User Manual 

7602-443 COMMUNICATING, PROGRAMMABLE THERMOSTAT

 

Heat Controller, Inc.

5.6  OTHER SETTINGS
 

5.6.1  SCREEN SETTINGS

 

Adjust the Screen settings using the up/down arrow 

buttons.  Press the center button to save changes.

 

•  Fahrenheit or Celsius (default Fahrenheit):

 

 

adjusts the temperature scale

 

•  12 or 24 Hour Clock (default 12 Hour Clock):

 

 

adjusts the clock format

 

•  Language (default English)

 

•  Contrast (default 4):

  adjusts the screen contrast 

 

 

-  options:  1 to 15

 

•  Backlight On Time (default 30 seconds):

  After

 

 

a button press, the backlight stays on for the 

 

 

selected amount of time  -  options:  30 to 120 

 

 

seconds, ON (in 30 second increments)

 

•  Date Display (default MM/DD/YY):

  adjusts the 

  

date 

format

 

5.6.2  OFFSETS

 

Not recommended for user access. Contact your 

dealer for changes.

 

5.6.3  CYCLES PER HOUR

 

Not recommended for user access. Contact your 

dealer for changes.

 

5.6.4  AUTO CHANGEOVER TIME

 

Not recommended for user access. Contact your 

dealer for changes.

 

5.6.5  PROGRAM SETTINGS

 

Set additional system parameters related to program 

scheduling and system operation.

 5.6.5.1 

SMART 

RECOVERY

 

Smart recovery is a feature designed to save 
energy by gradually adjusting temperatures.  When 
it is time for a program schedule temperature 
change, smart recovery begins working in 
advance, turning the system on and off as needed 
to slowly adjust the indoor temperature so that 
it reaches the program temperature setpoints at 
the time you set.  Rather than waiting to start the 
equipment until the program time has occurred.

 

Adjust the Smart Recovery setting using the up/
down arrow buttons.  Press the center button to 
save changes.

• 

Events Per Day (default On):

  options:  ON, 

OFF

 

NOTE 1

:  The thermostat must be confi gured for 

programmable mode by installer to access the 
Smart Recovery setting.

 

NOTE 2

:  Auxiliary heat will not be used during 

Smart Recovery.

 

5.6.5.2  EVENTS PER DAY

 

NOTE:  The thermostat must be confi gured for 
programmable mode by installer to access the 
Events per Day setting.

 

Events Per Day sets the number of program 
schedule events for each day.  An event is a period 
of time scheduled with a certain heat setpoint, cool 
setpoint, and fan mode.

 

Adjust the Events Per Day setting using the up/
down arrow buttons.  Press the center button to 
save changes.

• 

Events Per Day (default 4 events):  

options:  

4-Residential, 2-Residential, 2-Business

 

5.6.5.3  SMART HEAT STAGING

 

When there is auxiliary heating demand, Smart 
Heat Staging defi nes the minimum amount of 
time to wait before activating auxiliary heating.  If 
you fi nd that the thermostat is operating auxiliary 
heating equipment too quickly/slowly, this setting 
allows for adjustment to correct the temperature 
algorithm.

 
 

Adjust the Smart Heat Staging setting using the up/
down arrow buttons.  Press the center button to 
save changes.

• 

Smart Heat Staging (default Off):

  options:  

OFF, 5 – 120 minutes (in 5 minute increments)

 

5.6.5.4  ELECTRIC HEAT LOCKOUT

 

Electric heat lockout keeps electric heat turned off 
if the outdoor temperature is above the specifi ed 
temperature so as only to use electric heat when 
necessary.

 
 

Adjust the Electric Heat Lockout setting using the 
up/down arrow buttons.  Press the center button to 
save changes.

• 

Electric Heat Lockout (default Off):

  options:  

OFF, 5 – 60°F (in 5°F increments)

 

NOTE

:  An outdoor temperature sensor must be 

installed for this feature to work.

 

5.6.5.5  PROGRAMMED DEMAND REDUCTION

 

Programmed Demand Reduction is a feature 
designed to reduce your electric load during 
preselected time periods in which peak utility rates 
are high.  You can program your thermostat to 
reduce the electric load by limiting operation or 
capacity during the high utility rate time period that 
you specify for each day of the week.

 

While the Programmed Demand Reduction mode 
is active, the thermostat outputs will be limited 
by the Programmed Demand Reduction option 
selected below.

Содержание 7602-443

Страница 1: ...Heat Controller Inc 1900 Wellworth Ave Jackson MI 49203 517 787 2100 www heatcontroller com USER MANUAL 7602 443 Communicating Programmable Thermostat...

Страница 2: ...ustment 4 3 0 Fan Mode Selection 4 4 0 Humidity Level Adjustment 5 5 0 Main Menu Options Overview 6 5 1 Date and Time 7 5 2 Hold 7 5 3 Program 9 5 4 Fan 9 5 5 Mode 9 5 6 Other Settings 10 5 7 Security...

Страница 3: ...AUTO HUMID ON AUTO SETPOINT HEAT 62 COOL 82 RH TEMP FAN MENU MODE AUTO OPERATING MODE MENU SAVE OFF COOL HEAT EMERGENCY PREVIOUS CHANGE MODE HEAT The 7602 443 Communicating Programmable Thermostat is...

Страница 4: ...the Heating setpoint may be automatically reduced to enforce a 2 F dead band NOTE 3 In programmable mode the TEMP option provides the ability to temporarily modify setpoint s until the start time of...

Страница 5: ...ints Adjust the setpoints using the up down arrow buttons Press the center button to save changes Humidification Setpoint default 40 options 10 to 45 in 5 increments NOTE Humidifier must be installed...

Страница 6: ...ER HOUR 5 6 4 AUTO CHANGEOVER TIME 5 6 5 PROGRAM SETTINGS 5 6 5 1 Smart Recovery 5 6 5 2 Events Per Day 5 6 5 3 Smart Heat Staging 5 6 5 4 Electric Heat Lockout 5 6 5 5 Demand Reduction 5 6 6 INTERMIT...

Страница 7: ...y adjusts the time for daylight savings time 5 1 2 SET DATE AND TIME To set the current date and time use the up down arrow buttons Press the center button to save changes 5 1 3 DISPLAY DATE AND TIME...

Страница 8: ...Minimum Cooling Setpoint Limit section 5 6 8 95 F NOTE The thermostat forces a 2 F dead band between the Heating and Cooling setpoints While adjusting the Heating setpoint the Cooling setpoint may be...

Страница 9: ...ividual days or schedules for groups of days Event Heat Cool Fan see NOTE 2 Day 6 00A 70 F 78 F Auto Night 10 00P 62 F 82 F Auto SELECT OPTION MONDAY PREVIOUS TUESDAY WEDNESDAY COPY THURSDAY SATURDAY...

Страница 10: ...art Recovery 5 6 5 2 EVENTS PER DAY NOTE The thermostat must be configured for programmable mode by installer to access the Events per Day setting Events Per Day sets the number of program schedule ev...

Страница 11: ...uction schedule DEMAND REDUCTION OPTION FOR PROGRAM OPERATION SAVE NO AUXILIARY HEAT NO 2ND STAGE COMP PREVIOUS SELECT OPTION NO DEMAND REDUCTION No Demand Reduction default During the scheduled Progr...

Страница 12: ...d time settings using the up down arrow buttons in increments of 10 minutes Press the center button to save changes NOTE To disable Programmed Demand Reduction set the Start time equal to the End time...

Страница 13: ...igned Demand Reduction input is active the compressor is limited to only part load 1st stage operation and auxiliary heat is turned off regardless of system demand No Operation default if either setti...

Страница 14: ...T SETBACK Under Night Setback mode the thermostat will operate using alternate Night Setback heating and cooling setpoints fan mode and humidification and dehumidification setpoints Night Setback is a...

Страница 15: ...ttons Press the center button to save changes Auto Operation Only default While the Night Setback input is active the fan output will not be activated unless Y1 or W is active Fan Same As Occupied Whi...

Страница 16: ...Date Page Description 17 Sept 12 All First Published Revision History 9 17 12 97B0055N08 97B0055N08...

Отзывы: