Heat & Glo 6000TR-OAK Скачать руководство пользователя страница 28

Heat & Glo  •  6000TR-OAK, 6000TR-OAK-IPI  •  383-901  Rev. K  •   5/06

32

Step 10.  Finishing

Figure 38 shows the minimum vertical and corresponding

maximum horizontal dimensions of fireplace mantels or other

combustible projections above the top front edge of the

fireplace. See Figures 2 and 3 for other fireplace clearances.
Only non-combustible materials may be used to cover the

black fireplace front.

WARNING: WHEN FINISHING THE FIREPLACE,

NEVER OBSTRUCT OR MODIFY THE AIR IN-

LET/OUTLET GRILLES IN ANY MANNER.

!

Figure 38.

Minimum Vertical and Maximum Horizontal

Dimensions of Combustibles above Fireplace

CAUTION: IF JOINTS BETWEEN THE FINISHED WALLS

AND THE FIREPLACE SURROUND (TOP AND SIDES)

ARE SEALED, A 300° F. MINIMUM SEALANT MATE-

RIAL MUST BE USED.  THESE JOINTS ARE NOT RE-

QUIRED TO BE SEALED. ONLY NON-COMBUSTIBLE

MATERIAL (USING 300° F. MINIMUM ADHESIVE, IF

NEEDED) CAN BE APPLIED AS FACING TO THE FIRE-

PLACE SURROUND. SEE THE DIAGRAM BELOW.

Hearth Extensions

A hearth extension may be desirable for aesthetic reasons.

However, ANSI or CAN/CGA testing standards 

do not

 require

hearth extensions for gas fireplace appliances.

Figure 39   Sealant Material

0”

FINISH WALL MATERIAL MAY BE 

COMBUSTIBLE - TOP AND SIDES

0”

0”

NON-COMBUSTIBLE

BOARD

HIGH TEMPERATURE (300

0

F / 149

0

C MIN.)

TOP & SIDE SEAL JOINT

Note:

 There are 3 metal tabs holding the non-combustible

board in place for shipping. These tabs are to be cut off or

bent back before finishing around the fireplace front.

TOP FRONT EDGE OF FIREPLACE

1”

4”

9”

10”

11”

1”

2-1/2”

12”

13”

14”

15”

16”

17”

18”

31”

TO CEILING

9”

10”

11”

12”

8”

7”

6”

5”

4”

3”

Содержание 6000TR-OAK

Страница 1: ...the rating plate This appliance is not convertible for use with other gases unless a certified kit is used Please contact your Heat Glo dealer with any questions or concerns For the number of your ne...

Страница 2: ...fireplace front READ and UNDERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the...

Страница 3: ...tep 3 Installing the Vent System 15 A Vent System Approvals 15 B Installing Vent Components 22 C Vent Termination 25 Step 4 Positioning Leveling and Securing the Fireplace 27 Step 5 Installing the Opt...

Страница 4: ...cordance with local codes or in the absence of local codes with the National Electric Code ANSI NFPA No 70 in the United States or to the CSAC22 1 Canadian Electric Code in Canada These models may be...

Страница 5: ...read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas inspector of the side wall horizontally vented gas f...

Страница 6: ...to ensure maximum safety and benefit Failure to follow these instructions will void the owner s warranty and may present a fire hazard The Heat Glo Warranty will be voided by and Heat Glo disclaims an...

Страница 7: ...S LINE ACCESS ELECTRICAL ACCESS GAS CONTROLS RATING PLATE AND LABELS TRIM DOOR HOOD TOP STANDOFFS 41 1040mm 38 965mm 36 1 8 916mm 25 1 4 642mm 34 5 8 879mm 8 203mm VENT COLLARS ELECTRICAL ACCESS 26 7...

Страница 8: ...eplace Chase A chase is a vertical box like structure built to enclose the gas fireplace and or its vent system Vertical vents that run on the outside of a building may be but are not required to be i...

Страница 9: ...ing reference dimensions CAUTION MEASURE FIREPLACE DIMENSIONS AND VERIFY FRAMING METHODS AND WALL COVERING DETAILS BEFORE FRAMING 1 2 CLEARANCE FROM BACK OF FIREPLACE TO COMBUSTIBLE 0 CLEARANCE TO FRA...

Страница 10: ...irect Vent Component Specifications 5 inch inner pipe 8 inch outer pipe NOTE PIPES OVERLAP 1 1 4 INCHESAT EACH JOINT DVP90ST 12 9 16 11 1 4 7 1 4 1 1 4 TYP 1 2 TYP 8 9 16 DVP36 DVP48 48 24 36 4 6 DVP4...

Страница 11: ...guration used Identifying Vent Components The vent systems installed on this gas fireplace may in clude one two or three 90 elbow assemblies The rela tionships of vertical rise to horizontal run in ve...

Страница 12: ...a 1 4 nut driver by removing the four screws securing it in place see Figure 7 Figure 8 Flue Restrictor BREAK HERE Figure 7 EXHAUST SHIELD FLUE RESTRICTOR 2 Break the Flue Restrictor into two pieces...

Страница 13: ...o find the appropriate position to set the Flue Restrictor see Figure 9 1 2 3 4 5 SETTINGS 1 2 3 4 5 Figure 10 4 Center the Flue Restrictor on vent and secure in place by using two self tapping screws...

Страница 14: ...rance Figure 12 Venting with One 90 Elbow VENTING WITH ONE 1 90 ELBOW VENTING WITH ONE 1 90 ELBOW V FT H FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX...

Страница 15: ...10 MAX 3 1m 3 MIN 914 mm 6 MAX 1 86 m 15 MAX 4 65m 4 MIN 1 22 m 8 MAX 2 48 m 20 MAX 6 2m V H H1 40 MAX 12 4 m H 8 MAX 2 48 m H H1 20 MAX 6 2m Figure 15 Venting with Two 90 Elbows VENTING WITH TWO 2 90...

Страница 16: ...0 MAX 3 1m 3 MIN 914mm 6 MAX 1 86m 15 MAX 4 65m 4 MIN 1 22m 8 MAX 2 48m 20 MAX 6 2m V H H1 H2 40 MAX 12 4 m H 8 MAX 2 48 m H H1 H2 20 MAX 6 2 m V H H H1 H2 1 MIN 305mm 2 MAX 610mm 5 MAX 1 52m 2 MIN 61...

Страница 17: ...610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m NOTE H H1 20 MAX 6 2m V V1 H H1 40 MAX 12 4m V V1 FT H H1 FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65...

Страница 18: ...VENT SYSTEM IS AT TACHED TO THE TOP STARTING COLLARS WARNING FAILURE TO REMOVE INSULATION IN THE SET OF COLLARS YOU ARE USING COULD CAUSE A FIRE WARNING YOUMUSTLEAVETHEINSULATION IN PLACE IN THE SET...

Страница 19: ...ow and positioned so that it creates a 1 2 inch airspace between the shield and the combustible surface See Figure 21 COMBUSTIBLE SURFACE DIRECTION UP HEAT SHIELD 90 ELBOW 0 Figure 22 If the combustib...

Страница 20: ...STOP HEAT SHIELD NOTE There must be NO INSULATION or other combustibles inside the framed firestop opening 10 12 INTERIOR WALL SHIELD For Vertical Runs One ceiling firestop is REQUIRED at the hole in...

Страница 21: ...ramed firestop opening Figure 28 Trapezoid Termination Cap C Vent Termination Refer to Cinch Pipe and Termination Cap installation in structions Horizontal Termination The termination kit should pass...

Страница 22: ...open only on one side and with an overhang are permitted with the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be 3 feet minimum between termination caps 2 All mechanic...

Страница 23: ...ening To seal the roof hole and to divert rain and snow from the vent system Attach a flashing to the roof using nails and use a non hardening mastic around the edges of the flashing base where it mee...

Страница 24: ...steps Step 6 The Gas Control Systems WARNING THIS UNIT IS NOT FOR USE WITH SOLID FUEL Two types of gas control systems are used with these models Standing Pilot Ignition and Intermittent Pilot Igniti...

Страница 25: ...ustible insulation to pre vent cold air infiltration Open the fireplace lower grille insert the gas supply line throughthegaslinehole andconnectittotheshut offvalve When attaching the pipe support the...

Страница 26: ...all Switch Position the wall switch in the desired position on a wall Run a maximum of 25 feet 7 8 m or less length of 18 A W G minimum wire and connect it to the fireplace ON OFF switch pigtails WARN...

Страница 27: ...ck to black The fireplace can be used as necessary Once power 110 VAC is re stored disconnect red and black wire leads to extend bat tery life Optional Accessories Optional remote control kits require...

Страница 28: ...S ARE SEALED A 300 F MINIMUM SEALANT MATE RIAL MUST BE USED THESE JOINTS ARE NOT RE QUIRED TO BE SEALED ONLY NON COMBUSTIBLE MATERIAL USING 300 F MINIMUM ADHESIVE IF NEEDED CAN BE APPLIED AS FACING TO...

Страница 29: ...over ports Care should be taken not to cover the lighting trail of ports from back to front When placing Glowing embers onto the burner care should be taken so that the ports are not covered Place th...

Страница 30: ...minimum vertical vent run see Figure 43 If your installation has more than the minimum required vertical vent length adjustment of the air shutter may be necessary to obtain optimal flame appearance...

Страница 31: ...al check of your fireplace s flame patterns Make sure the flames are steady not lifting or floating See Figure 44 The flame sensor IPI or thermopile thermocouple standing pilot tips should be covered...

Отзывы: