7602-443 COMMUNICATING, PROGRAMMABLE THERMOSTAT

 

Heat Controller, Inc.

Adjust the Demand Reduction Whole House 
Dehumidifi cation settings using the up/down arrow 
buttons.  Press the center button to save changes.

• 

Suspend Whole House Dehumidifi cation 
(ClimaDry) (default):

  While the assigned 

Demand Reduction input is active, Whole 
House Dehumidifi cation is turned off, 
regardless of the dehumidifi caiton demand.

• 

Allow Whole House Dehumidifi cation 
(ClimaDry): 

 While the assigned Demand 

Reduction input is active, Whole House 
Dehumidifi cation will operate normally.

NOTE

:  The thermostat must be confi gured for 

humidity control by installer and the DXM2 must 
be confi gured for Whole House Dehumidifi cation 
operation to access Demand Reduction Whole 
House Dehumidifi cation settings.

5.6.9.3  FAN - DEMAND REDUCTION

This option allows for the customization of fan 
settings while Demand Reduction is active.
Adjust the Demand Reduction Fan settings using 
the up/down arrow buttons.  Press the center 
button to save changes.

• 

Auto Fan Only (default):

  While the assigned 

Demand Reduction input is active, the fan 
output will not be activated unless the heat 
pump is in 1st or 2nd stage operation or 
auxiliary heat mode is active.

• 

Allow Continuous Fan: 

 While the assigned 

Demand Reduction input is active, the fan 
output will operate normally.

5.7  SECURITY LOCKOUT

The Security Lockout function allows you to lockout 
thermostat display, requiring a password to make changes.
Adjust the four-digit Security Pin using the up/down arrow 
buttons.  Navigate between digits using the left/right arrow 
buttons.  Press the center button to save changes.

• Temp 

Adjust 

Only:

  while locked, thermostat will still 

allow temperature adjustment

•  Total Keypad Lockout: 

 while locked, thermostat will not 

allow any changes

5.8 NIGHT 

SETBACK

Under Night Setback mode, the thermostat will operate using 
alternate Night Setback heating and cooling setpoints, fan 
mode, and humidifi cation and dehumidifi cation setpoints. 
Night Setback is activated by an input signal at the unit 
control board to reduce the electric load while the building is 
unoccupied.    

NOTE

:  While the Night Setback mode is active, the screen 

backlight will be red when ON.

 

5.8.1  NIGHT SETBACK SETPOINTS

 

Adjust the Night Setback setpoints using the up/down 

arrow buttons.  Navigate between Night Setback 
setpoints using the left/right arrow buttons.  Press the 
center button to save changes.

•  Heat Setpoint (default 60

°

F):

  options:  55°F to 

Maximum Heating Setpoint Limit (section 5.6.8)

•  Cool Setpoint (default 80

°

F): 

 options:  Minimum 

Cooling Setpoint Limit (section 5.6.8) to 95°F

 

NOTE

: The thermostat forces a 2°F “dead-band” 

between the Night Setback Heating and Cooling 
setpoints.  While adjusting the Night Setback Heating 
setpoint, the Night Setback Cooling setpoint may be 
automatically increased to enforce a 2°F “dead-band”.  
Likewise, while adjusting the Night Setback Cooling 
setpoint, the Night Setback Heating setpoint may be 
automatically reduced to enforce a 2°F “dead-band”.

 

5.8.2  NIGHT SETBACK OVERRIDE

 

While the Night Setback mode is active, the 

alternate Night Setback setpoints can be temporarily 
overridden, by using the normal temperature 
adjustment screen.  If the heating and cooling 
setpoints are adjusted while Night Setback is active, 
these temporary setpoints will remain active for the 
current Night Setback Override time, unless they are 
adjusted again, or the Night Setback mode is de-
activated.

 

Adjust the Night Setback Override setting using the 

up/down arrow buttons.  Press the center button to 
save changes.

•  Night Setback Override (default 2 hours): 

options:  1 to 8 hours (in 15 minute increments)

SECURITY LOCKOUT

SAVE

TOTAL   KEYPAD  LOCKOUT

PREVIOUS

SELECT OPTION

TEMP  ADJUST   ONLY

MAIN  MENU

SET   DATE  AND  TIME

HOLD

SECURITY   LOCKOUT

PROGRAM

FAN

MODE

SETTINGS

Содержание 7602-443

Страница 1: ...Heat Controller Inc 1900 Wellworth Ave Jackson MI 49203 517 787 2100 www heatcontroller com USER MANUAL 7602 443 Communicating Programmable Thermostat...

Страница 2: ...ustment 4 3 0 Fan Mode Selection 4 4 0 Humidity Level Adjustment 5 5 0 Main Menu Options Overview 6 5 1 Date and Time 7 5 2 Hold 7 5 3 Program 9 5 4 Fan 9 5 5 Mode 9 5 6 Other Settings 10 5 7 Security...

Страница 3: ...AUTO HUMID ON AUTO SETPOINT HEAT 62 COOL 82 RH TEMP FAN MENU MODE AUTO OPERATING MODE MENU SAVE OFF COOL HEAT EMERGENCY PREVIOUS CHANGE MODE HEAT The 7602 443 Communicating Programmable Thermostat is...

Страница 4: ...the Heating setpoint may be automatically reduced to enforce a 2 F dead band NOTE 3 In programmable mode the TEMP option provides the ability to temporarily modify setpoint s until the start time of...

Страница 5: ...ints Adjust the setpoints using the up down arrow buttons Press the center button to save changes Humidification Setpoint default 40 options 10 to 45 in 5 increments NOTE Humidifier must be installed...

Страница 6: ...ER HOUR 5 6 4 AUTO CHANGEOVER TIME 5 6 5 PROGRAM SETTINGS 5 6 5 1 Smart Recovery 5 6 5 2 Events Per Day 5 6 5 3 Smart Heat Staging 5 6 5 4 Electric Heat Lockout 5 6 5 5 Demand Reduction 5 6 6 INTERMIT...

Страница 7: ...y adjusts the time for daylight savings time 5 1 2 SET DATE AND TIME To set the current date and time use the up down arrow buttons Press the center button to save changes 5 1 3 DISPLAY DATE AND TIME...

Страница 8: ...Minimum Cooling Setpoint Limit section 5 6 8 95 F NOTE The thermostat forces a 2 F dead band between the Heating and Cooling setpoints While adjusting the Heating setpoint the Cooling setpoint may be...

Страница 9: ...ividual days or schedules for groups of days Event Heat Cool Fan see NOTE 2 Day 6 00A 70 F 78 F Auto Night 10 00P 62 F 82 F Auto SELECT OPTION MONDAY PREVIOUS TUESDAY WEDNESDAY COPY THURSDAY SATURDAY...

Страница 10: ...art Recovery 5 6 5 2 EVENTS PER DAY NOTE The thermostat must be configured for programmable mode by installer to access the Events per Day setting Events Per Day sets the number of program schedule ev...

Страница 11: ...uction schedule DEMAND REDUCTION OPTION FOR PROGRAM OPERATION SAVE NO AUXILIARY HEAT NO 2ND STAGE COMP PREVIOUS SELECT OPTION NO DEMAND REDUCTION No Demand Reduction default During the scheduled Progr...

Страница 12: ...d time settings using the up down arrow buttons in increments of 10 minutes Press the center button to save changes NOTE To disable Programmed Demand Reduction set the Start time equal to the End time...

Страница 13: ...igned Demand Reduction input is active the compressor is limited to only part load 1st stage operation and auxiliary heat is turned off regardless of system demand No Operation default if either setti...

Страница 14: ...T SETBACK Under Night Setback mode the thermostat will operate using alternate Night Setback heating and cooling setpoints fan mode and humidification and dehumidification setpoints Night Setback is a...

Страница 15: ...ttons Press the center button to save changes Auto Operation Only default While the Night Setback input is active the fan output will not be activated unless Y1 or W is active Fan Same As Occupied Whi...

Страница 16: ...Date Page Description 17 Sept 12 All First Published Revision History 9 17 12 97B0055N08 97B0055N08...

Отзывы: