I. Prefabricated Metal Chimney

The chimney can be new or existing, masonry 

or prefabricated and must meet the following 

minimum requirements:

•  Must be minimum 6 inch (152mm) inside diameter of 

high temperature chimney listed to 

UL 103 HT (2100°F) 

or ULC-S628

.

•  Must use components required by the manufacturer 

for installation.

•  Must maintain clearances required by the manufacturer 

for installation.

•  Refer to manufacturers instructions for installation

•  This insert is listed to 

ASTM E 1509-12 Standard

 and 

is approved for installation into listed factory-built zero 

clearance fireplaces listed to 

UL 127

 conforming to the 

following specifications and instructions:

• 

The original factory-built clearance fireplace chimney 

cap must be re-installed after installing the approved 

chimney liner meeting type 

UL 103 HT requirements 

(2100°F) per UL 1777

.

•  If the chimney is not listed as meeting HT requirements, 

or if the factory built fireplace was tested prior to 1998, 

a full height listed chimney liner must be installed from 

the appliance flue collar to the chimney top.

• 

The liner must be securely attached to the insert flue 

collar and the chimney top. 

• 

The air flow of the factory-built zero-clearance fireplace 

system must not be altered. The flue liner top support 

attachment must not reduce the air flow for the existing 

air-cooled chimney system.

NOTE:

 It is necessary to permanently seal any opening 

between the masonry of the fireplace and the 

facing masonry.

•  No dilution air is allowed to enter the chimney.

a. 

Secure the fireplace damper in the open position. If 

this cannot be accomplished, it will be necessary to 

remove the damper

b.  Seal damper area of chimney around chimney 

connector with a high temperature sealant or seal 

insert against the face of the fireplace.

c.  Both methods must be removable and replaceable 

for cleaning and re-installation.

H. Installation into a Masonry Fireplace

All modifications that can be made to a Factory Built 

Fireplace can be made to a Masonry Fireplace.

In addition DO NOT remove any brick or mortar from the 

existing fireplace.

NOTICE:

 In Canada when using a factory-built 

chimney it must be safety listed, 

Type 

UL103 HT (2100°F) [1149°C] CLASS 

“A” or conforming to CAN/ULC-S629M, 

STANDARD FOR 650°C FACTORY-

BUILT CHIMNEYS

.

• 

Removing floor of fireplace must not weaken 

structure of firebox or reduce protection for 

combustible materials.

•  Final approval of this installation type is 

contingent upon the appropriate local authority 

having jurisdiction.

WARNING

Risk of Fire!

Follow venting manufacturer’s clearances and 

instructions when installing venting system.

WARNING

Содержание Quadra-Fire CB1200

Страница 1: ...restrictions installation inspection and permits CAUTION If the information in these instructions is not followed exactly a fire could result causing property damage personal injury or death Do not s...

Страница 2: ...Install Checklist 7 3 Dimensions and Clearances A Appliance Dimensions 8 B Clearance To Combustibles UL and ULC 9 C Masonry Chimney and Fireplace Clearances 10 D Minimum Opening for Masonry ZC Firepla...

Страница 3: ...put 10 200 to 33 900 hr BTU Input 17 000 to 48 500 hr Vent Size 3 4 L or PL or 6 Hopper Capacity 75 lbs Fuel Premium Wood Pellets Weighted average LHV Low Heating Value efficiency using data collected...

Страница 4: ...ductive harm For more information go to WWW P65Warnings ca gov WARNING F Non Combustible Materials Material which will not ignite and burn composed of any combination of the following Steel Plaster Br...

Страница 5: ...stallation MUST comply with local regional state and national codes and regulations Consult insurance carrier local building inspector fire officials or authorities having jurisdiction over restrictio...

Страница 6: ...ng the installation to ensure maximum safety and benefit Follow pipe manufacturer instructions for installation and air clearance requirements Tools and building supplies normally required for install...

Страница 7: ...ng this checklist for your file That this checklist remain visible at all times on the appliance until the installation is complete Electrical 120 VAC unswitched power provided to the appliance Check...

Страница 8: ...8 in 346mm 8 3 4 in 223mm Figure 8 5 Front View with large panel set SP CB12I3350 NB or NL TOP TRIM 18 5 16 in 465mm 24 5 16 in 618mm 50 in 1270mm 33 in 838mm 10 3 8 in 264mm 21 1 4 in 539mm 21 1 4 i...

Страница 9: ...art 811 0730 is available through your dealer to be used as a floor protector for the section under the insert body only Floor protection to front and sides of insert appliance must be supplied in add...

Страница 10: ...ment for clearances for any measurement in between the maximum and the minimum height The Maximum and minimum are already calculated for you in the above table for convenience E Hearth Extension Use a...

Страница 11: ...nt of the insert and 8 inches 203mm to each side of the door opening See Thermal Resistance R value NOTE Clearances may only be reduced by means approved by the regulatory authority having jurisdictio...

Страница 12: ...replace opening the portion of the insert extending onto the hearth must be supported Manufacturer designed adjustable support kit can be ordered from your dealer The following is only one example as...

Страница 13: ...nce fireplace system must not be altered The flue liner top support attachment must not reduce the air flow for the existing air cooled chimney system NOTE It is necessary to permanently seal any open...

Страница 14: ...rts of the structure P 12 in Clearance above roof line for vertical terminations All minimum clearances are listed with an Outside Air Kit OAK installed unless otherwise noted in table below 24 in Abo...

Страница 15: ...mands of the pellet appliance but consideration must be given to the total house demand House demand may consume the air needed for the appliance It may be necessary to add additional ventilation to t...

Страница 16: ...nce TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE Negative pressure results from the imbalance of air available for the appliance to operate properly It can be strongest in lower levels of the house Cau...

Страница 17: ...n Figure 17 2 1 Locate the calculated equivalent feet of pipe on the vertical left side of the chart 2 Move to the right horizontally on the chart until you reach your altitude above sea level 3 If yo...

Страница 18: ...Fire Risk Inspection of Chimney Masonry chimney must be in good condition Meets minimum standard of NFPA 211 Factory built chimney must be a minimum 6 inch 152mm UL103 HT WARNING CAUTION Never draw o...

Страница 19: ...all or partition of combustible construction is desired the installation shall conform to CAN CSA B365 NOTE Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY Illustrations d...

Страница 20: ...ials to seal any edge to prevent furture serviceability Figure 20 1 NOTE In Canada this fireplace insert must be installed with a continuous chimney liner extending from the fireplace insert to the to...

Страница 21: ...ke into the home 1 Remove the top vent adapter from the vertical exhaust transition pipe Figures 21 1 and 21 2 2 Using a Phillips head screwdriver and two screws to attach Filler Bracket Figure 21 3 3...

Страница 22: ...piece Figure 22 1 5 Install the Rear Panel using six screws Figure 22 2 6 Install the cover plate over the top vent opening using 4 screws Figure 22 3 7 Attach the left shroud panel using eight screws...

Страница 23: ...termination cap with second hose clamp 6 Secure termination cap to outside surface 7 Secure trim ring to interior wall Flex Hose Hose Clamp Collar Assembly Trim Ring Hose Clamp Termination Cap Assemb...

Страница 24: ...1 and 8 2 D Optional Log Set Placement Instructions NOTE Due to the abrasive nature of a pellet appliance fire the logs are not covered under warranty Any placement variation other than shown here can...

Страница 25: ...t and left side curtains are shipped with the insert Figure 25 2 Figure 25 3 Figure 25 4 6 Hold side curtains in open position and lower panel set over insert setting lower edge of top panel in slot b...

Страница 26: ...h the opening in the base plate and hold the base against the wall while aligning up to the holes Attach base plate using a Phillips head screwdriver and two screws 5 Connect your thermostat wire to t...

Страница 27: ...3280 Part 24 PART NUMBER 811 0872 Spark Arrestor Cap Roof Flashing Storm Collar Joist Shield Firestop Double Wall Connector Pipe Figure 27 1 CAUTION THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR W...

Страница 28: ...28 07 22 7027 804H 8 Reference Materials A Service Maintenance List Date of Service Performed By Description of Service...

Страница 29: ...f 24 229 1100 24 Y Blower Convection 7000 537 Y 33 Control Board 3 Speed SRV7000 704 Y Fuse 8 Amp Control Box Pkg of 10 812 3780 10 Y 34 Wire Harness SRV7000 155 Y Fuse 7 Amp Junction Box Pkg of 10 81...

Страница 30: ...832 0840 Logo Quadra Fire Pkg of 10 7000 649 10 Trim Panel Set Ots Nickel 510 5220 Panel Set Large W Black Nickel Trim 33 in x 50 in SP CB12I3350 NB Bracket L Trim Pkg of 2 832 0840 Logo Quadra Fire...

Страница 31: ...31 07 22 7027 804H...

Страница 32: ...maintenance instructions included Read understand and follow these instructions for safe installation and operation Leave this manual with party responsible for use and operation of this appliance We...

Отзывы: