A.  Gas Pressure Requirements

Pressure requirements for SOHO-CE fi replaces  are 
shown in Table 1 below.

Two taps are provided on the right hand side of the gas 
control for a test gauge connection to measure the inlet 
and outlet pressures. See 

Section 10

: Maintaining and 

Servicing the Appliance. 

The fi replace and its individual shut-off valve must be dis-
connected from the gas supply piping system during any 
pressure testing of the system at test pressures in excess 
of 60 mbar.

If the fi replace must be isolated from the gas supply pip-
ing system by closing an individual shut-off valve, it must 
be of the handle-less type.

Incoming gas line should be piped into the valve compart-
ment and connected to the ISO 7-Rp 1/2 (BSP Rp 1/2) 
threaded gas inlet connection on the manual shutoff valve.

Leak test all gas line points and the gas control valve prior 
to and after starting the gas appliance.

Table 1

Gas Information 

 

Natural Gas

(G20)

Propane

(G31)

Butane

(G30)

Natural Gas

(G25)

Inlet Pressure

20mbar

37 or 50mbar

30 or 50mbar

25mbar

Manifold Pressure

4.6-9.5mbar

15.8-25mbar

15.5-25mbar

5.4-11mbar

Gas Rate

.405 

m3

/

h

.134 

m3

/

h

.111 

m3

/

h

.40 

m3

/

h

Max. Input (NETCV)

4.0 kW

3.5 kW

3.6 kW

3.5 kW

Burner Injector

DMS 50

DMS 58

DMS 61

DMS 50

Pilot Injector

51

30

30

51

B. Gas Connection

Note: 

Have the gas supply line installed in accordance with 

local building codes by a qualifi ed installer approved and/or 
licensed as required by the locality. 

Note: 

Before the fi rst fi ring of the appliance, the gas supply 

line should be purged of any trapped air.

Note: 

Consult local building regulations to properly size the 

gas supply line leading to the (Rp 1/2 in.) hook-up at the 
unit.

WARNING

CHECK FOR GAS LEAKS

Explosion Risk

Fire Risk

Asphyxiation Risk

• Check all fi ttings and connections.

•  Do not use open fl ame.

•  After the gas line installation is complete, all 

connections must be tightened and checked 
for leaks with a commercially-available, non-
corrosive leak check solution. Be sure to rinse 
off all leak check solution following testing.

Fittings and connections may have loosened 
during shipping and handling.

WARNING

Fire Risk

Explosion Risk

High pressure will damage valve.

•  Disconnect gas supply piping BEFORE 

pressure testing gas line at test pressures 
above 60 mbar.

•  Close the manual shutoff valve BEFORE 

pressure testing gas line at test pressures 
equal to or less than 60 mbar.

Содержание Soho-CE

Страница 1: ...t glass will cause burns DO NOT touch glass until it is cooled NEVER allow children to touch glass Keep children away CAREFULLY SUPERVISE children in same room as fireplace Alert children and adults to hazards of high temperatures High temperatures may ignite clothing or other flammable materials Keep clothing furniture draperies and other flammable materials away Do not store or use gasoline or o...

Страница 2: ...t in safety reliability and efficiency As the owner of a new appliance you ll want to read and carefully follow all of the instructions contained in this Installer s Guide Pay special attention to all Cautions and Warnings This Installer s Guide should be retained for future reference We suggest that you keep it with your other important documents and product manuals The information contained in t...

Страница 3: ...ng the Appliance 17 8 Installing Flue Pipe A Assembly of Flue Sections 18 B Heat Shield Requirements for Horizontal Termination 19 C Install Horizontal Termination Cap 19 D Installing Vertical Termination Cap 20 E Assemble and Install Storm Collar 20 9 Gas Information A Gas Pressure Requirements 21 B Gas Connection 21 10 Electrical Information A Electronic Ignition System Wiring 22 11 Finishing A ...

Страница 4: ...ethod for Behavior of Materials in a Vertical Tube Furnace at 750º C shall be considered non com bustible materials C Combustible Materials Specification Materials made of or surfaced with wood compressed paper plant fibers plastics or other material that can ig nite and burn whether flame proofed or not or whether plastered or unplastered shall be considered combustible materials A Appliance Cert...

Страница 5: ... shipped in separate packages The logs are packaged separately inside the fireplace and must be field installed Report to your dealer any parts damaged in shipment particularly the condition of the glass Read all of the instructions before starting the insta llation Follow these instructions carefully during the installation to ensure maximum safety and benefit Check building codes prior to instal...

Страница 6: ...ming and Clearances Note Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY Illustrations diagrams are not drawn to scale Actual installation may vary due to individual design preference Fire Risk Provide adequate clearance Around air openings To combustibles For service access Locate appliance away from traffic areas A Selecting Appliance Location When selecting a locati...

Страница 7: ...lding codes MUST be checked Chases should be constructed in the manner of all out side walls of the home to prevent cold air drafting prob lems The chase should not break the outside building envelope in any manner Walls ceiling base plate and cantilever floor of the chase should be insulated Vapor and air infiltration barriers should be installed in the chase as per regional codes for the rest of...

Страница 8: ...H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING Angle H Min M 0 26 6 0 30 26 6 30 3 0 38 30 3 33 7 0 46 33 7 36 9 0 61 36 9 39 8 0 76 39 8 42 5 0 99 42 5 45 0 1 22 45 0 49 4 1 52 49 4 53 1 1 83 53 1 56 3 2 13 56 3 59 0 2 29 59 0 60 3 2 44 91 M minimum in snow regions Figure 4 1 Minimum height from roof to lowest discharge opening Figure 4 3 Staggered Termination Caps Gas Wood or Fuel Oi...

Страница 9: ...open on a minimum of 2 sides beneath the floor or meets Note 2 NOTE 1 On private property where termination is less than 7 feet above a sidewalk driveway deck porch veranda or balcony use of a listed cap shield is suggested See flue components page NOTE 2 Termination in an alcove space spaces open only on one side and with an overhang are permitted with the dimensions specified for vinyl or non vi...

Страница 10: ... 90º elbow On 45º runs 30 5 cm of diagonal is equal to 21 6 centimeters horizontal run and 21 6 centimeters vertical run A length of straight pipe is allowed between two 45º elbows see Flue diagrams Figure 5 1 A Flue Table Key The abbreviations listed in this flue table key are used in the flue diagrams C Measuring Standards Vertical and horizontal measurements listed in the flue diagrams were mad...

Страница 11: ... H2 Maximum Elbow only Not Allowed 30 cm 91 cm 61 cm 1 8 m 91 cm 2 7 m 1 2 m 3 7 m 1 5 m 4 6 m V H1 H2 Maximum 11 9 m H1 H2 Maximum 4 6 m D Flue Diagrams One Elbow V Minimum H Maximum Elbow only 76 cm 30 cm 91 cm 61 cm 1 8 m 91 cm 2 7 m 1 2 m 3 7 m 1 5 m 4 6 m V H Maximum 11 9 m H Maximum 4 6 m H2 H1 V1 INSTALLED HORIZONTALLY V1 H1 ...

Страница 12: ...orizontal Termination continued Three Elbows Three Elbows V1 Minimum H1 Maximum V2 Minimum H2 Maximum 30 cm 61 cm 30 cm 61 cm 61 cm 1 2 m 61 cm 1 2 m 91 cm 1 8 m 91 cm 1 8 m 1 2 m 2 4 m 1 2 m 2 2 m V1 V2 H1 H2 Maximum 11 9 m H1 H2 Maximum 4 6 m H1 V2 H2 V1 ...

Страница 13: ...Vertical Termination No Elbow Figure 5 6 Figure 5 7 Two Elbows V1 11 8 m Maximum V1 V1 V2 H1 Two Elbows V1 Minimum H Maximum Elbow only 46 cm 30 cm 91 cm 61 cm 1 2 m 91 cm 1 8 m 1 2 m 2 4 m 1 8 m 4 6 m V1 V2 H Maximum 11 9 m H1 H2 Maximum 4 6 m ...

Страница 14: ...14 Figure 5 8 2 Vertical Termination continued Three Elbows V2 H2 V1 INSTALLED HORIZONTALLY H1 Three Elbows V1 Minimum H1 H2 Maximum 30 cm 61 cm 61 cm 91 cm 91 cm 1 5 m 1 2 m 2 1 m 1 5 m 4 3 m V1 V2 H1 H2 Maximum 11 9 m H1 H2 Maximum 4 3 m ...

Страница 15: ...enever a non combustible wall is penetrated the wall shield firestop is only required on one side and no heat shield is necessary Figure 6 2 Exterior Wall Hole A B Shows center of flue framing hole The center of the hole is 2 54 cm above the center of the horizontal flue pipe Fire Risk Explosion Risk Maintain flue clearance to combustibles as specified Do not pack air space with insulation or othe...

Страница 16: ... to form a tube Bend three tabs on the bottom of the shield outward to allow attachment to the ceiling firestop Bend the remaining bottom tabs inward 90 to maintain the air space between the pipe and the shield Set the shield on the ceiling firestop and attach to the firestop Bend all tabs inward 90 around the top of the shield These tabs must be used to prevent blown insulation from getting betwe...

Страница 17: ...ide to side and front to back Shim the appliance as necessary It is acceptable to use wood shims Bend out nailing tabs on each side Keep nailing tabs flush with the framing Secure the appliance to the framing by using nails or screws through the nailing tabs Figure 7 7 Proper Positioning Leveling and Securing of a Appliance Fire Risk ALWAYS maintain specified clearances around the appliance Do NOT...

Страница 18: ...wo sto ries or High Rise Applications For Installation into a commercial multi family multi level exceeding two stories or high rise applications All outer pipe joints must be sealed with high temperature silicone including the slip section that connects directly to the hori zontal termination cap Apply a bead of silicone sealant inside the female outer pipe joint prior to joining sections Only ou...

Страница 19: ...firestop must to be trimmed A minimum 4 cm overlap MUST be maintained Use an extended heat shield if the finished wall thickness is greater than 18 cm The extended heat shield may need to be cut to length maintaining sufficient length for a 4 cm overlap between heat shields Attach the extended heat shield to either of the existing heat shields using the screws supplied with the extended heat shiel...

Страница 20: ... brackets Insert a bolt provided through the brackets and tighten the nut to complete the storm collar assembly Make sure the collar is tight against the pipe section Slide the assembled storm collar down the pipe section until it rests on the roof flashing see Figure 8 7 Caulk around the top of the storm collar see Figure 8 5 D Installing Vertical Termination Cap Attach the vertical termination c...

Страница 21: ...ar 15 8 25mbar 15 5 25mbar 5 4 11mbar Gas Rate 405 m3 h 134 m3 h 111 m3 h 40 m3 h Max Input NETCV 4 0 kW 3 5 kW 3 6 kW 3 5 kW Burner Injector DMS 50 DMS 58 DMS 61 DMS 50 Pilot Injector 51 30 30 51 B Gas Connection Note Have the gas supply line installed in accordance with local building codes by a qualified installer approved and or licensed as required by the locality Note Before the first firing...

Страница 22: ...t system The batteries are located within the ignition module which is located under the unit A wiring diagram is shown in Figure 7 1 The battery pack requires four AA batteries not included Figure 10 1 Electronic Ignition Wiring Diagram 10 10 Electrical Information CAUTION Battery polarity must be correct or module damage will occur CAUTION Label all wires prior to disconnection when servicing co...

Страница 23: ...E ZONE FINISH WALL MATERIAL MAY BE COMBUSTIBLE TOP AND SIDES 20 3 cm 74 cm 0 cm 0 cm 0 cm B Mantel Projections No mantels are allowed when using Studio CE fronts Risk of Fire Non combustible clearances MUST be maintained Sheetrock wood or other combustibles must NOT be used as sheathing or facing in the non combustible zone See Section 11 for proper clearances See Section 1 for combustible non com...

Страница 24: ...ial Ember material is shipped with this gas appliance To place the ember material Place small pieces of ember material on burner top around burner ports Do NOT press embers into burner ports Do NOT place embers in the center area shown in Figure 12 1 Use this material to give the appliance a realistic ash bed Save the remaining ember materials for use during appliance servicing The embers provided...

Страница 25: ...ocating tab Step 2 Place Log 2 SRV2111 701 onto base pan such that Log 2 fits in groove of Log 1 Push it back against the left hand side locating tab Ensure burner ports are not covered by logs Step 3 Place Log 3 SRV2111 702 so the top rests on Log 1 against Log 2 The base slot on Log 3 will fit over the locating tab on the front right hand side LOCATING TABS Figure 12 2 Figure 12 6 3 3 1 1 2 2 1 ...

Страница 26: ...e firebox liner by placing it on the base pan of the fireplace and sliding it back until it contacts the back of the fireplace See Figure 12 7 Figure 12 6 Figure 12 8 4 Set the rock tray on top of the base pan See Figure 12 8 DO NOT INSTALL ROCKS IN THIS AREA LOCATING TABS FIREBOX LINER BASE PAN Delayed Ignition Risk Do NOT place rocks on burner Do NOT place rocks in a position that they may fall ...

Страница 27: ...bly Replace the glass door on the appliance Pull out and latch the two glass assembly latches into the groove on the glass frame on the bottom and top edges BOTTOM LATCH GLASS ASSEMBLY Handle glass doors with care Inspect the gasket to ensure it is undamaged Inspect the glass for cracks chips or scratches Do NOT strike slam or scratch glass Do NOT operate appliance with glass door removed cracked ...

Страница 28: ...tter adjustment Ensure that there are no gas leaks Ensure that the glass is sealed and in the proper position Ensure that the flow of combustion and ventilation air is not obstructed flue terminations 13 13 Operating Instructions Glass door must be in place when appliance is operating Risk of Combustion Fumes Fire Do NOT operate appliance with glass door removed Open viewing glass for servicing on...

Страница 29: ... settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance DO NOT CONNECT 240 VAC TO THE CONTROL VALVE Improper installation adjustment alteration service or maintenance can cause injury or property dam age Refer to the owner s information manual provided with this fireplace This fireplace needs fresh air for safe operation and must be installed so there are provisions for ...

Страница 30: ...et off smoke detectors Smoke and odors may be irritating to sensitive individuals CAUTION Fire Hazard Keep combustible materials gasoline and other flammable vapors and liquids clear of appliance Do NOT store flammable materials in the appliance s vicinity Do NOT use gasoline lantern fuel kerosene charcoal lighter fluid or similar liquids in this appliance Combustible materials may ignite WARNING ...

Страница 31: ... along cable D Valve Replace valve Do not over tighten E Over tightened thermocouple interrupter Replace valve and thermocouple interrupter F Receiver Replace receiver and reprogram code 5 Pilot is lit and control continues to spark Valve shuts off after 10 30 seconds Valve operates manually A Receiver Replace receiver and reprogram code 6 Pilot is lit sparking stops if a flame is present Valve sh...

Страница 32: ...glass after initial 3 4 hours operation Longer operation without cleaning glass may cause a permanent white film on glass CAUTION When cleaning glass door Avoid striking scratching or slamming glass Do NOT use abrasive cleaners Use a hard water deposit glass cleaner on white film Do NOT clean glass when hot Turn off appliance after 3 4 hours of operation and ALLOW TO COOL Remove and clean glass as...

Страница 33: ...orrect as necessary Firebox 1 Inspect for paint condition warpage corrosion or perforation Sand and repaint as necessary 2 Replace appliance if firebox has been perforated Burner Ignition and Operation 1 Verify burner is properly secured and aligned with pilot or igniter 2 Clean off burner top inspect for plugged ports corrosion or deterioration Replace burner if necessary 3 Replace ember material...

Страница 34: ...F 5 6 O 94 6 G 11 5 P 9 6 H 83 2 Q 5 7 I 58 6 Appliance Dimensions Table Figure 16 1 Appliance Dimensions A B C D E F G H I J K L M ØN O P Q GAS LINE ACCESS ELECTRICAL ACCESS 16 16 Reference Materials A Appliance Dimension Diagram Dimensions are actual appliance dimensions Use for reference only For framing dimensions and clearances refer to Section 3 ...

Страница 35: ...Heat Glo Soho CE 2111 900 Rev i 10 10 38 C Limited Lifetime Warranty ...

Страница 36: ...Heat Glo Soho CE 2111 900 Rev i 10 10 39 ...

Страница 37: ...our nearest Heat Glo dealer please visit www heatnglo com Printed in U S A Copyright 2010 DO NOT DISCARD THIS MANUAL CAUTION Leave this manual with party responsible for use and operation Important operating and maintenance instructions included Read understand and follow these instructions for safe installation and operation THIS PRODUCT MAY BE COVERED BY ONE OR MORE OF THE FOLLOWING PATENTS Unit...

Отзывы: