BHD-G Service Manual 

Portable Dehumidifier with R-410A

 

Heat Controller, Inc.

7

5.Basic Test Procedures

5.1 DEFECTIVE COMPRESSOR 

Compressors are single phase, 115 volt. All compressor motors are permanent split capacitor type using only a 

running capacitor across the start and run terminal.

All compressors are internally spring mounted and externally mounted on rubber isolators.

COMPRESSOR WINDING TEST

Remove compressor terminal box cover and disconnect wires from terminals. 

Using an ohmmeter, check continuity across the following:

1. Terminal “C” and “S” - no continuity 

  - open winding - replace compressor.

2. Terminal “C” and “R” - no continuity 

  - open winding - replace compressor.

3. Terminal “R” and “S” - no continuity 

  - open winding - replace compressor.                 

GROUND TEST

Use an ohmmeter set on its highest scale. Touch one lead to the compressor body (clean point of contact as a 

good connection is a must) and the other probe in turn to each compressor terminal (see Figure 2.) If a reading is 

obtained, the compressor is grounded and must be replaced.               

CHECKING COMPRESSOR EFFICIENCY

The reason for compressor inefficiency is normally due to broken or 

damaged suction and/or discharge valves, reducing the ability of the 

compressor to pump refrigerant gas.

This condition can be checked as follows: 

1. Install a piercing valve on the suction and discharge or liquid line.

2. Attach gauges to the high and low sides of the system.

3. Start the system and run a “cooling or heating performance test.”

If test shows:

A. 

Below

 normal high side pressure.

B. 

Above

 normal low side pressure.

C. 

Low

 temperature difference across coil.

The compressor valves are faulty - replace the compressor.

THERMAL OVERLOAD (External)

Some compressors are equipped with an external overload which is located in the compressor terminal box 

adjacent to the compressor body. The overload is wired in series with the common motor terminal. The overload 

senses both amperage and compressor temperature. High motor temperature or amperage heats the disc causing it 

to open and break the circuit to the common motor terminal. 

Heat generated within the compressor shell is usually due to:

1. High amperage.

2. Low refrigerant charge.

3. Frequent cycling.

4. Dirty condenser.

TERMINAL OVERLOAD – TEST (Compressor - External Type)

1. Remove overload.

2. Allow time for overload to reset before attempting to test.

3. Apply ohmmeter probes to terminals on overload wires. There 

should be continuity through the overload.

Figure 1: Compressor winding test

Figure 2: Typical ground test

Содержание BHD-301-G

Страница 1: ...Heat Controller Inc 1900 Wellworth Ave Jackson MI 49203 517 787 2100 www heatcontroller com SERVICE MANUAL Portable Dehumidifer Series with R 410A BHD 301 G BHD 501 G BHD 651 G...

Страница 2: ...3 3 Operation with Water Tank 4 3 4 Operation with Continuous drainage 5 3 5 MAINTENANCE 5 4 Electronic function 6 4 1 Powering on the unit 6 4 2 Setting the relative humidity 6 4 3 Continuous Dehumi...

Страница 3: ...a jumper lead between the two 2 live test pins 2 The grounding conductor yellow green should be open 3 Measure the resistance value with an ohm meter between the jumped lead and each exposed metallic...

Страница 4: ...ferred set the fan control to Normal 5 TIMER Press to initiate the Auto start and Auto stop feature in conjuction with the and keys 6 Display Shows the set humidity level from 35 to 85 or auto start s...

Страница 5: ...rd to the proper power recepticable The unit s program will run a self check if it is normal the power indicator flashes at 0 5Hz Press Power button now the unit will start operating under DEHUMIDIFYI...

Страница 6: ...s thinners or other chemical agents to clean the unit as this may damage the unit Do not wash the unit directly under a tap or hose The electrical components inside may be damaged and the unit become...

Страница 7: ...ovide better air circulation When the humidistat senses that the room s actual humidity is 5 higher than the set humidity of 35 in continuous mode the compressor will restart and begin to dehumidify t...

Страница 8: ...r discharge valves reducing the ability of the compressor to pump refrigerant gas This condition can be checked as follows 1 Install a piercing valve on the suction and discharge or liquid line 2 Atta...

Страница 9: ...ogen through the system and unsolder the more distant connection first Filter drier high side process tube etc 5 Replace inoperative component and always install a new filter drier Add dry nitrogen th...

Страница 10: ...gerant charge is extremely critical Measure charge carefully as exact as possible to the nameplate charge 2 The correct method for charging the rotary compressor is to introduce liquid refrigerant int...

Страница 11: ...the pointer then gradually move back to infinity 4 Reverse the leads of the probe and momentarily touch the capacitor terminals The deflection of the pointer should be two times that of the first chec...

Страница 12: ...nd fan motor will shut down and the water full indicator will flash with LED displaying P2 Under this situation all buttons are deactivated After the water is removed the unit will restore operating a...

Страница 13: ...Heat Controller Inc Portable Dehumidifier with R 410A BHD G Service Manual 12 6 3 3 Humidity sensor check 6 3 4 Fail to start or fail to start motor...

Страница 14: ...heck the voltage of P1 P2 on main PCB Replace the main PCB if no voltage Capacitor Discharge capacitor before testing Test capacitor Replace if not within 10 of manufacturer s rating Replace if shorte...

Страница 15: ...er Clean if restricted Condenser and Evaporator Clean if restricted Fan motor Check the fan capacitor and replace if not within 10 of manufacturer s rating Room structure Ensure that the room the unit...

Страница 16: ...BHD G Service Manual Portable Dehumidifier with R 410A Heat Controller Inc 15 7 Wiring Diagram...

Страница 17: ...04 2009 05 2010...

Отзывы: