Hearth & Home Technologies • PIER-DV36IN, ST-DV36IN Installation Manual • 2658-980 Rev. C • 4/22
58
Combustible Mantels
C. Mantel and Wall Projections
WARNING! Risk of Fire!
Comply with all minimum clear-
ances as specified.
Mantel MUST be fastened to wall
with no gaps.
• Framing closer than the minimums listed must be
constructed entirely of non-combustible materials (i.e.,
steel studs, concrete board, etc.).
• No gaps allowed between the wall and the bottom of the
mantel.
•
Combustible mantel legs and wall projections may be
applied over the non-combustible board supplied with
the appliance. Follow guidelines as shown in the figures
below for mantels, mantel legs and wall projections.
Note:
Measurement is taken from top/side of the
opening, NOT the top/side of the fireplace.
If installing a television (TV) above the appliance, see
Section 2.B.
B. Installing a Television
Note:
All
measurements
in inches.
TO CEILING
5
10
11
12
2-1/2
13
14
15
16
17
18
19
31
9
10
11
12
8
7
6
5
4
3
25
18
MAX.
MIN.
MEASUREMENT FROM FIREPLACE
OPENING TO BOTTOM OF
APPLIANCE= 33-1/2 IN.
ST-DV36IN Combustible Mantel
Figure 10.4 Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles
PIER-DV36IN Combustible Mantel
Note:
All
measurements
in inches.
TO CEILING
5
10
11
12
1
13
14
15
16
17
18
19
31
9
10
11
12
8
7
6
5
4
3
25
18
MAX.
MIN.
MEASUREMENT FROM FIREPLACE
OPENING TO BOTTOM OF
APPLIANCE= 33-1/2 IN.
Figure 10.3 Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles