x 24 610 x 610 1 14 x 24 1 18 x 24 Weight Operating lbs kg 103 47 105 48 114 52 181 82 189 86 197 89 203 92 218 99 263 119 278 126 Weight Packaged lbs kg 113 51 115 52 124 56 186 84...

Страница 6: ...0 8 1 8 0 8 1 2 8 1 5 1 2 1 0 8 8 9 6 7 5 2 1 3 16 1 9 8 1 1 0 6 cm 48 5 86 6 27 9 24 4 2 0 4 4 2 0 20 6 13 0 5 4 1 9 22 7 17 0 13 3 3 3 41 0 25 0 2 7 1 5 018 in 20 1 43 1 17 1 15 3 2 4 1 9 2 1 1 2 12...

Страница 7: ...5 55 9 3 6 7 1 24 0 7 1 15 6 5 9 7 3 14 9 22 5 22 7 12 9 22 9 22 9 14 0 5 3 41 1 25 1 1 9 018 in 21 5 21 5 39 0 1 8 3 8 15 2 3 6 8 1 2 3 1 2 4 1 7 1 10 1 6 4 3 8 14 0 14 0 5 3 2 3 18 3 20 2 0 7 cm 54...

Страница 8: ...electrical cables and other items that prohibit future removal of components or the unit itself 4 Use a manual portable jack lift to lift and support the weight of the unit during installation and se...

Страница 9: ...ower Disconnect Power Wiring Insulated supply duct with at least one 90 deg elbow to reduce air noise Return Air Supply Air Unit Hanger 3 8 10mm threaded rods Unit Power Flexible Duct Connector Figure...

Страница 10: ...position as shown being careful with the blower wiring 3 Check blower wire routing and connections for tension or contact with sheet metal edges Reroute if necessary 4 Check refrigerant tubing for con...

Страница 11: ...19mm ID plastic hose Insure that the hose is without kinks to maintain unobstructed flow of condensate from the unit to the drain Verify that condensate line is pitched towards the drain 1 4 per foot...

Страница 12: ...eyond all four edges of the unit 2 Provide adequate clearance for filter replacement and drain pan cleaning Do not block filter access with piping conduit or other materials Refer to unit submittal da...

Страница 13: ...r neoprene isolation pad to minimize vibration transmission to the building structure Figure 9 Vertical Sound Attenuation Condensate Piping Vertical Units Vertical units utilize a condensate hose insi...

Страница 14: ...compound is preferred use compound only in small amounts on the external pipe threads of the fitting adapters Prevent sealant from reaching the flared surfaces of the joint Note When anti freeze is us...

Страница 15: ...ed pumping systems may also be included in the external piping The piping system should be flushed to remove dirt piping chips and other foreign material prior to operation see Piping System Cleaning...

Страница 16: ...s are OK to 0 5 ppm Ammonia ion All 0 5 ppm as hydroxide chloride nitrate and sulfate compounds Maximum Maximum Allowable at maximum water temperature Chloride Levels 50 F 10 C 75 F 24 C 100 F 38 C Co...

Страница 17: ...0 1 80 7 5 8 9 15 5 575 60 3 518 633 1 4 7 39 0 1 40 6 1 7 2 15 1 208 230 60 1 197 254 1 25 6 170 0 4 30 29 9 36 4 60 V H060 3 208 230 60 3 197 254 1 14 7 124 0 4 30 19 0 22 7 35 4 460 60 3 414 506 1...

Страница 18: ...size Grnd Rev 5 17 01 B Capacitor WARNING Disconnect electrical power source to prevent injury or death from electrical shock 208 Volt Operation All commercial 208 230 Volt units are factory wired fo...

Страница 19: ...mostat should be wired directly to the CXM board Figure 19 Low Voltage Field Wiring Low Water Temperature Cutout The CXM control senses low water temperature utilizing thermistor FP1 Note that the FP1...

Страница 20: ...60 seconds to open very little water will flow before 45 seconds Once fully open an end switch allows the compressor to be energized Only relay or triac based electronic thermostats should be used wit...

Страница 21: ...ermostat wires protrude through the middle of the back plate Mark the position of the back plate mounting holes and drill holes with a 3 16 5mm bit Install supplied anchors and secure plate to the wal...

Страница 22: ...21 TYPICAL WIRING DIAGRAM HCH HCV UNITS WITH CXM BOARD SINGLE PHASE...

Страница 23: ...Description of Operation LED Alarm Relay Normal Mode On Open Normal Mode with UPS Warning On Cycle closed 5 sec Open 5 sec CXM is non functional Off Open Fault Retry Slow Flash Open Lockout Fast Flash...

Страница 24: ...ds normal operation is restored This is not considered a fault or lockout If the CXM is in over under voltage shutdown for 15 minutes the alarm relay will close Over under voltage shut down code 7 Uni...

Страница 25: ...gle most important step to insure proper start up and continued efficient operation of the system Follow the instructions below to properly clean and flush the system 1 Insure that electrical power to...

Страница 26: ...and adjust water pH if necessary to maintain a level between 6 and 8 5 Proper pH promotes longevity of hoses and fittings see table 3 System flushing Verify that all hoses are connected end to end wh...

Страница 27: ...thermostat to the lowest setting Place the thermostat mode switch in the HEAT position b Slowly raise the thermostat to a higher temperature until the compressor activates c Check for warm air deliver...

Страница 28: ...27 Table 8e HCH_HCV Coax Water Pressure UNIT OPERATING CONDITIONS Table 9 Water Temperature Change Through Heat Exchanger...

Страница 29: ...per Sub Temp Temp Pressure Pressure Super Sub Temp Temp Temp F GPM ton PSIG PSIG heat cooling Rise F Drop F DB PSIG PSIG heat cooling Drop F DB Rise F 1 5 66 75 160 1 0 10 0 6 16 0 0 5 60 70 05 0 10 1...

Страница 30: ...produce a slimy substance in the drain pan it may be necessary to treat the drain pan chemically with an algaecide approximately every three months to minimize the problem The condensate pan may also...

Страница 31: ...heck static vs blower table X Air Temperature out of range Too much cold vent air Bring entering air temp within design parameters X Improper temperature limit setting 30 F vs 10 F Normal airside appl...

Страница 32: ...X X Inlet Water too Hot or Cold Check load loop sizing loop backfill ground moisture High Head Pressure X Reduced or no Air flow Check for dirty air filter and clean or replace in heating Check fan m...

Страница 33: ..._______ flow rate diff factor _____________ Btu hr Superheat Subcooling Suction temperature suction saturation temp Discharge saturation temp liquid line temp deg F deg F Look up pressure drop in I O...

Страница 34: ...4006 1900 WELLWORTH AVENUE JACKSON MICHIGAN 49203 THE QUALITY LEADER IN CONDITIONING AIR visit us at www heatcontroller com Specifications and performance data subject to change without notice 97B0016...

Отзывы: