Heat & Glo  •  PIER-HV-IPI, ST-HV-IPI, L&R-COR-HV-IPI  •  2005-900  Rev. M  • 9/08

33

V

= VENT  TERMINAL

X

= AIR SUPPLY INLET

= AREA WHERE TERMINAL IS NOT PERMITTED

     Figure 29.  Vent Termination Minimum Clearances

A

= 12" ....................... clearances above grade, veran-

da, porch, deck or balcony

B

= 12" ....................... clearances  to  window  or  door

that may be opened, or to per-

manently  closed  window.

D*

= 18" ....................... vertical clearance to unventilat-

ed soffit or to ventilated soffit lo-

cated above the terminal

 *36” ...................... for  vinyl  clad  soffits  and  below

electrical  service

F

=  9" ........................ clearance to outside corner

G

= 6" ......................... clearance to inside corner

H

= 3 ft. (Canada) ...... not  to  be  installed  above  a  gas

meter/regulator  assembly  within

3 feet (90cm) horizontally from the

center-line of the regulator

I

= 3 ft. ....................... clearance  to  gas  service  regu-

lator vent outlet

J

= 9" (U.S.A.)

12"  (Canada) ........ clearance to non-mechanical air

supply  inlet  to  building  or  the

combustion air inlet to any other

appliance

K

= 3 ft. (U.S.A.)

6 ft. (Canada) ......... clearance  to  a  mechanical

air supply inlet

L** = 7 ft. ......................... clearance  above  paved

sidewalk or a paved driveway

located on 

public

 property

M*** = 18" ......................... clearance  under  veranda,

porch, deck, balcony or over-

hang.

36” ......................... vinyl

N

= 6” ........................... non-vinyl  sidewalls

12” ......................... vinyl  sidewalls

P

= 8 ft.

CAUTION: IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS SUGGESTED THAT A VINYL PROTECTOR KIT BE
INSTALLED.

  ** a  vent  shall  not  terminate  directly  above  a  sidewalk  or  paved

driveway  which  is  located  between  two  single  family  dwellings

and  serves  both  dwellings.

 *** only permitted if veranda, porch, deck or balcony is fully open on

a minimum of 2 sides beneath the floor, or meets Note 2.

NOTE  1

:  On  private  property  where  termination  is  less  than  7  feet

above a sidewalk, driveway, deck, porch, veranda or balcony, use of

a listed cap shield is suggested.

NOTE 2

: Termination in an alcove space (spaces open only on one side

and with an overhang) are permitted with the dimensions specified for

vinyl or non-vinyl siding and soffits. 

1

. There must be 3 feet minimum

between termination caps. 

2.

 All mechanical air intakes within 10 feet

of a termination cap must be a minimum of 3 feet below the termination

cap.

3.

 All gravity air intakes within 3 feet of a termination cap must be

a minimum of 1 foot below the termination cap.

(See Note 1)

(See Note 1)

(See Note 2)

S =  6" .......................... clearance from sides of elec-

trical service

T = 12" ......................... clearance  above  electrical

service

______________________________________________________________________

______________________________________________________________________

______________________________________________________________________

______________________________________________________________________

Q

MIN

     R

MAX

  1 cap

  3 feet

   2 x Q 

ACTUAL

  2 caps

  6 feet

   1 x Q 

ACTUAL

  3 caps

  9 feet

2/3 x Q 

ACTUAL

  4 caps

12 feet

1/2 x Q 

ACTUAL

Q

MIN

 = # termination caps x 3        R

MAX

 = (2 / # termination caps) x Q

ACTUAL

(See Note 5)

(See Note 5)

Electrical

Service

V

S

V

S

V

T

D*

V

NOTE  3

:  Local  codes  or  regulations  may  require  different

clearances.

NOTE 4: 

Termination caps may be hot. Consider their proximity to

doors  or  other  traffic  areas.

NOTE 5: 

Location of the vent termination must not interfere with

access  to  the  electrical  service.

WARNING: In the U.S:

 Vent system termination is 

NOT

 permitted

in  screened  porches. You  must  follow  side  wall,  overhang  and

ground clearances as stated in the instructions.

In Canada:

 Vent system termination is 

NOT

 permitted in screened

porches.  Vent  system  termination  is  permitted  in  porch  areas

with  two  or  more  sides  open.  You  must  follow  all  side  walls,

overhang and ground clearances as stated in the instructions.
Heat  &  Glo  assumes  no  responsibility  for  the  improper  perfor-

mance of the fireplace when the venting system does not meet

these  requirements.

D

E

B

L

v

v

v

v

v

v

v

v

B

B

A

H

M

X

J or K

I

A

G

F

U.S.

(3 FT)

B

M

N

P

R

Q

Содержание LCOR-HV-IPI

Страница 1: ...her flammable materials away DO NOT DISCARD THIS MANUAL CAUTION Important operating and maintenance instructions included This appliance may be installed as an OEM installation in manufactured home US...

Страница 2: ...f the fireplace front READ and UNDERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will vo...

Страница 3: ...3 A Vent System Approvals 23 B Installing Vent Components 30 C Vent Termination 32 Step 4 Positioning Leveling and Securing the Fireplace 35 Step 5 The Gas Control System 35 Step 6 The Gas Supply Line...

Страница 4: ...R COR HV IPI 2005 900 Rev M 9 08 4 3 2 5 4 6 1 Log Set Assembly Service Parts Diagram Service Parts Pier HV IPI Beginning Manufacturing Date June 2003 Ending Manufacturing Date ______ 8 9 10 11 7 Par...

Страница 5: ...bly GLA MS X Ember Mesh Assembly 2006 008 Exhaust Baffle 385 128 Fiberglass Rope 060 455 Glass Latch Assembly 386 122A X Junction Box 4021 013 X Lava Rock 2005 790 Mineral Wool 050 721 Non Combustible...

Страница 6: ...be installed in a bedroom or bed sitting room in the U S A and Canada 1Approvals and Codes High Altitude Installations U L Listed gas appliances are tested and approved with out requiring changes for...

Страница 7: ...hall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas inspector of the side wall horizontally vented...

Страница 8: ...ensure maximum safety and benefit Failure to follow these instructions will void the own er s warranty and may present a fire hazard The Heat Glo Warranty will be voided by and Heat Glo disclaims any...

Страница 9: ...5mm 42 5 8 1082mm 8 205mm 12 305mm ELECTRICAL ACCESS GAS LINE ACCESS 34 3 4 883mm 4 1 16 102mm 4 1 2 114mm 4 3 4 121mm 2 5 16 58mm 37 7 16 950mm 17 15 16 455mm 24 610mm 21 9 16 547mm 32 5 16 820mm 21...

Страница 10: ...183mm 42 1067mm 32 5 16 821mm 21 9 16 548mm 36 3 16 919mm 2 5 16 58mm 4 3 4 121mm 4 1 16 102mm 4 1 2 114mm ELECTRICAL ACCESS GAS LINE ACCESS 12 305mm 4 1 2 114mm 2 9 16 64mm 24 610mm 8 1 2 216mm 34 3...

Страница 11: ...5mm 8 205mm 34 3 4 882mm 10 254mm 7 1 4 184mm 4 3 4 121mm 32 5 16 821mm 37 7 16 950mm ELECTRICAL ACCESS GAS LINE ACCESS 42 5 8 1083mm 2 9 16 64mm 2 5 16 58mm 17 15 16 455mm 21 9 16 547mm 24 1 8 612mm...

Страница 12: ...t the face of the fireplace is one inch 25 mm The metal ends of the fireplace may NOT be recessed into combustible construction Note Refer to Figure 4B for dimensions and appliance locations if instal...

Страница 13: ...ceiling is measured from the top of the unit excluding the standoffs see Figures 37 38 The distance from the unit to combustible construction is to be measured from the unit outer wrap surface to the...

Страница 14: ...23 35 3 4 48 ST HV IPI 47 5 8 42 1 2 23 35 3 4 48 L RCOR HV IPI 42 1 8 42 1 2 28 3 4 35 3 4 48 Figure 5 Framing Dimensions NOTE DIMENSIONS SHOWN IN INCHES Shows center of 10 x 12 vent framing holes fo...

Страница 15: ...AP 1 1 4 INCHES AT EACH JOINT Figure 6 DVP Series Direct Vent Component Specifications 5 inch inner pipe 8 inch outer pipe DVP90ST 12 9 16 11 1 4 7 1 4 1 1 4 TYP 1 2 TYP 8 9 16 DVP36 DVP48 48 24 36 4...

Страница 16: ...iguration used Identifying Vent Components The vent systems installed on this gas fireplace may in clude one two or three 90 elbow assemblies The rela tionships of vertical rise to horizontal run in v...

Страница 17: ...ctor into two pieces Do this by bending the part back and forth until it breaks see Figure 10 1 2 3 4 5 SETTINGS 1 2 3 4 5 5 Center the Flue Restrictor on vent and secure in place using two self tappi...

Страница 18: ...2 MAX 610mm 2 MIN 610mm 4 MAX 1 22m 3 MIN 914mm 6 MAX 1 83m 4 MIN 1 22m 8 MAX 2 4m 5 MIN 1 5m 10 MAX 3 0m 6 MIN 1 83m 12 MAX 3 6m V H 50 MAX 15 2m NATURAL GAS VENTING WITH ONE 90 ELBOW V FT H FT 900...

Страница 19: ...10mm 2 MIN 610mm 4 MAX 1 22m 3 MIN 914mm 6 MAX 1 83m 4 MIN 1 22m 8 MAX 2 4m 5 MIN 1 5m 10 MAX 3 0m 6 MIN 1 83m 12 MAX 3 6m V H H1 50 MAX 15 2m NATURAL GAS VENTING WITH TWO 90 ELBOWS V V1 FT H FT 900 E...

Страница 20: ...610mm 2 MIN 610mm 4 MAX 1 22m 3 MIN 914mm 6 MAX 1 83m 4 MIN 1 22m 8 MAX 2 4m 5 MIN 1 5m 10 MAX 3 0m 6 MIN 1 83m 12 MAX 3 6m V H H1 50 MAX 15 2m H H1 12 MAX 3 6m H H1 18 MAX 5 5m NATURAL GAS VENTING W...

Страница 21: ...4 MAX 1 22m 3 MIN 914mm 6 MAX 1 83m 4 MIN 1 22m 8 MAX 2 4m 5 MIN 1 5m 10 MAX 3 0m 6 MIN 1 83m 12 MAX 3 6m V V1 H H1 H2 50 MAX 15 2m H H1 H2 12 MAX 3 6m H H1 H2 18 MAX 5 5m NATURAL GAS VENTING WITH TH...

Страница 22: ...AX 914mm 2 MIN 610mm 6 MAX 1 83m 3 MIN 914mm 9 MAX 2 7m 4 MIN 1 22m 12 MAX 3 6m 5 MIN 1 5m 15 MAX 4 5m 6 MIN 1 83m 18 MAX 5 5m V V1 H H1 50 MAX 15 2m PROPANE VENTING WITH THREE 90 ELBOWS V V1 FT H H1...

Страница 23: ...f the unit horizontally the elbow cover plate must first be removed from the unit see Figure 20 The elbow can be removed from the unit by aligning the seams of the elbow to the arrows on the surroundi...

Страница 24: ...each succeed ing component into place Ensure that each succeeding vent component is secure ly fitted and locked into the preceding component in the vent system Securing pipe sections with a maximum o...

Страница 25: ...s To attach and secure the termination to the last section of horizontal vent refer to the Cinch Pipe and Termination Cap installation instructions Push on and snap lock as described at the beginning...

Страница 26: ...en only on one side and with an overhang are permitted with the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be 3 feet minimum between termination caps 2 All mechanical...

Страница 27: ...ECESSARY IN THE INTER EST OF SAFETY SEE THE FOLLOWING DIAGRAM FOR MINIMUM HEIGHTS PROVIDED THE TERMI NATION CAP ISAT LEAST 20 INCHES FROMAVER TICAL WALLAND 2 FEET BELOWAHORIZONTAL OVERHANG NOTE This a...

Страница 28: ...the base pan for securing the unit to the floor The diagram below shows how to properly position level and secure the fireplace Figure 31 Proper Positioning Leveling and Securing of a Fireplace Step...

Страница 29: ...exceed 2 in diameter and it does not penetrate the actual firebox Open the fireplace lower grille insert the gas supply line through the gas line hole and connect it to the shut off valve When attach...

Страница 30: ...rity when wiring the junc tion box Figure 34 Intermittent Pilot Ignition IPI Wiring Diagram Operation using Battery Power This fireplace has an optional battery operation The sys tem is fully function...

Страница 31: ...cessories Optional fan and remote control kits require that 110 120 VAC be wired to the factory installed junction box before the fireplace is permanently installed NOTE If any of the original wire as...

Страница 32: ...ed switch leg wire to the wall switch as shown At the appliance connect the black hot white neutral and green ground wires to the junction box as shown Add a 1 4 inch insulated female connector to the...

Страница 33: ...ther combustible mate rial such as wood can be placed on the top edge and sides of the fireplace Hearth Extensions A hearth extension may be desirable for aesthetic reasons However ANSI or CAN CGA tes...

Страница 34: ...l Type PIER HV IPI TEMPERED ST HV IPI TEMPERED L RCOR HV IPI TEMPERED Heat Glo fireplaces manufactured with tempered glass may be installed in hazardous locations such as bathtub enclosures as defined...

Страница 35: ...should cover the remaining base pan area see Figure 46 Do not put lava rock on top of the glass teco sil Figure 46 Turn on the electric ember lights and paint the glass to a darkness as desired see Fi...

Страница 36: ...ember materials for use during fire place servicing The bag of embers provided is sufficient for 3 to 5 applications Replace the glass door and a front trim door on the unit Figure 50 Placement of the...

Страница 37: ...ng is complete the fireplace will light and will operate normally Subsequent lightings of the fireplace will not require this purging of air from the gas supply lines unless the gas valve has been tur...

Страница 38: ...logs Cleaning Flame Sensor Rod IPI Systems Frequency Periodically By Qualified service technician Task Make a visual check of the straight flame sensor rod Use emery cloth to carefully remove any exis...

Страница 39: ..._________________________________________________________ _______________________________________________________________________________ DO NOT DISCARD THIS MANUAL CAUTION Important operating and mai...

Отзывы: