background image

5

       WARNING:   

Rework  worksheet, add-

ing    the    space    of    the    adjoining
unconfined  space.  The  combined  spaces
must   have  enough  fresh air  to supply  all
appliances  in  both  spaces.

AIR  FOR  COMBUSTION
AND  VENTILATION

Continued
VENTILATION  AIR

Ventilation  Air  From  Inside Building
This  fresh  air  would  come  from  an
adjoining    unconfined    space.    When
ventilating   to  an  adjoining  unconfined
space, you  must  provide  two permanent
openings: one  within  12

"

  of  the  ceiling

and  one  within  12

"

  of  the  floor  on  the

wall  connecting  the  two  spaces  (see
options 1 and 2,  Figure  2). You  can  also
remove  door  into  adjoining  room (see
option 3, Figure 2). 

Follow  the  National

Fuel  Gas  Code  NFPA 54/ANS Z223.1.
Section  5.3,  Air  for  Combustion  and
Ve n t i l a t i o n    f o r     r e q u i r e d   s i z e   o f
ventilation  grills  or  ducts

 Example:
 Gas  water  heater          44,000        Btu/Hr
 Vent  free  heater    +      10,000        Btu/Hr
 Total                         =      54,000       Btu/Hr

If  the actual  Btu/Hr  used  is  less  than  the  maximum  Btu/Hr  the  space  can  support, the  space  is  an
unconfined  space. You  will  need  no  additional  fresh  air  ventilation.

3. Add  the  Btu/Hr of all fuel burning appliances in the space.

     Vent-free heater                                                       Btu/Hr
     Gas water heater*                                                         Btu/Hr
     Gas furnace

                                      Btu/Hr

     Vented gas heater                                                   Btu/Hr
     Gas Fireplace logs

                                        Btu/Hr

     Other gas appliances* +                                         Btu/Hr
    Total                                =                                        Btu/Hr

    *Do  not  include  direct-vent  gas  appliances. Direct-vent  draws  combustion  air  from  the  outdoors  and
       vents to the outdoors.

4. Compare  the  maximum  Btu/Hr  the  space  can  support  with  the  actual amount of Btu/Hr used.

Btu/Hr (maximum the space can support)

                 

Btu/Hr (actual amount of Btu/Hr used)

Example :  51,200 Btu/Hr(maximum the space can support)

                           54,000 Btu/Hr(actual amount of Btu/Hr used)
The  space  in  the  above  example  is  a  confined  space  because  the  actual  Btu/Hr  used  is  more  than  the
maximum  Btu/Hr  the  space  can  support.
You  must  provide  additional  fresh  air.  Your  options  are  as  follows:
A.  Rework  worksheet, adding  the  space  of  an  adjoining  room. If  the  extra  space  provides  an  unconfined
space, remove  door  to  adjoining  room  or  add  ventilation  grills   between  rooms. 

See  Ventilation  Air  From

Inside  Building, page 5.
B.  Vent  room  directly  to  the  outdoors. See  

Ventilation  Air  From  Outdoors, page 6 .

C.  Install  a  lower  Btu/Hr  heater, if  lower  Btu/Hr  size  makes  room  unconfined.

Figure  2 -Ventilation  Air  from  Inside  Building

Содержание HB06ML-1

Страница 1: ...structions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or gas supplier ImportantSafetyInformation 2 Product Features 3 ProperVentilation FreshAir 4 Installation 6 OperatingYour Heater 10 Cleaning Maintenance 13 Trouble Shooting 14 Specifications 17 Parts List 19 Warranty information 24 WARNING Thi...

Страница 2: ...ce Never place any objects on the heater Due to high temperatures heater s h o u l d b e k e p t o u t o f traffic and away from furniture and draperies Surface of heater becomes very hot when running heater Keep children and adults away from hot surface to avoid burns or clothing ignition Heater will remain hot for a time after shut down Allow surface to cool before touching Carefully supervise y...

Страница 3: ...that has complied with all the requirements of the authority having jurisdiction State of Massachsetts The installation must be made by a licensed plumber or gas fitter in the Commonwealth of Massachusetts Sellers of unvented propane or natural gas fired supplemental room heaters shall provide to each purchaser a copy of 527 CMR 30 upon sale of the unit In the state of Massachusetts unvented propa...

Страница 4: ...described in the National Fuel Gas Code ANS Z223 1 Section 5 3 or applicable local codes Unusually Tight Construction The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation However in buildings of unusually tight construction you must provide additional fresh air Unusually tight construction is defined as construction where a walls and ceilings expo...

Страница 5: ...dd the Btu Hr of all fuel burning appliances in the space Vent free heater Btu Hr Gas water heater Btu Hr Gas furnace Btu Hr Vented gas heater Btu Hr Gas Fireplace logs Btu Hr Other gas appliances Btu Hr Total Btu Hr Do not include direct vent gas appliances Direct vent draws combustion air from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actu...

Страница 6: ...G HEATER This heater is designed to be mounted on a wall For convenience and efficiency install heater where there is an easy access for operation inspection and service in coldest part of room INSTALLATION CAUTION If you install the heater in a home garage heater pilot and burner must be at least 18 inches above floor locate heater where moving vehicle will not hit it CAUTION This heater creates ...

Страница 7: ...een studs or to solid walls concrete or masonry Decide which method better suits your needs Either method will provide a secure hold for the mounting bracket Marking Screw Locations 1 Tape mounting bracket to wall where heater will be located Make sure mounting bracket is level 2 Mark screw locations on wall see Figure 8 Note Only mark last hole on each end of mounting bracket Insert mounting scre...

Страница 8: ...gs 5 Place mounting bracket onto wall Line up last hole on each end of bracket with wall anchors 6 Insert mounting screws through bracket and into wall anchors 7 Tighten screws until mounting bracket is firmly fastened to wall Placing Heater On Mounting Bracket 1 Locate two horizontal slots on back panel of heater see Figure 11 2 Place heater onto mounting bracket Slide horizontal slots onto stand...

Страница 9: ...d pressure regulator with wrench when connecting it to gas piping and or fittings CAUTION Use pipe joint sealant that is resistant to liquid petroleum LP gas Figure 14 Gas Connection The installer must supply an external regulator The external regulator will reduce incoming gas pressure You must reduce incoming gas pressure to between 11 and 13 inches of water If you do not reduce incoming gas pre...

Страница 10: ...lve to control valve see Figure 16 Apply mixture of liquid soap and water to gas joints Bubbles forming show a leak 5 Correct all leaks at once 6 Light heater see Operating Heater pages 10 and 11 for non thermostat models or page 12 for thermostat model Check the rest of the internal joints for leaks 7 Turn off heater see To Turn Off Gas to Appliance page 11 for non thermostat models or page 12 fo...

Страница 11: ...rtially press down the control knob slightly and rotate counterclockwise Release the downward pressure on the knob while continuing to turn until the knob locks at the desired set ting position Do not operate between locked positions Set control knob to desired heating position NOTE Both HIGH and LOW are locked positions You must press in control knob before turning it from these positions TO TURN...

Страница 12: ...t refer to Troubleshooting pages 14 through 16 Also contact a qualified service person or gas supplier for repairs Until repairs are made light pilot with match To light pilot with match see Manual Lighting Procedure 7 Keep control knob pressed in for 30 seconds after lighting pilot After 30 seconds release control knob If control knob does not pop up when released contact a qualified service pers...

Страница 13: ...soap and water mixture Wipe the cabinet to remove dust INSPECTING BURNER Check pilot flame pattern and burner flame pattern often PILOT FLAME PATTERN Figure 21 shows a correct pilot flame pattern Figure 22 shows an incorrect pilot flame pattern The incorrect pilot flame is not touching thermocouple This will cause the thermocouple to cool When the thermocouple cools the heater will shut down If pi...

Страница 14: ...g is not correct 6 Control knob not in PILOT position 7 Depleted gas supply 1 Control knob is not fully pressed in 2 Control knob is not pressed in long enough 3 Equipment shutoff valve is not fully open 4 Thermocouple connection is loose at control valve 5 Thermocouple damaged 6 Control valve damaged REMEDY 1 Replace ignitor 2 Replace ignitor 3 Reconnect ignitor cable 4 Free ignitor cable if pinc...

Страница 15: ...ing while heating or contracting while cooling 1 When heated the vapors from furniture polish wax carpet cleaners etc turn into white powder residue REMEDY 1 Clean burner orifice see Cleaning and Maintenance Page 13 or replace burner orifice 2 Replace burner orifice 3 Contact local propane LPgascompany 1 Contact local propane LP gascompany 2 Clean burner see Cleaning and Maintenance Page 13 or rep...

Страница 16: ...ne LP gas company 3 Clean ODS pilot see Cleaning Page 13 1 Locate and correct all leaks see Checking Gas Connections Page 10 2 Replace control valve 1 Take apart gas tubing and remove foreign matter 2 Locate and correct all leaks see Checking Gas Connections Page 10 1 Refer to Air for Combustion and Ventilation requirements Page 4 POSSIBLE CAUSE 1 Heater is burning vapors from paint hair spray glu...

Страница 17: ... from whom you purchased this product If they are unable to supply original replacement part s call the num ber on the front of this manual When contacting your dealer or HearthRite have ready your name your address model and serial numbers of your heater how heater was malfunction ing type of gas used propane LP or natural gas purchase date warranty card Usually we will ask you to return the defe...

Страница 18: ...1 8 ILLUSTRATED PARTS BREAKDOWN HB06ML ...

Страница 19: ...084 03E ML060 02 ML083 03 MB28001 ML070 12E ML071 02 PARTS AVAILABLE NOT SHOWN DESCRIPTION Cabinet Assembly Lower Front Panel Assembly Reflector Unit Glass Upper Glass Retainer Lower Glass Retainer Self Tapping Screw Control Valve Ignitor Line Control Valve Fixed Nut Control Knob Assembly Pressure Regulator Self Locking Screw Pressure Tap Main Inlet Tube Assembly ODS Line Assembly Gas Outlet Tube ...

Страница 20: ...2 0 ILLUSTRATED PARTS BREAKDOWN HB10ML ...

Страница 21: ... ML084 03E ML060 02 ML083 03 MB28001 ML070 14E ML071 02 PARTS AVAILABLE NOT SHOWN DESCRIPTION Cabinet Assembly Lower Front Panel Assembly Reflector Unit Glass Upper Glass Retainer Lower Glass Retainer Self Tapping Screw Control Valve Ignitor Line Control Valve Fixed Nut Control Knob Assembly Pressure Regulator Self Locking Screw Main Inlet Tube Assembly ODS Line Assembly Gas Outlet Tube Assembly B...

Страница 22: ...2 2 ILLUSTRATED PARTS BREAKDOWN HB10TL ...

Страница 23: ...83 03 MB28001 ML070 30E ML071 02 ML065 01 PARTS AVAILABLE NOT SHOWN DESCRIPTION Cabinet Assembly Lower Front Panel Assembly Reflector Unit Glass Upper Glass Retainer Lower Glass Retainer Self Tapping Screw SIT Thermostat Valve Assembly Thermostat Valve Base Bracket Nut Screws Grill Self Locking Screw Middle Panel Pressure Regulator Ignitor Line Mounting Bracket Main Inlet Tube Assembly ODS Line As...

Страница 24: ...2 4 ...

Отзывы: