Heat Controller GMDA Скачать руководство пользователя страница 27

27

80+ HIGH ALTITUDE
INSTRUCTIONS
(TABLES 6 & 9)

INSTALLATION OF THIS FURNACE

AT ALTITUDES ABOVE 2000 FT (610

m) SHALL BE IN ACCORDANCE WITH

LOCAL CODES, OR IN THE ABSENCE

OF LOCAL CODES, THE NATIONAL

FUEL GAS CODE, ANSI Z223.1/NFPA

54 OR NATIONAL STANDARD OF

CANADA, NATURAL GAS AND

PROPANE INSTALLATION CODE,

CAN B149.1.

34" 80 Plus furnaces installed above
2,000 ft. require the furnace to be de-
rated 4% per thousand feet.

IMPORTANT:

Factory installed orifices

are calculated and sized based on a sea
level Natural Gas heating value of 1075
BTU per cubic ft.

NOTE:

Orifices are available through

your local distributor.

Reference Tables 6 and 9 for
appropriate orifice sizing.

The following are examples of orifice
sizing using the National Fuel Gas Code
Appendix F:

For a simplified estimation of orifice size
based on gas heating value and
elevation, Tables 6 and 9 may be used.
However, calculations are the best
method.

Example: 900 BTU/ft

3

Regional Natural

Gas Heating Value

I/H = Q
25000 / 900 = 27.78 ft

3

I = Sea Level input (per burner): 25000
H = Sea Level Heating Value: 900
Q = 27.78 ft

3

Natural Gas per hour.

From Table F.1 of

National Fuel Gas

Code Handbook, 2002

(3.5

w.c.

column).

Orifice required at Sea Level: #40

From Table F.4 of

National Fuel Gas

Code Handbook, 2002

Orifice required at 5000 ft. elevation (4%
de-rate per thousand ft): #42

Orifice required at 8000 ft. elevation (4%
de-rate per thousand ft.): #44

Example: 1050 BTU/ft3 Regional

Natural Gas Heating Value

I / H = Q
25000 / 1050 = 23.81ft

3

I = Sea Level input (per burner): 25000
H = Sea Level Heating Value: 1050
Q = 23.81 ft

3

Natural Gas per hour.

From Table F.1 of

Natural Fuel Gas

Code Handbook, 2002

(3.5

w.c.

column).

Orifice required at Sea Level: #43

From Table F.4 of

National Fuel Gas

Code Handbook, 2002

Orifice required at 5000 ft. elevation
(4% de-rate per thousand ft.): #45

Orifice required at 8000 ft elevation (4%
de-rate per thousand ft): #47

LP GAS (TABLE 7)

NOTE:

Keep any parts removed during

LP conversion procedure stored with
the product literature for future use.

LP Gas is a manufactured gas that has
consistent heating value across most
regions.

The NFGC guidelines are used with the
following exception:

The recommended LP Gas high
altitude orifice selections differ slightly
in that the NFGC LP orifice chart, as
they are not accurate for Rheem
products. The National Fuel Gas Code
LP orifices are based on an 11" of
water column pressure at the orifice,
which differs from products that use 10"
of water column at the orifice. This
difference requires a deviation from the
NFGC orifice size recommendations.
The Sea Level input should still be
reduced by 4% per thousand ft. and the
orifice size must be selected based on
the reduced input in Table 7.

FIGURE 19

MANIFOLD PRESSURE-CHANGE LABEL

THE MANIFOLD PRESSURE OF THIS APPLIANCE HAS 

BEEN FIELD ADJUSTED TO OBTAIN THE CORRECT 

INPUT RATING FOR INSTALLATION AT ALTITUDES 

BETWEEN 2,000 FEET AND 4,500 FEET ELEVATION.

LA PRESSION DU DISTRIBUTEUR D'ALIMENTATION 

DE CET APPAREIL A ÉTÉ AJUSTÉ SUR LES LIEUX AFIN  

D'OBTENIR LA BONNE PUISSANCE D'ENTRÉE POUR 

UNE INSTALLATION ENTRE 2000 ET 4500 PIEDS 

D'ALTITUDE.

92-24399-01-01

!

CAUTION

Natural Gas Orifice Drill Size (4% per 1000 ft. De-Rate)

IMPORTANT:

80+ Models only. Do not use this chart for any 90+ Models.

Burner Input (per burner) 25,000 BTU @ Sea Level

Sea level

2000 to

3000 to

4000 to

5000 to

6000 to

7000 to

8000 to

to 1999 ft

2999 ft

3999 ft

4999 ft

5999 ft

5999 ft

7999 ft

8999 ft

38

39

40

41

41

42

42

43

40

41

42

42

42

43

43

44

41

42

42

42

43

43

44

44

42

42

43

43

43

44

44

45

43

44

44

44

45

45

46

47

Annual Avg. Heat

Value (btu per ft

3

)

850

900

975

1075

1170

TABLE 6

TABLE 7

LP GAS

IMPORTANT: 80+ MODELS ONLY! DO NOT

USE THIS CHART WITH ANY 90+ MODELS.

Input (per

Orifice

Altitude

burner) 25000

Size

0 to 2000 ft.

25000

#54

2000

-3000

24000

#54

3000

-4000

23000

#54

4000

-5000

22000

#54

5000

-6000

21000

#54

6000

-7000

20000

#54

7000

-8000

19000

#55

8000

-9000

18000

#55

9000

-10000

17000

#55

Содержание GMDA

Страница 1: ...e with the manufacturer s recommendations and or local laws rules regulations or customs Upflow Horizontal Models Downflow Models Model Number Input Btu Tons Model Number Input Btu Tons GMUH50 E3A 50...

Страница 2: ...el DC microamp A flame signal hot surface ignition units Correct control voltage Measure and set heat anticipator amperage Air conditioning low voltage wires connected to terminals Y C not with wire n...

Страница 3: ...ause cancer or birth defects such as fiberglass insulation lead in brass and combustion products from natural gas All new equipment shipped for sale in California will have labels stating that the pro...

Страница 4: ...ALLATION ADJUSTMENT AND OPERATION OF THIS UNIT READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION A...

Страница 5: ...APPLIANCES SUCH AS WATER HEATERS OR BOILERS ALL JOINTS SEAMS AND OPENINGS IN THE EQUIPMENT AND DUCT MUST ALSO BE SEALED TO PREVENT DEPRESSURIZATION OF THE SPACE AND POSSIBLE MIGRATION OF COMBUSTION BY...

Страница 6: ...ATE COMBUSTION AND VENTILATION AIR FOR THE FURNACE FAILURE TO DO SO CAN CREATE HAZARDOUS CONDITIONS RESULTING IN PROPERTY DAMAGE BODILY INJURY OR DEATH FROM SMOKE FIRE OR CARBON MONOXIDE WARNING NEVER...

Страница 7: ...ICATION BY PROPERLY APPLYING THE APPROPRIATE INDUSTRY ACCEPTED STANDARD IF LESS THAN MINIMUM STANDARDS ARE APPLIED THE EQUIPMENT USER COULD EXPECT TO EXPERIENCE HIGHER UTILITY BILLS MAJOR COMPONENT FA...

Страница 8: ...lation Codes for Gas Burning Appliances Since furnace technology and venting requirements are changing awareness of local state and federal codes and industry changes is imperative GENERAL INFORMATION...

Страница 9: ...ONDI TIONS AND ARE NOT COVERED BY THE UNIT WARRANTY IN COMPLIANCE WITH RECOGNIZED CODES IT IS RECOMMENDED THAT AN AUXILIARY DRAIN PAN BE INSTALLED UNDER ALL EVAPORATOR COILS OR UNITS CONTAINING EVAPOR...

Страница 10: ...T SIDE FRONT RIGHT SIDE ALTERNATE GAS CONNECTION BOTTOM RETURN AIR AIRFLOW SUPPLY AIR 26 13 16 26 5 8 24 11 32 24 11 32 19 32 9 16 24 7 16 28 1 16 26 5 8 14 3 8 11 1 2 34 1 5 8 DIA 23 15 20 D 7 8 DIA...

Страница 11: ...1 32 15 5 8 23 5 8 0 0 0 1 3 6 150 lbs FIGURE 4 DOWNFLOW DIMENSIONS TOP BOTTOM 24 1 2 19 3 4 C A B D LOW VOLTAGE GAS CONNECTION ELECTRIC CONNECTION E S A R A 26 5 8 26 13 16 6 3 16 20 3 8 23 3 8 5 8 5...

Страница 12: ...O NOT take return air from bathrooms kitchens furnace rooms garages utility or laundry rooms or cold areas IMPORTANT When using outside air design and adjust the system to maintain a return air temper...

Страница 13: ...indoor coil on the supply air side of the furnace Insure that no air can bypass this coil 3 Connect the supply air plenum to the furnace plenum opening DOWNFLOW UNITS THE DOWNFLOW FURNACE DESIGN IS CE...

Страница 14: ...uded from warranty coverage The following types of installation may require OUTDOOR AIR for combustion due to chemical exposures Commercial buildings Buildings with indoor pools Furnaces installed in...

Страница 15: ...E A confined space any space smaller than shown above as unconfined must have openings into the space which are located in accordance with the requirements set forth in the following subsections A and...

Страница 16: ...all equipment in the enclosure Here are typical duct sizes B Method 2 One permanent opening located within 12 inches of the top of the enclosure shall be permitted where the equipment has clearances o...

Страница 17: ...the inlet air opening at the furnace must be protected from accidental blockage Install a 90 elbow pointing horizontally at the top of inlet air pipe See Figure 11 maximum of 2 45 or 90 elbows allowed...

Страница 18: ...al Fuel Gas Code ANSI Z223 1 and or the Natural Gas Installation Code CSA B149 1 2 for proper installation practices NOTE Follow combustion air instructions as outlined in this manual Single wall vent...

Страница 19: ...height above the highest connected equipment draft hood or flue collar 3 Must rise 1 4 per foot away from the furnace on horizontal runs and be supported with straps or hangers so it has no sags or d...

Страница 20: ...xhausts so they will operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers 3 Follow the lighting instructions Place the appliance being inspected into operation Adjust t...

Страница 21: ...n gas valve on the furnace Refer to Table 2 for the recommended pipe size for natural gas and Table 3 for LP gas pipe sizes IMPORTANT It is permissible to run flexible gas connector inside the unit to...

Страница 22: ...s pressure of 13 w c ELEVATIONS ABOVE 2000 FT REQUIRE THAT THE FURNACE INPUT RATING BE ADJUSTED AND THAT THE SIZE OF THE BURNER ORIFICES BE RE CALCULATED BASED ON ELEVATION AND GAS HEATING VALUE THE B...

Страница 23: ...re at the regulator See Table 3 NOTE Depending on the amount of LP vapor and the outdoor ambient temperature the LP storage tank may require supplemental heat to maintain proper pressure levels Ensure...

Страница 24: ...t ratings apply For high altitudes elevations 8 000 and over and for any necessary major changes in the gas flow rate the orifice spud must be changed TO CHANGE ORIFICE SPUDS 1 Shut off the manual mai...

Страница 25: ...1 CSA Standard C22 1 and local building codes This can be obtained from National Fire Protection Association Batterymarch Park Quincy MA 02269 WARNING WARNING ELECTRICAL WIRING thermostat lead wires...

Страница 26: ...NT ONLY BOTTOM RETURNS CAN BE USED NO MORE THAN TWO FURNACES CAN SHARE THE SAME SUPPLY AND RETURN FURNACES MUST HAVE SAME HEATING AND BLOWER CAPACITY TWINNING FURNACES MUST OPERATE OFF THE SAME PHASE...

Страница 27: ...per thousand ft 47 LP GAS TABLE 7 NOTE Keep any parts removed during LP conversion procedure stored with the product literature for future use LP Gas is a manufactured gas that has consistent heating...

Страница 28: ...must be measured onsite with manifold pressure adjustment to ensure that an actual 10 reduction in input rate is achieved Once this field adjustment has been made the label shown in Figure 19 must be...

Страница 29: ...8 48 25 000 24 000 23 000 22 000 21 000 20 000 19 000 18 000 17 000 16 000 All calculations are performed by using the first three columns of information only Before beginning any calculations determi...

Страница 30: ...h es close the spark igniter energizes The induced draft blower operates for the complete heating cycle 4 After the spark igniter energizes the gas valve opens for a 8 second trial for ignition 5 The...

Страница 31: ...CAL SHOCK RESULTING IN SEVERE PERSONAL INJURY OR DEATH The blower motor is wired for blower speeds required for normal operation as shown If additional blower speed taps are available speeds may be ch...

Страница 32: ...to the approved temperature rise range listed on the furnace name plate See Figure 22 If the measured temperature rise is above the approved range either the air flow is too low or the manifold press...

Страница 33: ...1 02 2 05 3 07 4 10 5 12 6 15 7 17 CFM L s AIR DELIVERY EXTERNAL STATIC PRESSURE INCHES kPa WATER COLUMN Note Recommended blower speeds are in bold BLOWER PERFORMANCE DATA DOWNFLOW MODELS 50K 11 x 6...

Страница 34: ...ch will shut the furnace down Switches for the upflow horizontal models furnaces are located on either side of the burner cover plate and just above the burners on the blower divider panel The downflo...

Страница 35: ...TE These models are not factory equipped with filters or filter rods Filters must be field installed IMPORTANT Do not operate the system for extended periods without filters A portion of the dust entr...

Страница 36: ...AE 60520 01 FILTER SUPPORT ANGLE SEE ANGLE DETAIL AE 61883 01 FILTER ROD SUPPORT ANGLE AE 60520 01 FILTER SUPPORT ANGLE AE 61883 01 CUT OUT AND DRILL DETAIL FILTER AND ROD ASSEMBLY ROD FILTER SUPPORT...

Страница 37: ...T EXCHANGER CAN CAUSE TOXIC FUMES TO ENTER THE HOME RESULTING IN CARBON MONOXIDE POISONING OR DEATH THE VENT PIPE OR HEAT EXCHANGER MUST BE REPLACED IF THEY LEAK IMPORTANT It is recommended that at th...

Страница 38: ...limit open during ignition trial If yes go to D Check line voltage between HEAT and NEUTRAL on IFC Check wires connections and continuity between IFC and IBM Check IBM capacitor Check IBM CHECK groun...

Страница 39: ...FIGURE 28 FOR MODELS WITH UT ELECTRONIC CONTROLS 1027 200 INTEGRATED FURNACE CONTROL AND DIRECT SPARK IGNITION 39...

Страница 40: ...40 CM 0810...

Отзывы: