background image

Heat & Glo  •  PIER-HV-IPI, ST-HV-IPI, L&R-COR-HV-IPI  •  2005-900  Rev. M  •  9/08

36

• Insert insulation from the outside of the fireplace and

pack the insulation tightly to totally seal between the

pipe and the outer casing.

• At the gas line access hole the gap between the supply

piping and gas access hole can be plugged with non-

combustible insulation to prevent cold air infiltration.

Step 6.  The Gas Supply Line

NOTE: Have the gas supply line installed in accordance

with

local

building  codes  by  a  qualified  installer

approved and/or licensed as required by the locality.

(In the state of Massachusetts installation must be

performed by a licensed plumber or gas fitter).
NOTE: Before the first firing of the fireplace, the gas

supply line should be purged of any trapped air.
NOTE: Consult local building codes to properly size

the  gas  supply  line  leading  to  the  1/2  inch

(13 mm) hook-up at the unit.

This  gas  fireplace  is  designed  to  accept  a  1/2  inch

(13 mm) gas supply line.
To install the gas supply line:
• A listed (and State of Massachusetts approved) 1/2 inch

(13mm) tee-handle manual shut-off valve and a listed

flexible gas connector are connected to the 1/2 inch

(13mm) inlet of the control valve. 

NOTE:

 If substituting

for these components, please consult local codes for

compliance.

• Locate the gas line access hole in the outer casing of

the fireplace.

• The gas line may be run from either side of the fireplace

provided the hole in the outer wrap does not exceed 2” in

diameter and it does not penetrate the actual firebox.

• Open the fireplace lower grille, insert the gas supply line

through the gas line hole, and connect it to the shut-off

valve.

• When attaching the pipe, support the control so that the

lines are not bent or torn.

• After the gas line installation is complete, all connec-

tions must be tightened and checked for leaks with a

commercially-available, non-corrosive leak check solu-

tion. Be sure to rinse off all leak check solution following

testing.

WARNING: DO NOT USE AN OPEN FLAME

TO CHECK FOR GAS LEAKS

.

!

Step 7.  Gas Pressure Requirements

Pressure requirements for Heat & Glo gas fireplaces

are shown in the table below.

Pressure

Natural Gas

Propane

Minimum

5.0 inches

11.0 inches

Inlet Pressure

w.c.

w.c.

Maximum Inlet

14.0 inches

14.0 inches

Gas Pressure

w.c.

w.c.

Manifold

3.5 inches

10.0 inches

Pressure

w.c.

w.c.

A one-eighth (1/8) inch (3 mm) N.P.T. plugged tapping is

provided on the inlet and outlet side of the gas control for a

test gauge connection to measure the manifold pressure.
The  fireplace  and  its  individual  shut-off  valve  must  be

disconnected from the gas supply piping system during

any pressure testing of the system at test pressures in

excess of one-half (1/2) psig (3.5 kPa).
The fireplace must be isolated from the gas supply piping

system by closing its individual shut-off valve during any

pressure testing of the gas supply piping system at test

pressures equal to or less than one-half (1/2) psig (3.5 kPa).

Figure 33.   Gas Supply Line

USE A WRENCH ON

SHUT-OFF VALVE

WHEN TIGHTENING

GAS LINE.

MANUAL

SHUT-OFF

VALVE

FLEX CONNECTOR

GAS VALVE

GAS LINE

ACCESS

CONTROL VALVE

Содержание LCOR-HV-IPI

Страница 1: ...her flammable materials away DO NOT DISCARD THIS MANUAL CAUTION Important operating and maintenance instructions included This appliance may be installed as an OEM installation in manufactured home US...

Страница 2: ...f the fireplace front READ and UNDERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will vo...

Страница 3: ...3 A Vent System Approvals 23 B Installing Vent Components 30 C Vent Termination 32 Step 4 Positioning Leveling and Securing the Fireplace 35 Step 5 The Gas Control System 35 Step 6 The Gas Supply Line...

Страница 4: ...R COR HV IPI 2005 900 Rev M 9 08 4 3 2 5 4 6 1 Log Set Assembly Service Parts Diagram Service Parts Pier HV IPI Beginning Manufacturing Date June 2003 Ending Manufacturing Date ______ 8 9 10 11 7 Par...

Страница 5: ...bly GLA MS X Ember Mesh Assembly 2006 008 Exhaust Baffle 385 128 Fiberglass Rope 060 455 Glass Latch Assembly 386 122A X Junction Box 4021 013 X Lava Rock 2005 790 Mineral Wool 050 721 Non Combustible...

Страница 6: ...be installed in a bedroom or bed sitting room in the U S A and Canada 1Approvals and Codes High Altitude Installations U L Listed gas appliances are tested and approved with out requiring changes for...

Страница 7: ...hall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas inspector of the side wall horizontally vented...

Страница 8: ...ensure maximum safety and benefit Failure to follow these instructions will void the own er s warranty and may present a fire hazard The Heat Glo Warranty will be voided by and Heat Glo disclaims any...

Страница 9: ...5mm 42 5 8 1082mm 8 205mm 12 305mm ELECTRICAL ACCESS GAS LINE ACCESS 34 3 4 883mm 4 1 16 102mm 4 1 2 114mm 4 3 4 121mm 2 5 16 58mm 37 7 16 950mm 17 15 16 455mm 24 610mm 21 9 16 547mm 32 5 16 820mm 21...

Страница 10: ...183mm 42 1067mm 32 5 16 821mm 21 9 16 548mm 36 3 16 919mm 2 5 16 58mm 4 3 4 121mm 4 1 16 102mm 4 1 2 114mm ELECTRICAL ACCESS GAS LINE ACCESS 12 305mm 4 1 2 114mm 2 9 16 64mm 24 610mm 8 1 2 216mm 34 3...

Страница 11: ...5mm 8 205mm 34 3 4 882mm 10 254mm 7 1 4 184mm 4 3 4 121mm 32 5 16 821mm 37 7 16 950mm ELECTRICAL ACCESS GAS LINE ACCESS 42 5 8 1083mm 2 9 16 64mm 2 5 16 58mm 17 15 16 455mm 21 9 16 547mm 24 1 8 612mm...

Страница 12: ...t the face of the fireplace is one inch 25 mm The metal ends of the fireplace may NOT be recessed into combustible construction Note Refer to Figure 4B for dimensions and appliance locations if instal...

Страница 13: ...ceiling is measured from the top of the unit excluding the standoffs see Figures 37 38 The distance from the unit to combustible construction is to be measured from the unit outer wrap surface to the...

Страница 14: ...23 35 3 4 48 ST HV IPI 47 5 8 42 1 2 23 35 3 4 48 L RCOR HV IPI 42 1 8 42 1 2 28 3 4 35 3 4 48 Figure 5 Framing Dimensions NOTE DIMENSIONS SHOWN IN INCHES Shows center of 10 x 12 vent framing holes fo...

Страница 15: ...AP 1 1 4 INCHES AT EACH JOINT Figure 6 DVP Series Direct Vent Component Specifications 5 inch inner pipe 8 inch outer pipe DVP90ST 12 9 16 11 1 4 7 1 4 1 1 4 TYP 1 2 TYP 8 9 16 DVP36 DVP48 48 24 36 4...

Страница 16: ...iguration used Identifying Vent Components The vent systems installed on this gas fireplace may in clude one two or three 90 elbow assemblies The rela tionships of vertical rise to horizontal run in v...

Страница 17: ...ctor into two pieces Do this by bending the part back and forth until it breaks see Figure 10 1 2 3 4 5 SETTINGS 1 2 3 4 5 5 Center the Flue Restrictor on vent and secure in place using two self tappi...

Страница 18: ...2 MAX 610mm 2 MIN 610mm 4 MAX 1 22m 3 MIN 914mm 6 MAX 1 83m 4 MIN 1 22m 8 MAX 2 4m 5 MIN 1 5m 10 MAX 3 0m 6 MIN 1 83m 12 MAX 3 6m V H 50 MAX 15 2m NATURAL GAS VENTING WITH ONE 90 ELBOW V FT H FT 900...

Страница 19: ...10mm 2 MIN 610mm 4 MAX 1 22m 3 MIN 914mm 6 MAX 1 83m 4 MIN 1 22m 8 MAX 2 4m 5 MIN 1 5m 10 MAX 3 0m 6 MIN 1 83m 12 MAX 3 6m V H H1 50 MAX 15 2m NATURAL GAS VENTING WITH TWO 90 ELBOWS V V1 FT H FT 900 E...

Страница 20: ...610mm 2 MIN 610mm 4 MAX 1 22m 3 MIN 914mm 6 MAX 1 83m 4 MIN 1 22m 8 MAX 2 4m 5 MIN 1 5m 10 MAX 3 0m 6 MIN 1 83m 12 MAX 3 6m V H H1 50 MAX 15 2m H H1 12 MAX 3 6m H H1 18 MAX 5 5m NATURAL GAS VENTING W...

Страница 21: ...4 MAX 1 22m 3 MIN 914mm 6 MAX 1 83m 4 MIN 1 22m 8 MAX 2 4m 5 MIN 1 5m 10 MAX 3 0m 6 MIN 1 83m 12 MAX 3 6m V V1 H H1 H2 50 MAX 15 2m H H1 H2 12 MAX 3 6m H H1 H2 18 MAX 5 5m NATURAL GAS VENTING WITH TH...

Страница 22: ...AX 914mm 2 MIN 610mm 6 MAX 1 83m 3 MIN 914mm 9 MAX 2 7m 4 MIN 1 22m 12 MAX 3 6m 5 MIN 1 5m 15 MAX 4 5m 6 MIN 1 83m 18 MAX 5 5m V V1 H H1 50 MAX 15 2m PROPANE VENTING WITH THREE 90 ELBOWS V V1 FT H H1...

Страница 23: ...f the unit horizontally the elbow cover plate must first be removed from the unit see Figure 20 The elbow can be removed from the unit by aligning the seams of the elbow to the arrows on the surroundi...

Страница 24: ...each succeed ing component into place Ensure that each succeeding vent component is secure ly fitted and locked into the preceding component in the vent system Securing pipe sections with a maximum o...

Страница 25: ...s To attach and secure the termination to the last section of horizontal vent refer to the Cinch Pipe and Termination Cap installation instructions Push on and snap lock as described at the beginning...

Страница 26: ...en only on one side and with an overhang are permitted with the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be 3 feet minimum between termination caps 2 All mechanical...

Страница 27: ...ECESSARY IN THE INTER EST OF SAFETY SEE THE FOLLOWING DIAGRAM FOR MINIMUM HEIGHTS PROVIDED THE TERMI NATION CAP ISAT LEAST 20 INCHES FROMAVER TICAL WALLAND 2 FEET BELOWAHORIZONTAL OVERHANG NOTE This a...

Страница 28: ...the base pan for securing the unit to the floor The diagram below shows how to properly position level and secure the fireplace Figure 31 Proper Positioning Leveling and Securing of a Fireplace Step...

Страница 29: ...exceed 2 in diameter and it does not penetrate the actual firebox Open the fireplace lower grille insert the gas supply line through the gas line hole and connect it to the shut off valve When attach...

Страница 30: ...rity when wiring the junc tion box Figure 34 Intermittent Pilot Ignition IPI Wiring Diagram Operation using Battery Power This fireplace has an optional battery operation The sys tem is fully function...

Страница 31: ...cessories Optional fan and remote control kits require that 110 120 VAC be wired to the factory installed junction box before the fireplace is permanently installed NOTE If any of the original wire as...

Страница 32: ...ed switch leg wire to the wall switch as shown At the appliance connect the black hot white neutral and green ground wires to the junction box as shown Add a 1 4 inch insulated female connector to the...

Страница 33: ...ther combustible mate rial such as wood can be placed on the top edge and sides of the fireplace Hearth Extensions A hearth extension may be desirable for aesthetic reasons However ANSI or CAN CGA tes...

Страница 34: ...l Type PIER HV IPI TEMPERED ST HV IPI TEMPERED L RCOR HV IPI TEMPERED Heat Glo fireplaces manufactured with tempered glass may be installed in hazardous locations such as bathtub enclosures as defined...

Страница 35: ...should cover the remaining base pan area see Figure 46 Do not put lava rock on top of the glass teco sil Figure 46 Turn on the electric ember lights and paint the glass to a darkness as desired see Fi...

Страница 36: ...ember materials for use during fire place servicing The bag of embers provided is sufficient for 3 to 5 applications Replace the glass door and a front trim door on the unit Figure 50 Placement of the...

Страница 37: ...ng is complete the fireplace will light and will operate normally Subsequent lightings of the fireplace will not require this purging of air from the gas supply lines unless the gas valve has been tur...

Страница 38: ...logs Cleaning Flame Sensor Rod IPI Systems Frequency Periodically By Qualified service technician Task Make a visual check of the straight flame sensor rod Use emery cloth to carefully remove any exis...

Страница 39: ..._________________________________________________________ _______________________________________________________________________________ DO NOT DISCARD THIS MANUAL CAUTION Important operating and mai...

Отзывы: