Hearth Technologies Royal Fireplaces R-5500RHT Скачать руководство пользователя страница 19

21

For Vertical Terminations -

 To locate the vent and install

the vent sections:
• Locate and mark the vent centerpoint on the underside

of the roof, and drive a nail through the centerpoint.

• Make the outline of the roof hole around the centerpoint

nail.

• The size of the roof hole framing dimensions depend on the

pitch of the roof. There 

MUST BE

 a 1-inch (25.4mm) clear-

ance from the vertical vent pipe to combustible materials.

• Mark the roof hole accordingly.

• Cover the opening of the installed vent pipes.

• Cut and frame the roof hole.

• Use framing lumber the same size as the roof rafters

and install the frame securely. Flashing anchored to the

frame must withstand heavy winds.

• Continue to install concentric vent sections up through

the roof hole (for inside vent installations) or up past the

roof line until you reach the appropriate distance above

the roof (for outside terminations).

WARNING:  MAJOR U.S. BUILDING CODES

SPECIFY  MINIMUM  CHIMNEY  AND/OR

VENT HEIGHT ABOVE THE ROOF TOP. THESE MIN-

IMUM HEIGHTS ARE NECESSARY IN THE INTER-

EST OF SAFETY. SEE FIGURE 22 FOR MINIMUM

HEIGHTS, PROVIDED THE TERMINATION CAP IS

AT LEAST TWO (2) FEET FROM A VERTICAL WALL

AND 2-FEET BELOW A HORIZONTAL OVERHANG.

NOTE: This also pertains to vertical vent systems in-

stalled on the outside of the building.

!

Roof Pitch

H (min.) ft.

flat to 6/12

1.0

6/12 to 7/12

1.25

over 7/12 to 8/12

1.5

over 8/12 to 9/12

2.0

over 9/12 to 10/12

2.5

over 10/12 to 11/12

3.25

over 11/12 to 12/12

4.0

over 12/12 to 14/12

5.0

over 14/12 to 16/12

6.0

over 16/12 to 18/12

7.0

over 18/12 to 20/12

7.5

over 20/12 to 21/12

8.0

Figure 22.   Minimum Height from Roof to

                   Lowest Discharge Opening

To seal the roof hole, and to divert rain and snow from the

vent system:
• Attach a flashing to the roof using nails, and use a non-

hardening mastic around the edges of the flashing base

where it meets the roof.

• Attach a storm collar over the flashing joint to form a

water-tight seal. Place non-hardening mastic around the

joint, between the storm collar and the vertical pipe.

• Slide the termination cap over the end of the vent pipe

and rotate the pipe clockwise 1/4 turn.

HORIZONTAL

OVERHANG

VERTICAL

WALL

TERMINATION

CAP

12

X

ROOF PITCH

IS  X/ 12

LOWEST 

DISCHARGE 

OPENING

H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING

2 FT.

MIN.

2 FT. MIN.

Содержание Royal Fireplaces R-5500RHT

Страница 1: ...PPLIANCE FOR FUTURE REFERENCE 1 This appliance may be installed in an af termarket permanentlylocated manufac tured mobile home wherenotprohibited by local codes 2 Thisapplianceisonlyforusewiththetype...

Страница 2: ...he installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the first firing of the fireplace READ the Using Your Firepla...

Страница 3: ...t System 11 A Vent System Approvals 11 B Installing Vent Components 15 C Vent Termination 19 Step 4 Positioning Leveling and Securing the Fireplace 22 Step 5 The Gas Control System 22 Step 6 The Gas S...

Страница 4: ...ates or to the CSAC22 1 Canadian Electric Code in Canada This model may be installed in a bedroom or bed sitting room in the U S A and Canada 1Approvals and Codes High Altitude Installations U L Liste...

Страница 5: ...lure to follow these instructions will void the own er s warranty and may present a fire hazard The Hearth Technologies Warranty will be voided by and Hearth Technologies disclaims any responsibility...

Страница 6: ...of the R 5500RHT 41 1043mm 38 965mm 36 1 8 916mm 25 642mm 34 5 8 879mm ELECTRICAL ACCESS 10 259mm 3 90mm GAS LINE ACCESS 2 1 8 55mm 6 7 8 174mm 14 362mm 8 5 8 219mm VENT COLLARS 21 1 2 548mm 11 5 8 2...

Страница 7: ...rance diagrams on pages 20 and 21 in this manual The distance from the unit to combustible construction is to be measured from the unit outer wrap surface to the combustible construction NOT from the...

Страница 8: ...r pipe DV 36D 5 3 4 146mm 8 3 4 222mm 11 3 4 298mm DV 48D 7 3 8 187mm 6 5 32 156mm 11 5 8 295mm 8 5 8 220mm 8 1 2 216mm 6 7 16 164mm 11 1 16 281mm 6 1 2 165mm 8 1 2 216mm 5 1 16 129mm 8 5 8 220mm 35 3...

Страница 9: ...d should be used in conjunction with this Installers Guide The flame and ember appear ance may vary based on the type of fuel burned and the venting configuration used Terminations Kits HORIZONTAL TER...

Страница 10: ...bow NOTE IF A 90o ELBOW IS FIRST AT TACHED TO THE UNIT THE MAXIMUM HORIZONTAL RUN IS 3 FEET 914mm VENTING WITH ONE 1 90 ELBOW V FT H FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 M...

Страница 11: ...MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m V H H1 40 MAX 12 4m 20 MAX 6 2m V V1 H 40 MAX 12 4m Figure 8 Venting with Two 90 Elbows NOTE There MUST b...

Страница 12: ...914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m NOTE H H1 20 MAX 6 2m V V1 H H1 40 MAX 12 4m VENTING WITH THREE 3 90 ELBOWS V FT H H1 FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914Amm 15 MAX...

Страница 13: ...s When the internal beads of each 8 5 8 inch 219mm outer pipe line up rotate the pipe section clockwise about one quarter 1 4 turn Theventpipeisnowlockedtogether WARNING ENSURE THAT THE FIBER GLASS RO...

Страница 14: ...ay be installed and rotated to any point around the preceding component s vertical axis If an el bow does not end up in a locked position with the pre ceding component attach with a minimum of two 2 s...

Страница 15: ...mbustible wall To install firestops for horizontal runs that pass through either interior or exterior walls Cut a 12 inch by 12 inch 305mm X 305mm hole through the wall NOTE The center of the hole is...

Страница 16: ...11 inch 280mm X 280mm hole through the ceiling using the centerpoint previously marked Frame the hole with framing lumber the same size as the ceiling joists Figure 18 Ceiling Firestop Ceiling Side If...

Страница 17: ...of the wall firestop to secure the vent pipe in place For trapezoidal cap termination kits Using screws secure the cap to the exterior wall through the flanges in the cap Figure 20 Round Trapezoid Te...

Страница 18: ...or that may be opened C 9 U S A 12 Canada clearance to permanently closed window D 18 vertical clearance to ventilated soffit located above the termi nal within a horizontal distance of 2 feet 60 cm f...

Страница 19: ...EE FIGURE 22 FOR MINIMUM HEIGHTS PROVIDED THE TERMINATION CAP IS AT LEAST TWO 2 FEET FROMA VERTICAL WALL AND 2 FEET BELOW A HORIZONTAL OVERHANG NOTE This also pertains to vertical vent systems in stal...

Страница 20: ...ition level and secure the fireplace Figure 23 Proper Positioning Leveling and Securing of a Fireplace Figure 24 Gas Control System STANDING PILOT Step 5 The Gas Control System WARNING THIS UNIT IS NO...

Страница 21: ...nnect it to the shut off valve When attaching the pipe support the control so that the lines are not bent or torn After the gas line installation is complete use a soap solution to carefully check all...

Страница 22: ...itch in the desired position on a wall Run a maximum of 25 feet 7 8 m or less length of 18 A W G minimum wire and connect it to the fireplace ON OFF switch pigtails WARNING DO NOT CONNECT 110 120 VAC...

Страница 23: ...ontal Dimensions of Combustibles above Fireplace CAUTION IF JOINTS BETWEEN THE FINISHED WALLS AND THE FIREPLACE SURROUND TOP AND SIDES ARE SEALED A 300 F MINIMUM SEALANT MATE RIAL MUST BE USED THESE J...

Страница 24: ...sooting occurs the logs might need to be repositioned slightly to avoid excessive flame impingement Step 10 Installing Trim Logs and Ember Material Placing the Ember Material Ember material is shipped...

Страница 25: ...ate normally Subsequent lightings of the fireplace will not require this purging of air from the gas supply lines unless the gas valve has been turned to the OFF position in which case the air would h...

Страница 26: ...s Frequency Once annually By Qualified service technician Task Brush or vacuum the control compartment fireplace logs and burner areas surrounding the logs Checking Flame Patterns Flame Height Frequen...