Heat & Glo • ST-36TRB-IPI, PIER-36TRB-IPI, LCOR-36TRB-IPI, RCOR-36TRB-IPI • 2128-900 Rev. i • 3/13
53
F. Wall Switch Installation for Fan (Optional)
If the box is being wired to a wall mounted switch for use
with a fan (See Figure 12.4):
• The power supply for the appliance must be brought into
a switch box.
• The power can then be supplied from the switch box to
the appliance using a minimum of 14-3 with ground wire.
• At the switch box connect the black (hot) wire and red
(switch leg) wire to the wall switch as shown.
• At the appliance connect the black (hot), white (neutral)
and green (ground) wires to the junction box as shown.
• Add a 1/4 in. insulated female connector to the red (switch
leg) wire, route it through the knockout in the face of the
junction box, and connect to the top fan switch connector
(1/4 in. male) as shown.
ROMEX CONNECTORS
Figure 12.3 Junction Box Detail
NOTICE: DO NOT wire 110-120 VAC to wall switch.
RED
SWITCH
SWITCH BOX
RED
BLACK
BLACK
GREEN
GREEN
WHITE
POWER
SUPPLY
WIRES
WHITE
RED
BLACK
GREEN
WHITE
MINIMUM 14-3 AWG
WITH GROUND
JUNCTION BOX
KNOCKOUT
Figure 12.4 Junction Box Wired to Wall Switch
E. Junction Box Installation
The junction box must be wired from the
INSIDE
of the
appliance:
• Determine which side of the appliance the junction box
is located on.
• Pull the electrical wires from outside the appliance through
the knockout making sure to use a Romex connector to
fasten the electrical wires to the unit.
• Pull enough wire into the valve compartment to easily reach
the junction box location.
• Remove the screw attaching the junction box to the junction
box bracket and set it aside.
• Route the wire through the knockout in the junction box
bracket.
• Wire the junction box and reattach it to the bracket by
inserting the tab in the slot and attaching with screw
previously removed. Ensure that a Romex connector is
used to attach the electrical wires to the junction box.