29
If the pressure is not suffi cient, ensure:
• The piping used is large enough.
• The supply regulator is adequately adjusted.
• That the total gas load for the residence does not
exceed the amount supplied.
The supply regulator (the regulator that attaches directly
to the residence inlet or to the propane tank) should supply
gas at the suggested input pressure listed above. Contact
the local gas supplier if the regulator is at an improper
pressure.
Leak test all gas line joints and the gas control valve prior
to and after starting the appliance.
Before making the gas connection, ensure that the
appliance you are installing is designed for the type of
gas being supplied. This information can be found on the
ratings label under the appliance. If the appliance has
been converted to propane (LP), the valve cover should
have a label stating that the appliance has been converted
to propane.
Connect the gas line at the 3/8 in. (10 mm) pipe connector
on the valve at the back of appliance.
We recommend
connecting the appliance with an approved flex gas line.
If flex gas lines are not approved in your area, you must
connect a hard pipe to the gas hookup.
You must supply a manual shut-off valve in a visible
location within 3 ft. (914 mm) of the appliance.
Note:
Have the gas supply line installed in accordance
with local building codes, if any. If not, follow ANSI
223.1. Installation should be done by a qualifi ed installer
approved and/or licensed as required by the locality. (In
the Commonwealth of Massachusetts installation must be
performed by a licensed plumber or gas fi tter).
D. Gas Connection
Note:
A listed (and Commonwealth of Massachusetts ap-
proved) 1/2 inch (13 mm) T-handle manual shut-off valve and
fl exible gas connector are connected to the 1/2 inch (13 mm)
control valve inlet.
• If substituting for these components, please consult
local codes for compliance.
Gas Leak Risk
• Support control when attaching pipe to
prevent bending gas line.
Note:
The gap between supply piping and gas access hole
may be caulked with high temperature caulk or stuffed with
non-combustible, unfaced insulation to prevent cold air
infi ltration.
WARNING
Fire hazard.
Do NOT change the valve settings.
• This valve has been preset at the factory.
• Changing valve settings may result in fi re
hazard or bodily injury.
CHECK FOR GAS LEAKS
Explosion Risk
Fire Risk
Asphyxiation Risk
• Check all fi ttings and connections.
• Do not use open fl ame.
• After the gas line installation is complete, all
connections must be tightened and checked
for leaks with a commercially-available,
non-corrosive leak check solution. Be sure
to rinse off all leak check solution following
testing.
Fittings and connections may have loosened
during shipping and handling.
Fire or Explosion Hazard
• Gas buildup during line purge may ignite.
• Purge should be performed by qualifi ed technician.
• Ensure adequate ventilation.
• Ensure there are no ignition sources such as
sparks or open fl ames.
• A small amount of air will be in the gas supply lines.
When fi rst lighting appliance it will take a short time for
air to purge from lines. When purging is complete the
appliance will light and operate normally.
Air only needs to be purged again if gas valve has been
turned to the OFF position.
WARNING
WARNING
WARNING
HIGH ALTITUDE INSTALLATIONS
Omni-Test Laboratories, Inc. listed gas appliances are tested
and approved without requiring changes for elevations from
0 to 2000 feet in the U.S.A. and 0 to 4500 feet in Canada.
When installing this appliance at an elevation above 2000
feet, it may be necessary to decrease the input rating by
changing the existing burner orifi ce to a smaller size. Input
rate should be reduced by 4% for each 1000 feet above a
2000 foot elevation in the U.S.A. If the heating value of the
gas has been reduced, these rules do not apply. To identify
the proper orifi ce size, check with the local gas utility.
If installing this appliance at an elevation above 4500 feet
(in Canada), check with local authorities.