background image

11

Heat & Glo  •  TIARA II-B  •  7011-148 Rev. G  •  10/12

D. 

How to Use the Vent Graph

E. 

Venting Guidelines

1.  Measure the distance from the top of appliance to the 

center of the 90° elbow. On the graph below, draw a 
horizontal line from that measurement on the vertical axis 
across until it intersects with the slanted  line.

2.  From the point of this intersection, draw a vertical line to 

the bottom of the graph.

3.  The point at which this line meets the bottom line of the 

graph is the maximum length of the horizontal run. 

Example 1

:  If the vertical dimension from the center line of 

the  fl ue vent to the center of the 90° elbow is 7 ft. (2m), the 
horizontal run to the outer wall fl ange must not exceed 16 ft. 
(5m).

.

Example 2:

 

 

If the vertical dimension from the center line of the 

fl ue vent is 21 ft. (6m), the horizontal run to the outer wall fl ange 
must not exceed 12 ft. 10 in. (4m).

4.  Each 90° elbow is equivalent to 3 ft. (914mm) of vent pipe 

and each 45° elbow is equivalent to 1 ft. (305mm) of vent 
pipe, and must be subtracted from the vent pipe run. A 
single horizontal to vertical 90° elbow is already calculated 
into the allowable 20 ft. (6m) run. Each additional 90° 
elbow reduces the maximum horizontal distance by 3 ft. 
(914mm).

Example:  

The use of 3 elbows would reduce the allowable 

horizontal run to 9 ft. (3 -1 =  2 elbows x 3 ft. = 6 ft.; 20 ft. 
max. - 6 ft. = 14 ft. max.).

•  The maximum horizontal vent run is 20 ft. (6m) when the 

vertical vent rise is 10 ft. (3m).

•  The minimum horizontal vent run is 6 in. (152mm).

•  Horizontal sections require a 1/4 in. (6mm) rise for every 12 

in. (305 mm) of horizontal travel.

•  Exterior Vent Diameter = 6-5/8 in. (168mm); Inner Vent 

Diameter = 4 in. (102mm).

•  Horizontal sections require non-combustible support every 

3 ft. (914mm), e.g. wall straps.

•  For any vertical termination a minimum of 6 ft. (2m)  vertical 

must be used.

Figure 5.2

Example 1 

Example 2 

2'           4'          6 '          8'          10'         12'        14'   15'  16'  17'  18'  19'  20' 

2' 

4' 

6' 

8' 

10' 

12 

14' 

16' 

18' 

20' 

22' 

24' 

26' 

28' 

30' 

32' 

34' 

35' 

36' 

37' 

38' 

39' 

40' 

Damper position 

more CLOSED in 

this area 

40 ft. (12m)  

Maximum Vertical 

VERTICAL DISTANCE 

FROM APPLIANCE TO 

90° ELBOW 

6 in. (152mm) Minimum  

Vertical Termination 

For rear vent or top of 

appliance for top vent 

6 in. (152mm) Minimum starter pipe 

3 ft. (914mm) Maximum Horizontal run with no 
vertical pipe and with 1/4 in (6mm) rise per foot. 
Must use Snorkel cap. 

No damper 
in this area 

Damper position 

more OPEN in 

this area 

 

Part:  SLK-991DA

Part:  SLK-011TRD

EXCEPTIONS FOR HORIZONTAL INSTALLATIONS:

*When installing in a rear vent configuration with no 
vertical rise, a Snorkel Kit must be used. Refer to venting 
components.
*The maximum horizontal vent run is 3 ft. (914mm).
*The maximum horizontal vent run with a 45° elbow is 2 ft.  
(609mm).
*The minimum horizontal vent run is 6 in. (152mm).

INDIVIDUAL INSTALLATIONS MAY VARY.  PERCENTAGE 
CLOSED BASED ON FULL RANGE OF DAMPER TRAVEL.

NOTE:  IF YOUR INSTALLATION FALLS WITHIN A SHADED 
AREA ON THE GRAPH, THE DAMPER MUST BE USED.* SEE 
INFORMATION ON DAMPER ADJUSTMENT ON PAGE 31.
*In the Commonwealth of Massachusetts, the word damper 
shall be replaced with the words flue restrictor.

Содержание Heat & Glo TIARAII-BK-B

Страница 1: ...operty damage personal injury or death Installation and service of this appliance should be performed by qualified personnel Hearth Home Technologies suggests NFI certified or factory trained professionals or technicians supervised by an NFI certified professional DO NOT DISCARD This appliance may be installed as an OEM installation in manufactured home USA only or mobile home and must be installe...

Страница 2: ...pplicablesectionsofUL307bGasBurningHeatingAppliancesforManufacturedHomesandRecreational Vehicles CAN CGA2 17 M91GasFiredAppliancesforuseatHighAltitudes ThisapplianceismanufacturedforoperationwithNaturalGas ForconversiontopropaneManufacturer sinstructionsmustbeused This appliancemaybeinstalledinabedroomorbedsittingroom inCanadaremotethermostatinstallationisrequired APPROUVÉ POURLECANADAETLESÉTATS U...

Страница 3: ...27 Section 8 Appliance Setup A Remove Shipping Materials 28 B Top to Rear Conversion 28 C Damper Adjustment 29 D Shutter Adjustment 29 E Leg Leveling System 30 F Brick Installation 30 G Positioning the Logs 31 H Mineral Wool 31 I Accessories 31 J Optional Blower 31 K Glass Replacement 33 L Warming Shelves Installation 34 Section 9 Operating Instructions A Before Lighting Appliance 35 B Controls 35...

Страница 4: ...YPE Vented Gas Fireplace Heater STANDARD ANSI Z21 88 2002 ּ CSA 2 33 2002 UL307b ּ CAN CBA 2 17 M91 Model US or Canada Maximum Input BTU Minimum Input BTU Orifice Size Steady State Efficiency P 4 Tiara II B NG 38 500 27 000 120 81 36 60 97 Tiara II B LP 39 000 30 500 073 83 62 64 14 Materials that are reported as passing ASTM E 136 Standard Test Method for Behavior of Materials in a Vertical Tube ...

Страница 5: ...vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS G Requirements for the Commonwealth of Massachusetts Inspection The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installa ti...

Страница 6: ... Inspect appliance and components for damage Damaged parts may impair safe operation WARNING Do NOT install damaged components Do NOT install incomplete components Do NOT install substitute components Report damaged parts to dealer Where the appliance is to be installed The vent system configuration to be used Gas supply piping Electrical wiring Whether optional accessories devices such as a blowe...

Страница 7: ...efer to Section 12 A G A A B F E A A measurement is from appliance top not side C C G H D 90 off top up and out ceiling Model A B C D E F G H Top of pipe Side of pipe Inside Outside corner wall vent Tiara II B Inches 5 1 4 1 4 3 8 54 36 40 31 3 4 1 1 2 1 9 Millimeters 133 6 9 1 2 1372 914 1016 806 76 25 229 NOTE Flooring beneath appliance may reach 90 degrees plus room ambient temperature Check wi...

Страница 8: ...of Pitch H Min Ft Flat to 6 12 1 0 Over 6 12 to 7 12 1 25 Over 7 12 to 8 12 1 5 Over 8 12 to 9 12 2 0 Over 9 12 to 10 12 2 5 Over 10 12 to 11 12 3 25 Over 11 12 to 12 12 4 0 Over 12 12 to 14 12 5 0 Over 14 12 to 16 12 6 0 Over 16 12 to 18 12 7 0 Over 18 12 to 20 12 7 5 Over 20 12 to 21 12 8 0 3 foot minimum in snow regions Measure vertical clearances from this surface Measure horizontal clearances...

Страница 9: ... D V D E B L v v v v v v v v B B A H M X J or K I A G F U S 3 FT B M N P R Q RMAX 2 termination caps x QACTUAL QMIN termination caps X 3 a vent shall not terminate diretly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings only permitted if veranda porch deck or balcony is fully open on a minimum of 2 sides beneath the floor or meets N...

Страница 10: ...agonal runs have both vertical and horizontal vent aspects when calculating the effects Use the rise for the vertical aspect and the run for the horizontal aspect See Figure 5 1 Two 45 elbows may be used in place of one 90 elbow On 45 runs one foot of diagonal is equal to 8 1 2 in 216mm horizontal run and 8 1 2 in 216mm vertical run A length of straight pipe is allowed between two elbows See Figur...

Страница 11: ...0 ft 3m The minimum horizontal vent run is 6 in 152mm Horizontal sections require a 1 4 in 6mm rise for every 12 in 305 mm of horizontal travel Exterior Vent Diameter 6 5 8 in 168mm Inner Vent Diameter 4 in 102mm Horizontal sections require non combustible support every 3 ft 914mm e g wall straps For any vertical termination a minimum of 6 ft 2m vertical must be used Figure 5 2 Example 1 Example 2...

Страница 12: ... locked The female locking lugs may not be visible from the outside They may be located by examining the inside of the female ends Type A Up Out Installation Type C 45 Elbow in Corner Installation Type B Straight Out Installation 45 Elbow 3 8 in 10mm Clearance from stove corner to combustible wall 3 8 in 10mm Clearance from stove corner to combustible wall for valve access on side Wall Thimble Hea...

Страница 13: ...mm square around the pilot hole See Figure 5 7 8 in 203mm 7 in 178mm 7 in 178mm 6 in 152mm Figure 5 6 Figure 5 7 Figure 5 5 CENTER LINE CENTER OF HOLE WALL THIMBLE CENTER LINE Step 3 For installations using a round support box wall thimble check pipe manufacturer s instructions mark the wall for a 10 in x 10 in 254mm x 254mm square hole The center of the square hole should line up with the center ...

Страница 14: ...ides VINYL SIDING Figure 5 8 Fire Risk Exhaust Fume Risk Impaired Performance of Appliance WARNING Ensure vent components are locked together correctly Pipe may separate if not properly joined Note The attachment from the vent pipe to the vent termination cap must be sealed with silicone Termination caps shall not be recessed into a wall or siding Burn Risk Local codes may require installation of ...

Страница 15: ...le placed in the roof in Step 2 The hole should be of sufficient size to meet the minimum requirements for clearance to combustibles as specified Continue to assemble lengths of pipe and elbows necessary to reach from the ceiling support box wall thimble up through the roof line Galvanized pipe and elbows may be utilized in the attic as well as above the roofline The galvanized finish is desirable...

Страница 16: ...t above and below the joint between the storm collar and the pipe Optional High Wind Termination Cap Secure Flashing with Non Hardening Sealant and Roofing Nails Figure 5 15 Ceiling Firestop Nails Minimum 1 in 25mm Clearance Minimum 1 in 25mm Clearance Minimum 1 in 25mm Clearance Minimum 1 in 25mm Clearance Figure 5 16 Fire Risk Explosion Risk WARNING Any occupied areas above the first floor inclu...

Страница 17: ...dges of the support box to make a seal between it and the roof Clean out any combustible material from inside the support box Step 7 Complete the cathedral ceiling installation by following the same procedures outlined in steps 7 through 9 for vertical installations pages 17 18 Step 6 Place the support clamp provided with the support box inside the support box at the bottom and secure to the pipe ...

Страница 18: ... installer BEFORE converting to direct vent appliance High Wind Termination Cap Sheet Metal Screws Drill Four 1 8 in 3mm Diamater Holes Figure 5 22 Figure 5 23 Step 4 Pass the flex pipe down through the center of the chimney system and center the top adapter on the top of the chimney pipe Drill four 1 8 in 3mm diameter holes through the top adapter and into the chimney top Ensure that you are dril...

Страница 19: ... below the end of the 4 ft 1m Air Intake section This section of the chimney must be sealed TERMINATION CAP FLASHING 4 in 102mm FLEX LINER TOP ADAPTOR RETRO CONNECTOR 90 ELBOW DIRECT VENT PIPE Chimney Liner Termination Cap 30 ft 9m of 3 in 76mm Flex Liner Exhaust Section 4 ft 1m of 3 in 76mm Flex Liner Air Intake Section Chimney must be sealed from 4 ft 1m section to termination using a smoke shel...

Страница 20: ...length extended to its nominal length Be sure to leave 2 3 in 51 76mm of flex above the existing chimney to allow for connection to the termination kit Step 3 Secure the flashing to the top of the masonry chimney using a bead of non hardening sealant adhesive If the flashing is larger than the top of the chimney cut and fold flashing as needed to fit chimney Figure 5 26 Step 5 Connect the flex lin...

Страница 21: ...lide wall thimble cover over retro connector and secure with masonry bolts Figure 5 30 If you have a framed wall in front of the masonry use wood screws to mount wall thimble cover to framed wall over retro connector and 10 in 254mm square framed opening Figure 5 25 page 22 If needed add a section of direct vent pipe to the retro connector in order to extend through the opening in the wall thimble...

Страница 22: ...rx TH20 5 32 in Allen wrench 5 8 in open end wrench Remove front if installed glass and logs if installed Figure 6 1 Using the 2 Phillips screwdriver remove the two 2 1 4 x 20 screws securing the burner as indicated Lift burner out of firebox Figure 6 3 Pull off pilot hood and set aside NOTE Do not remove retaining clip from hood NOTE Gas conversions should only be performed by a qualified service...

Страница 23: ...ng a Torx TH20 or slotted screwdriver remove the three pressure regulator mounting screws 1 pressure regulator tower 2 and diaphragm 3 2 Valve Regulator Replacement Remove upper and lower back shield Loosen the set col lars on the extension rods with the 3 32 in Allen wrench Remove the rods and adapter cap Fire Risk Explosion Risk Disconnect any electrical cords and turn off gas supply to unit bef...

Страница 24: ...gas appliances are operating Install regulator upstream of valve if line pressure is greater than 1 2 psig NOTE A listed and Commonwealth of Massachusetts approved 1 2 inch 13mm T handle manual shut off valve and flexible gas connector are connected to the 1 2 inch 13mm control valve inlet If substituting for these components please consult local codes for compliance NOTE The gap between the suppl...

Страница 25: ...d by 4 for each 1000 feet above a 2000 foot elevation in the U S A If the heating value of the gas has been reduced these rules do not apply To identify the proper orifice size check with the local gas utility If installing this appliance at an elevation above 4500 feet in Canada check with local authorities A small amount of air will be in the gas supply lines When first lighting appliance it wil...

Страница 26: ...f appliance 4 Use low resistance thermostat wire for wiring from igni tion system to the wall switch and thermostat 5 Use the following chart for wire sizing 6 Keep wire lengths as short as possible by removing any excess wire length 7 Low voltage and 110 VAC voltage cannot be shared within the same wall box Wire Size Max Length 16 gauge 65 feet 18 gauge 40 feet 20 gauge 25 feet 22 gauge 18 feet W...

Страница 27: ...e Pilot position and depressed the ignitor should begin sparking immediately If the ignitor does not begin sparking immediately then it is in need of service The ignitor is located on a plate attached to the side of the appliance using two 8 Phillips head screws To access the ignitor remove the two screws securing the plate to the side of the appliance and slide the plate out The single AA 1 5 V b...

Страница 28: ...ealant to bottom of adapter before installing as shown in Figure 8 8 Figure 8 3 Remove the inner collar adapter Screws Screws Figure 8 4 Locate the knock out on rear of appliance Either remove the four screws holding the back shield in place saving the screws OR break the seal on the knock out and discard the knock out Figure 8 5 Remove rear access plate and gasket Save the screws CAUTION Sharp Ed...

Страница 29: ...re 8 10 Locate the damper adjustment on the intake plenum accessing through the appliance front Adjustor is centered at the top of the appliance 1 Rear Vent Installations Figure 8 9 The rear vent damper is located in the back of the firebox It is recommended to make adjustment prior to installation 1 Remove front glass logs and brick if installed 2 Loosen screws and slide up to suggested settings ...

Страница 30: ...plied with this appliance is NOT an optional accessory The brick must be installed for safe and proper operation F Brick Installation REAR PANEL Figure 8 15 Install rear panel by placing it behind the log pins flush and centered against back of firebox TABS Figure 8 16 Install left and right side panels Fold tabs over on left and right sides to hold panels in place TOP PANEL BAFFLE Figure 8 17 Ins...

Страница 31: ...ll approved accessories per instructions included with accessories Refer to Section 12 for appropriate accesso ries Shock or Fire risk Use ONLY optional accessories approved for this appliance Using non listed accessories voids warranty Using non listed accessories may result in a safety hazard Only Hearth Home Technologies approved accessories may be used safely WARNING J Optional Blower The GFK ...

Страница 32: ...bly onto the 10 32 screw located on the left underside of the appliance Secure the bracket assembly with the wing nut provided Disconnect the two wire ends connected together on the power cord Connect female end to one side of temperature sensor switch Connect one end of the black wire provided with the kit to the remaining wire end on power cord Feed loose ends of the black and blue wires through...

Страница 33: ...its bottom and carefully set aside 4 The new glass will come installed in a new glass frame Installation of the new glass and frame is the opposite of the removal 5 Re install appliance front Handle glass assembly with care CAUTION Inspect the gasket to ensure it is undamaged Inspect the glass for cracks chips or scratches Do NOT strike slam or scratch glass Do NOT operate appliance with glass doo...

Страница 34: ...igure 8 30 Install warming shelf bracket loosely to each warming shelf using the screw provided Figure 8 31 Gently lift cast top off of appliance and set aside Install warming shelf to appliance gently aligning the shelf with the tabs that are in place on the side of the appliance Use the leveling screw located in the center of the warming shelf to adjust the shelf to its desired position Figure 8...

Страница 35: ...that there are no gas leaks Ensure that the glass is sealed and in the proper posi tion Ensure that the flow of combustion and ventilation air is not obstructed front grilles and vent caps B Controls FAN SPEED The blower is optionally installed on the appliance and this knob controls the speed of the blower that pushes the heated air into the room MAIN BURNER This control is used to turn the appli...

Страница 36: ... power from the appliance 4 Open the door of the appliance May need to remove face front first 5 Push in gas control knob slightly and turn clockwise to the OFF position Do not force 6 Wait five 5 minutes to clear out any gas Smell for gas including near the floor If you smell gas STOP Follow B of the safety information above If you don t smell gas go to the next step 7 Push gas control knob in an...

Страница 37: ... of appliance Keep furniture draperies away from appliance ISSUE SOLUTIONS Condensation on the glass This is a result of gas combustion and temperature variations As the appliance warms this condensation will disappear Blue flames This is a result of normal operation and the flames will begin to yellow as the appliance is allowed to burn for 20 to 40 minutes Odor from appliance When first operated...

Страница 38: ...hermocouple connection at the gas valve is fully inserted and tight hand tighten plus 1 4 turn Disconnect the thermocouple from the valve place one millivolt lead wire on the tip of the thermocouple and the other meter wire on the thermocouple copper lead Start the pilot and hold the valve knob in If the millivolt reading is less than 15mV replace the thermocouple b Defective valve If the thermoco...

Страница 39: ...exhaust gases back into the system Check for proper vent connection at flue collar and all vent joints c Horizontal vent improperly pitched The horizontal vent cap should slope down only enough to prevent any water from entering the appliance d Bad thermopile or thermocouple Replace if necessary e Improper vent cap installation Check for proper installation and freedom from debris or blockage 6 Gl...

Страница 40: ... door Avoid striking scratching or slamming glass Do NOT use abrasive cleaners Use a hard water deposit glass cleaner on white film Do NOT clean glass when hot Turn off appliance after 3 4 hours of operation and ALLOW TO COOL Remove and clean glass assembly Replace glass assembly and operate appliance for additional 12 hours Refer to maintenance instructions Inspect external vent cap regularly Ens...

Страница 41: ...and and repaint as neces sary 2 Replace appliance if firebox has been perforated Burner Ignition and Operation 1 Verify burner is properly secured and aligned with pilot or igniter 2 Clean off burner top inspect for plugged ports corrosion or deterioration Replace burner if necessary USE CAUTION WHEN CLEANING HANDLING CERAMIC BURNER 3 Replace ember material with new dime size and shape pieces Do n...

Страница 42: ...B Location Inches Millimeter Location Inches Millimeter A 41 3 4 1060 E 22 1 4 565 B 29 1 2 749 F 14 3 4 375 C 9 1 2 240 G 22 1 4 565 D 29 1 4 743 NOTE Diagrams show gas appliance equipped with optional Blower Part GFK 160A D E Dimensions are actual appliance dimensions Use for reference only For clearances to combustibles refer to Section 3 ...

Страница 43: ... 4 in 235mm 6 1 2 in 165mm 6 5 8 in 168mm 17 24 in 432 610mm 11 3 4 in 298mm 5 3 4 in 146mm 6 5 8 in 168mm 6 3 8 in 162mm 6 1 2 in 165mm 9 5 8 in 244mm 6 5 8 in 168mm 6 1 2 in 165mm 6 3 8 in 162mm 9 5 8 in 244mm SLP6M SLP12M SLP12AM SLP45 BK SLP90M 3 3 4 in 95mm 12 17 in 305 432mm 35 3 4 in 908mm 23 3 4 in 603mm 47 3 4 in 1213mm SLP4M SLP48M SLP36M SLP24M SLP6AM ...

Страница 44: ...ck SLP36 BK 46 DVA 36B 48 Pipe Length Galvanized SLP48M 46 DVA 48 48 Pipe Length Black SLP48 BK 46 DVA 48B Adjustable Length 3 6 Black SLP6A BK Adjustable Length 3 6 Galvanized SLP6AM Adjustable Length 3 7 Galvanized 46DVA 08A Adjustable Length 3 7 Black 46DVA 08AB Adjustable Length 3 12 Black SLP12A BK Adjustable Length 3 12 Galvanized SLP12AM Adjustable Length 3 14 5 Galvanized 46DVA 16A Adjusta...

Страница 45: ... d a R e v i t a r o c e D Firestop Spacer Ceiling Firestop SLP FSM 46DVA FS Flex Trap Cap with Firestop SLP FLEX TRAP Flex Trap Cap with Firestop and 30 Flex Pipe SLP FLEX TRAP30 Masonry Chimney Conversion Kit 46DVA KMC S E A V D 6 4 t r o p p u S t e s f f O K B T W P L S k c a l B e l b m i h T l l a W t e s f f O C S A V D 6 4 M C S P L S r a l l o C m r o t S S W A V D 6 4 M S V H P L S d n a...

Страница 46: ...owing page Log Set Assembly 1 3 2 Gas Stove DV 4 5 6 8 9 11 12 13 14 15 16 17 18 19 20 21 22 23 24 10 7 Color SKU No Mfg Dates Matte Black Tiaraii BK B 8 03 Active Brown TiaraII BR B 8 03 Active Espresso TiaraII CES 9 07 Active Color SKU No Mfg Dates Almond TiaraII AL B 8 03 8 05 Green TiaraII GR B 8 03 8 05 Tuscan Olive TiaraII CTO 9 07 3 11 10 12 D Service Parts ...

Страница 47: ...k 7011 105BK Brown 7011 105PBR Espresso 7011 105CES Green 7011 105PGR Tuscon Olive 7011 105CTO 6 Brick Retainer 479 0190 7 Door LH Almond 7011 131PAL Black 7011 131BK Brown 7011 131PBR Espresso 7011 131CES Green 7011 131PGR Tuscon Olive 7011 131CTO 8 Door RH Almond 7011 130PAL Black 7011 130BK Brown 7011 130PBR Espresso 7011 130CES Green 7011 130PGR Tuscon Olive 7011 130CTO 9 Brick Set BRICK T2 10...

Страница 48: ...alve Gas NG S I T 230 0710 Y 21 Back Shield 7011 124 22 Switch Rocker ON OFF 230 0730 Y 23 Ignition Module 230 1880 Y 24 Ignition Access Cover 464 0300 Adapter DV 4 in 200 2470 Adapter DV 6 5 8 in 7010 172 Air Deflector 7011 139 AVK Repair Kit RIVNUT REPAIR Y Blower Bracket 7010 146 Blower Housing 7010 145 Burner Neck Support Assembly PRE 007879357 7011 008 Y POST 007879357 7011 016 Y Gasket Burne...

Страница 49: ... Rheostat 100 512 Y Rheostat Assembly 100 510A Y Temp Sensor Limit w Bracket 107 531A Y Flex Line 3 8 COMP x 30 in 200 2940 Y Flex Line 3 8 Flare x 22l 7000 197 Y Gasket Cover Plate 7010 160 Gasket Elbow 460 0610 Gasket Flue Collar 455 0660 Hinge Pin Gold Button Head Pkg of 2 844 5750 Y Igniton Control Cable 230 1900 Y Knob Brass 200 2390 Leveling Assembly 7000 000 Magnet Round SRV7000 140 Y Miner...

Страница 50: ...an authorized dealer Stocked at Depot ITEM DESCRIPTION COMMENTS PART NUMBER Conversion Kit NG NGK T2 Y Conversion Kit LP LPK T2 Y Pilot Orifice NG 842 4440 Y Pilot Orifice LP 200 2630 Y Regulator NG 230 1570 Y Regulator LP 230 1520 Y ACCESSORIES Mesh Screen MESH T2 Grill Rear Vent RV GRILLE T2 Warming Shelf Black WS TIARA BK Brown WS TIARA BR Espresso WS TIARA CES No longer available WS TIARA CTO ...

Страница 51: ...purchase In the case of new home construction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent authorized HHT dealer distributor whichever occurs earlier The warranty shall commence no later than 24 months following the date of product shipment from HHT regardless of the installation or occupancy date The warranty...

Страница 52: ...QRUPDO XVH V D KHDWLQJ DSSOLDQFH VRPH FKDQJHV LQ FRORU RI LQWHULRU DQG H WHULRU VXUIDFH ILQLVKHV PD RFFXU 7KLV LV QRW D IODZ DQG LV QRW FRYHUHG XQGHU ZDUUDQW DPDJH WR SULQWHG SODWHG RU HQDPHOHG VXUIDFHV FDXVHG E ILQJHUSULQWV DFFLGHQWV PLVXVH VFUDWFKHV PHOWHG LWHPV RU RWKHU H WHUQDO VRXUFHV DQG UHVLGXHV OHIW RQ WKH SODWHG VXUIDFHV IURP WKH XVH RI DEUDVLYH FOHDQHUV RU SROLVKHV 5HSDLU RU UHSODFHPHQW ...

Страница 53: ...ARA II B GAS STOVE Printed in U S A Copyright 2012 Heat Glo TIARA II B 7011 148 Rev G 10 12 Heat Glo a brand of Hearth Home Technologies Inc 7571 215th St Lakeville MN 55044 www heatnglo com Please contact your Heat Glo dealer with any questions or concerns For the location of your nearest Heat Glo dealer please visit www heatnglo com F Contact Information This product may be covered by one or mor...

Отзывы: