Hearth & Home Technologies • DV3732, DV3732L, DV4236 Installation Manual • 2355-980 Rev. H • 3/16
46
10
10
Finishing
A. Facing Material
• Metal front faces may be covered with non-combustible
materials only.
• Facing and/or
fi
nishing materials must not interfere with
air
fl
ow through louvers, operation of louvers or doors,
or access for service.
• Facing and/or
fi
nishing materials must never overhang
into the glass opening.
• Observe all clearances when applying combustible
materials.
• Seal joints between the
fi
nished wall and appliance top
using a 300 ºF minimum sealant. Refer to Figure 10.2.
WARNING! Risk of Fire! DO NOT
apply combustible
materials beyond the minimum clearances. Comply with
all minimum clearances to combustibles as speci
fi
ed in
this manual. Overlapping materials could ignite and will
interfere with proper operation of doors and louvers.
Figure 10.1 Non-combustible Facing Diagram - DV3732
0 IN.
0 IN.
0 IN.
SHEETROCK/FINISH WALL MATERIAL UP TO 1/2 IN. THICK
MAY BE COMBUSTIBLE - TOP AND SIDES
Figure 10.2 Non-combustible Facing Diagram - DV4236
0 IN.
3-1/2 IN.
SHEETROCK/FINISH WALL MATERIAL UP TO 1/2 IN. THICK
MAY BE COMBUSTIBLE - TOP AND SIDES
0 IN.
= NON-COMBUSTIBLE ZONE
HIGH TEMPERATURE SEALANT (300° F/149° C MIN.) SEAL JOINT