Heat Controller GMDA Скачать руководство пользователя страница 38

FIGURE 27

TROUBLESHOOTING FLOWCHART

GO TO

E

WARNING

INTEGRATED FURNACE CONTROL (IFC)

TROUBLESHOOTING GUIDE

HAZARDOUS VOLTAGE

LINE VOLTAGE

CONNECTIONS

DISCONNECT POWER BEFORE SERVICING.
SERVICE MUST BE BY A TRAINED, QUALIFIED
SERVICE TECHNICIAN.

NOTE: Most failures are not due to the IFC. Double check all other
possibilities, including the ground connection, before replacing the IFC.

NOTE: Always verify gas valve inlet and outlet gas
pressure.

KEY TO ABBREVIATIONS

IBM = Indoor Blower Motor
IDM = Induced Draft Motor
IFC = Integrated Furnace Control
PS = Pressure Switch(es)
SE = Spark Electrode
HSI = Hot-Surface Ignition
DSI = Direct-Spark Ignition

FLAME (AMBER) LED CODES

OFF = No Flame Present
RAPID BLINK = Unexpected Flame
SLOW BLINK = Marginal Flame Sense
STEADY ON = Normal Flame Sense

BLINK CODES (GREEN LED)

1 Blink - Soft lockout

Reset System power and
start over from beginning

2 Blinks - PS Circuit open

go to point “F.”

3 Blinks - Limit circuit open

go to point “D.”

4 Blinks - PS Circuit closed

Go to point “G.”

5 Blinks - Twin Fault (Optional)

*Go to point “H.”

1) Set FAN switch to “AUTO”
2) Set thermostat to call for heat (set temp. differ-

ential to greater than 10°F

Does the IDM Energize?

IDM Runs for 30 sec. pre-purge?

Spark Ignitor Electrode (SE) Energizes

or HSI Ignitor Glowing?

Does Main Burner Light and stay lit?

Is the gas valve energized?

PS dropping out?

Check IFC*

Does IBM start on heat speed 20 seconds

after burners light?

Does main burner remain lit until

heat call ends?

Does thermostat maintain reasonable room 

temperature near setpoint?

Set thermostat to off position (W to C = ØV)

Does gas valve shut off immediately?

Does IDM shut off after ten second post-purge?

Does IBM shut off after a max. of 3 min?

END

Heat-mode troubleshooting

“POWER” LED ON?

24V on W to IFC?

Is “STATUS” LED blinking,

steady-on, or off?

Check IFC*.

Check IFC*.

Does IDM run
indefinately.

Does IDM Run for 60 sec. and then off for Five minutes

- Check thermostat in “heat” mode,
battery, wire, and connections.

SEE BLINK CODES

- Check 24V at IFC.
- Check Fuse.
- Check Door Switch and Line Power.
- Check Transformer.
- Check Breaker.

- Check PS contacts
- Check wires for short.
- Check IFC*.
- Check switches and hoses for

water or moisture

- For Twinned units, check that both IFCs are set for “TWIN” and wires

are connected between “TWIN” terminals.

- Check IFC*.
- For twinned units, ensure transformers are in phase.

(if out of phase, flame LED will be dim).

- For non-twinned units, ensure “TWIN” is in the single (OFF) position.
- For Twinned units – ensure both IFC‘s have same part number.

- Check PS, PS Hoses, and wires.
- Check for blocked vent, excessive vent length or elbows, or

blocked heat exchanger.

- Check IDM wired correctly.
- Ensure against excessive wind, which can open pressure switch.
- If downflow 90+, check aux. limit – shoud be closed
- Check for intermittent P.S. operation.
- Check switches and hoses for water or moisture.

- Check gas supply and manifold pressure.
- Ensure L1 and Neutral not swapped on IFC and junction box.
- Check SE alignment.
- Check orifice or other restrictions to gas flow.
- Check flame sense rod (clean with sandpaper).
- Check flame carry over.

- Check wires, continuity, and connection between IFC and gas valve.
- Ensure 24 V between appropriate pins on connector of IFC.
- Ensure manual switch on valve is in the “ON” position.
- 90+ check aux. limit open? Should be closed
- 90+ upflow models – check drain pressure switch between IFC and

gas valve – should be closed – replace drain pressure switch if drain
is not blocked or clear drain if blocked.

- Did a pressure switch open during ignition trial? If yes, go to  F

- Did a limit open during ignition trial? If yes, go to  D

- Check line voltage between “HEAT” and “NEUTRAL” on IFC.
- Check wires, connections, and continuity between   IFC and IBM.
- Check IBM capacitor.
- Check IBM.

CHECK:
- grounding on IFC and unit.
- check for proper polarity between L1 & neutral.
- flame sense rod (clean if necessary).
- wire continually between flame sense rod and appropriate pin of

connector on IFC

- flame carries across all burners, and all burners stay lit.

CHECK:
AIRFLOW - ensure no restrictions, such as dirty filter, dampers, closed registers, etc.
LIMITS - ensure good wire and connections between IFC and all limits. Make sure
limits are not open when circulating air temperature is within a specified range.
ROLLOUTS - ensure rollouts or overtemperature limits do not need to be reset. Make
sure no flame rollout in burner compartment due to blocked flu or heat exchanger.
OVERFIRE - ensure furnace is not overtemperature (temp rise is above stated range).
Check gas valve, proper orifice size, gas pressure, etc.

Is Limit circuit or IDM wire through aux. limit open or
opening and closing?
Note: IFC Status LED should be blinking a Fault Code 3.

Is the IFC sensing a good flame: NOTE:
Flame sense light should be steady-on
when burners are lit. If flame LED blinking,
or off, flame sense is low or absent.

Ensure thermostat is properly placed and not improperly affected by
registers, fans, sunlight, heat through walls, pipes, or wires in walls.

- Check heat anticipator setting. Furnace may need an isolation relay.
- Check installation instructions under section titled “Isolation Relay” for

details.

- Verify correct furnace sizing.

NOTE: If IFC goes into lockout (“STATUS LED will blink code “1”), shut
off main power to unit, wait 30 seconds and then reset power.

PROBLEM

STILL

PRESENT

“STATUS” LED

BLINKING

“FLAME” LED BLINKING
OR STEADY ON

If “E” did not
resolve issue

Double check - Is W off at IFC?

(W to C = ØV?)

Voltage present at gas valve?

- Check gas valve.

SEE BLINK CODES

- Check IFC*.

Check IFC*.

*Most failures are not due to the IFC. Double
check all other possibilities, including the
ground connection or wire connections, before
replacing the IFC.

Ensure TSTAT is not in “FAN” position.
Is “STATUS” LED blinking?
Is “FLAME” LED blinking or steady-on?

**System will attempt to light 4 times. Voltage
is present at gas valve for only 7 seconds dur-
ing each trial for ignition. The entire system will
go into a 1 hour lockout after 4 attempts. The
main blower and IDM will run 180 seconds
between 2nd and 3rd ignition attempts.

- Check line voltage at IDM.
- Check wires and connections between IDM and IFC.
- Ensure line voltage on IDM pins of IFC connector.
- Check IDM capacitor (90+ only).

CHECK BLINK CODES

- Check for open limit or limit circuit.
- Check for intermittent PS operation.
- Check for vent restrictions.
- Ensure vent lengths not excessive or

too small diameter.

- Check for blocked heat exchanger.

FOR SPARK IGNITION

- Check SE wire & connections.
- Clean SE with sandpaper. Replace SE if necessary.
- If problem persists, check IFC*.
- Check SE gas and proper SE ground.
- Check SE wire for spark arcing to metal before electrode.

FOR HOT SURFACE IGNITION

- Check ignitor connected.
- Check ignitor wires.
- Check ignitor resistance. If open circuit, low or high resistance, replace.
- Check ignitor for fractures or cracking
- Check ignitor placement.
- If problem persists, check IFC*.

START

REPEAT THIS PROCEDURE UNTIL TROUBLE-FREE OPERATION IS OBTAINED.

NO

NO

NO

If “

I

” did not

resolve issue.

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

BLINKING

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

STEADY-ON

I

D

F

H

E

G

YES

NO

YES

PREPURGE

IGNITION TRIAL

IBM “ON” DELAY

STEADY HEAT

END HEAT CALL

POST-PURGE

IBM “OFF” DELAY

STEADY OFF

NO

OFF

**

92-101654-01-00

GO TO

F

GO TO

I

PREPURGE

38

Содержание GMDA

Страница 1: ...e with the manufacturer s recommendations and or local laws rules regulations or customs Upflow Horizontal Models Downflow Models Model Number Input Btu Tons Model Number Input Btu Tons GMUH50 E3A 50...

Страница 2: ...el DC microamp A flame signal hot surface ignition units Correct control voltage Measure and set heat anticipator amperage Air conditioning low voltage wires connected to terminals Y C not with wire n...

Страница 3: ...ause cancer or birth defects such as fiberglass insulation lead in brass and combustion products from natural gas All new equipment shipped for sale in California will have labels stating that the pro...

Страница 4: ...ALLATION ADJUSTMENT AND OPERATION OF THIS UNIT READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION A...

Страница 5: ...APPLIANCES SUCH AS WATER HEATERS OR BOILERS ALL JOINTS SEAMS AND OPENINGS IN THE EQUIPMENT AND DUCT MUST ALSO BE SEALED TO PREVENT DEPRESSURIZATION OF THE SPACE AND POSSIBLE MIGRATION OF COMBUSTION BY...

Страница 6: ...ATE COMBUSTION AND VENTILATION AIR FOR THE FURNACE FAILURE TO DO SO CAN CREATE HAZARDOUS CONDITIONS RESULTING IN PROPERTY DAMAGE BODILY INJURY OR DEATH FROM SMOKE FIRE OR CARBON MONOXIDE WARNING NEVER...

Страница 7: ...ICATION BY PROPERLY APPLYING THE APPROPRIATE INDUSTRY ACCEPTED STANDARD IF LESS THAN MINIMUM STANDARDS ARE APPLIED THE EQUIPMENT USER COULD EXPECT TO EXPERIENCE HIGHER UTILITY BILLS MAJOR COMPONENT FA...

Страница 8: ...lation Codes for Gas Burning Appliances Since furnace technology and venting requirements are changing awareness of local state and federal codes and industry changes is imperative GENERAL INFORMATION...

Страница 9: ...ONDI TIONS AND ARE NOT COVERED BY THE UNIT WARRANTY IN COMPLIANCE WITH RECOGNIZED CODES IT IS RECOMMENDED THAT AN AUXILIARY DRAIN PAN BE INSTALLED UNDER ALL EVAPORATOR COILS OR UNITS CONTAINING EVAPOR...

Страница 10: ...T SIDE FRONT RIGHT SIDE ALTERNATE GAS CONNECTION BOTTOM RETURN AIR AIRFLOW SUPPLY AIR 26 13 16 26 5 8 24 11 32 24 11 32 19 32 9 16 24 7 16 28 1 16 26 5 8 14 3 8 11 1 2 34 1 5 8 DIA 23 15 20 D 7 8 DIA...

Страница 11: ...1 32 15 5 8 23 5 8 0 0 0 1 3 6 150 lbs FIGURE 4 DOWNFLOW DIMENSIONS TOP BOTTOM 24 1 2 19 3 4 C A B D LOW VOLTAGE GAS CONNECTION ELECTRIC CONNECTION E S A R A 26 5 8 26 13 16 6 3 16 20 3 8 23 3 8 5 8 5...

Страница 12: ...O NOT take return air from bathrooms kitchens furnace rooms garages utility or laundry rooms or cold areas IMPORTANT When using outside air design and adjust the system to maintain a return air temper...

Страница 13: ...indoor coil on the supply air side of the furnace Insure that no air can bypass this coil 3 Connect the supply air plenum to the furnace plenum opening DOWNFLOW UNITS THE DOWNFLOW FURNACE DESIGN IS CE...

Страница 14: ...uded from warranty coverage The following types of installation may require OUTDOOR AIR for combustion due to chemical exposures Commercial buildings Buildings with indoor pools Furnaces installed in...

Страница 15: ...E A confined space any space smaller than shown above as unconfined must have openings into the space which are located in accordance with the requirements set forth in the following subsections A and...

Страница 16: ...all equipment in the enclosure Here are typical duct sizes B Method 2 One permanent opening located within 12 inches of the top of the enclosure shall be permitted where the equipment has clearances o...

Страница 17: ...the inlet air opening at the furnace must be protected from accidental blockage Install a 90 elbow pointing horizontally at the top of inlet air pipe See Figure 11 maximum of 2 45 or 90 elbows allowed...

Страница 18: ...al Fuel Gas Code ANSI Z223 1 and or the Natural Gas Installation Code CSA B149 1 2 for proper installation practices NOTE Follow combustion air instructions as outlined in this manual Single wall vent...

Страница 19: ...height above the highest connected equipment draft hood or flue collar 3 Must rise 1 4 per foot away from the furnace on horizontal runs and be supported with straps or hangers so it has no sags or d...

Страница 20: ...xhausts so they will operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers 3 Follow the lighting instructions Place the appliance being inspected into operation Adjust t...

Страница 21: ...n gas valve on the furnace Refer to Table 2 for the recommended pipe size for natural gas and Table 3 for LP gas pipe sizes IMPORTANT It is permissible to run flexible gas connector inside the unit to...

Страница 22: ...s pressure of 13 w c ELEVATIONS ABOVE 2000 FT REQUIRE THAT THE FURNACE INPUT RATING BE ADJUSTED AND THAT THE SIZE OF THE BURNER ORIFICES BE RE CALCULATED BASED ON ELEVATION AND GAS HEATING VALUE THE B...

Страница 23: ...re at the regulator See Table 3 NOTE Depending on the amount of LP vapor and the outdoor ambient temperature the LP storage tank may require supplemental heat to maintain proper pressure levels Ensure...

Страница 24: ...t ratings apply For high altitudes elevations 8 000 and over and for any necessary major changes in the gas flow rate the orifice spud must be changed TO CHANGE ORIFICE SPUDS 1 Shut off the manual mai...

Страница 25: ...1 CSA Standard C22 1 and local building codes This can be obtained from National Fire Protection Association Batterymarch Park Quincy MA 02269 WARNING WARNING ELECTRICAL WIRING thermostat lead wires...

Страница 26: ...NT ONLY BOTTOM RETURNS CAN BE USED NO MORE THAN TWO FURNACES CAN SHARE THE SAME SUPPLY AND RETURN FURNACES MUST HAVE SAME HEATING AND BLOWER CAPACITY TWINNING FURNACES MUST OPERATE OFF THE SAME PHASE...

Страница 27: ...per thousand ft 47 LP GAS TABLE 7 NOTE Keep any parts removed during LP conversion procedure stored with the product literature for future use LP Gas is a manufactured gas that has consistent heating...

Страница 28: ...must be measured onsite with manifold pressure adjustment to ensure that an actual 10 reduction in input rate is achieved Once this field adjustment has been made the label shown in Figure 19 must be...

Страница 29: ...8 48 25 000 24 000 23 000 22 000 21 000 20 000 19 000 18 000 17 000 16 000 All calculations are performed by using the first three columns of information only Before beginning any calculations determi...

Страница 30: ...h es close the spark igniter energizes The induced draft blower operates for the complete heating cycle 4 After the spark igniter energizes the gas valve opens for a 8 second trial for ignition 5 The...

Страница 31: ...CAL SHOCK RESULTING IN SEVERE PERSONAL INJURY OR DEATH The blower motor is wired for blower speeds required for normal operation as shown If additional blower speed taps are available speeds may be ch...

Страница 32: ...to the approved temperature rise range listed on the furnace name plate See Figure 22 If the measured temperature rise is above the approved range either the air flow is too low or the manifold press...

Страница 33: ...1 02 2 05 3 07 4 10 5 12 6 15 7 17 CFM L s AIR DELIVERY EXTERNAL STATIC PRESSURE INCHES kPa WATER COLUMN Note Recommended blower speeds are in bold BLOWER PERFORMANCE DATA DOWNFLOW MODELS 50K 11 x 6...

Страница 34: ...ch will shut the furnace down Switches for the upflow horizontal models furnaces are located on either side of the burner cover plate and just above the burners on the blower divider panel The downflo...

Страница 35: ...TE These models are not factory equipped with filters or filter rods Filters must be field installed IMPORTANT Do not operate the system for extended periods without filters A portion of the dust entr...

Страница 36: ...AE 60520 01 FILTER SUPPORT ANGLE SEE ANGLE DETAIL AE 61883 01 FILTER ROD SUPPORT ANGLE AE 60520 01 FILTER SUPPORT ANGLE AE 61883 01 CUT OUT AND DRILL DETAIL FILTER AND ROD ASSEMBLY ROD FILTER SUPPORT...

Страница 37: ...T EXCHANGER CAN CAUSE TOXIC FUMES TO ENTER THE HOME RESULTING IN CARBON MONOXIDE POISONING OR DEATH THE VENT PIPE OR HEAT EXCHANGER MUST BE REPLACED IF THEY LEAK IMPORTANT It is recommended that at th...

Страница 38: ...limit open during ignition trial If yes go to D Check line voltage between HEAT and NEUTRAL on IFC Check wires connections and continuity between IFC and IBM Check IBM capacitor Check IBM CHECK groun...

Страница 39: ...FIGURE 28 FOR MODELS WITH UT ELECTRONIC CONTROLS 1027 200 INTEGRATED FURNACE CONTROL AND DIRECT SPARK IGNITION 39...

Страница 40: ...40 CM 0810...

Отзывы: