Heat & Glo BW36 Скачать руководство пользователя страница 16

4-00

16

30491D

BW36 SERIES WOODBURNING FIREPLACE

No one builds a better fire

24"

AS8 ATTIC
INSULATION
SHIELD

FS338
FIRESTOP
SPACER

CHIMNEY

INSULATION

10

1

/

2

"

14

1

/

2

"

Figure 14

Installing an AS8

Figure 16

Ceiling and Attic Construction

STEP 10 - Marking the Exit Point of the Roof.

Locate the point where the chimney will exit the roof
by plumbing down to the center of the chimney.
Drive a nail up through the roof to mark the center.
See Figure 16.

STEP 8 - Double-checking the Chimney Assembly.

Continue assembling the chimney sections up through
the firestop spacers as needed.  While doing so, be
aware of the height and unsupported chimney length
limitations that are given on page 11 under “Chimney
Requirements”.

Check each section by pulling up slightly from the top
to ensure proper engagement before installing the
succeeding sections.  If they have been connected
correctly, they will not disengage when tested.

STEP 9 - Securing the Chimney System.

When offsets and returns are joined to straight pipe
sections, they must be locked into position with the
screws provided, using the predrilled holes.  To prevent
gravity from pulling the chimney sections apart, the
returns and the chimney stabilizers have straps for
securing these parts to joists or rafters.
See Figure 15.

FIRESTOP

STRAPS

OPTIONAL
ADDITIONAL
SUPPORT

JOINT

BAND

(OPTIONAL)

STEP 11 - Cutting Out the Hole in the Roof.

Measure to either side of the nail and mark the 14

1

2

" x

14

1

2

" opening required.  This is measured on the hori-

zontal; actual length may be larger depending on the
pitch of the roof.  Cut out and frame the opening.
See Chapter 25 of the Uniform Building Code for
Roof Framing details.  Be sure to maintain a 2" mini-
mum air space between the chimney section and the
roof.

WARNING!

WHEN CHIMNEY SECTIONS EXCEED-

ING SIX FEET IN LENGTH ARE

INSTALLED BETWEEN AN OFFSET/

RETURN, STRUCTURAL SUPPORT

MUST BE PROVIDED TO REDUCE

OFF-CENTER LOADING AND PRE-

VENT CHIMNEY SECTIONS FROM

SEPARATING AT THE CHIMNEY

JOINTS.

NOTE: Be sure to provide support for the
pipe during construction and check to be
sure inadvertent loading has not dislodged
the chimney section from the fireplace or at
any chimney joint.

Figure 15 - Offset/Return with Stabilizer

Содержание BW36

Страница 1: ...on of Hearth Technologies Inc 20802 Kensington Blvd Lakeville MN 55044 BW36 BW36C WOODBURNING FIREPLACE INSTALLATION OPERATING INSTRUCTIONS FOR RESIDENTIAL USE Model BW36 shown 558 900 D 4 00 No one b...

Страница 2: ...may not provide all the air required to support combustion Heat N Glo is not responsible for any smoking or related prob lems that may result from the lack of adequate combustion air It is the respons...

Страница 3: ...EMS IN THIS SYSTEM UNLESS ALLOWED BY THESE INSTALLATION INSTRUCTIONS WILL VOID THE UNDERWRITERS LABORATORIES LISTING AND MAY VOID THE PRODUCT WARRANTY IT MAY ALSO CREATE A HAZARDOUS INSTALLATION READ...

Страница 4: ...24 long SL336 Chimney Section 36 long SL348 Chimney Section 48 long SL3 Chimney Stabilizer SL315 Chimney Offset Return 15 SL330 Chimney Offset Return 30 FS338 Firestop Straight FS339 Firestop 15 FS34...

Страница 5: ...1 71 4 33 4 36 335 8 21 6 385 8 327 8 BW36 BW36C 52 16 4 00 5 30491D GR16 AS8 HEARTH EXTENSIONS GLASS DOORS OUTSIDE AIR KIT STRAIGHT ATTIC INSULATION SHIELD INTEGRAL GRATES BW36 SERIES WOODBURNING FIR...

Страница 6: ...5 8 HTI CAT A B FS338 0 141 2 FS339 15 183 8 FS340 30 23 CHIMNEY SECTIONS CHIMNEY STABILIZER OFFSETS RETURNS SL3 FIRESTOP SPACERS ROOF FLASHING 101 2 Flat to 6 12 Pitch RF370 6 12 to 12 12 Pitch RF371...

Страница 7: ...ECTIONS TR342 ROUND TERMINAL CAP TR344 ROUND TERMINAL CAP WITH STORM COLLAR CT35 CHASE TOP ST375 SQUARE TERMINAL CAP 72 36 2 107 8 BW36 SERIES WOODBURNING FIREPLACE No one builds a better fire 8 Flue...

Страница 8: ...AIR MAY BE DRAWN FROM ATTIC SPACES BASEMENTS OR ABOVE THE ROOF WHERE OTHER HEATING APPLIANCES OR FANS AND CHIMNEYS EXHAUST OR UTILIZE AIR THESE PRECAUTIONS WILL REDUCE THE POSSIBILITY FOR SMOKING OR F...

Страница 9: ...TION LOCALIZED OVERHEATING COULD OCCUR AND A FIRE COULD RESULT Combustible Material Material made of or surfaced with wood compressed paper plant fibers plastics or any material capable of igniting a...

Страница 10: ...4 00 10 30491D Figure 5 Factory Built Hearth Extension Figure 6 Hearth Extension EXAMPLES OF INSULATION USG MICORE CV230 1 2 0 43 REQUIRED THICKNESS K VALUE x 5 THICKNESS OF ALTERNATE MAT INCHES x 5 5...

Страница 11: ...ween Offset Return 6 ft Maximum straight unsupported chimney height above firebox 25 ft 4 SIDEWALLS SURROUNDS 5 MANTEL BW36 SERIES WOODBURNING FIREPLACE CAT A B BW36 36 38 5 8 BW36C 36 38 5 8 93 4 143...

Страница 12: ...The B dimensions that coincide with the A dim ensions represent the required vertical clearance that is needed to complete the offset and return d Read across the chart and find the number of chimney...

Страница 13: ...adverse wind conditions etc may create a need for a taller chimney should smok ing occur 2 CHIMNEY HEIGHT REQUIREMENTS Above the roof line Figure 9 Chimney Height Height of Chimney Components Chimney...

Страница 14: ...assembly Framing that is per pendicular to the fireplace front may contact the side of the firebox assembly at the nailing flanges Slide the metal strips two inches under the front edge of the firepl...

Страница 15: ...e you slip it on the collar Once it is on line it up and secure it with screws to the unit collar through the slots in the elbow Figure 13 Installing the Firestop Spacer STEP 7 Installing an AS8 insul...

Страница 16: ...ctions they must be locked into position with the screws provided using the predrilled holes To prevent gravity from pulling the chimney sections apart the returns and the chimney stabilizers have str...

Страница 17: ...replace sides and the enclosure as well as the fireplace back and the enclosure See Figure 4 for framing details STEP 16 Provisions for an Optional Gas Log Set Knockouts are provided on both sides of...

Страница 18: ...art a structure fire You may only use non combustible material over the black face of the fireplace Refer to Figure 7 for combustible material information Do not cover or restrict any of the louvered...

Страница 19: ...S MUST BE STRICTLY FOLLOWED INCLUDING THE PROVISION OF AIR SPACE CLEARANCE BETWEEN CHIMNEY SYSTEM AND ENCLO SURE TO PROTECT AGAINST AGAINST THE EFFECTS OF CORROSION ON THOSE PARTS EXPOSED TO THE WEATH...

Страница 20: ...RFACES FAILURE TO OPERATE THIS FIREPLACE WITH THE DAMPER IN THE OPEN POSI TION MAY RESULT IN ASPHYXIATION OR A STRUCTURE FIRE CAUTION FIREPLACE OPERATION DOES RE QUIRE AIR DO NOT TAKE AIR FROM OTHER F...

Страница 21: ...volatile fuels that burn at excessive tem peratures may cause the fireplace to operate in an unsafe manner Flammable liquid fuel are explosive and must never be used to start or freshen a fire Heat N...

Страница 22: ...bstructions damage or poor wet fuels can cause smoke spillage CHIMNEY INSPECTION Visually inspect the chim ney internally for obstructions and construction dam age Flue pipe joints and seams must be c...

Страница 23: ...e place and to allow air to pass between the burning logs It is important to keep the fire off the hearth and to allow the ashes to collect beneath the fire thereby forming a layer of additional heat...

Страница 24: ...six 6 months after installation HEAT N GLO shall at its option replace or repair the Glass Doors and any electrical components if operation is faulty This does not include Glass panels broken during...

Отзывы: