Hearth and Home Technologies BEK Скачать руководство пользователя страница 8

Hearth & Home Technologies Inc. • Cinch Pipe & Term Caps • 4033-900 Rev K • 05/05

8

Secure the Vent Sections

Vertical sections of pipe must be supported every 8 ft after 
the 25 ft maximum unsupported rise. The vent support or 
plumber’s strap (spaced 120° apart) may be used to do this 
(see Figures 2.12 and 2.13).

Horizontal sections of vent must be supported every 5 ft with 
a vent support or plumber’s strap.

D. Disassemble Vent Sections

To disassemble any two pieces of pipe, rotate either section 
(see Figure 2.14), so that the seams on both pipe sections 
are aligned (see Figure 2.15). They can then be carefully 
pulled apart.

Figure 2.12  Securing Vertical Pipe Sections

Figure 2.13  Securing Horizontal Pipe Sections

Fire Risk
Explosion Risk
Asphyxiation Risk

Use vent run supports per installation 
instructions.
Connect vent sections per installation 
instructions
•  Maintain all clearances to combustibles.
•  Do NOT allow vent to sag below 

connection point to appliance.

•  Maintain specifi ed slope (if required).

Improper support may allow vent to sag or 
separate.

WARNING

Figure 2.14  Rotate Seams for Disassembly

Figure 2.15  Align and Disassembly Vent Sections

Содержание BEK

Страница 1: ...e assembly instructions See the appliance installation instructions for con guration of vent assembly and clearances to pipe If DVP AD adapters are used off the top of the appliance the termination he...

Страница 2: ...0ST 90 elbow DVP WS wall shield with heat shield DVP TRAP1 termination cap with telescoping ue and one fastener pack DVP TRAPK2 Vent kit containing DVP90ST 90 elbow DVP WS wall shield with heat shield...

Страница 3: ...in 6 in Slip Section Vent Pipe to be used with another piece of pipe DVP12A 3 in 12 in Slip Section Vent Pipe to be used with another piece of pipe DVP12MI 12 in Vent Pipe non unitized can be cut to l...

Страница 4: ...0 7 8 in 6 3 4 in to 10 3 4 in GNTC50 5 in to 6 3 4 in 4 7 8 in to 6 5 8 in 7 3 8 in to 11 3 8 in 7 3 8 in to 11 3 8 in Designer 4 in to 5 3 4 in 5 3 4 in to 7 1 2 in 6 3 8 in to 10 3 8 in 8 1 8 in to...

Страница 5: ...urations 2 Installing Vent Pipe B Penetrating a Wall Wherever a combustible wall is penetrated the hole must be framed with an interior wall shield DVP WS as shown in Figures 2 3 2 4 This shield maint...

Страница 6: ...he pipe section into the appliance collar until all the lances see Fig ure 2 5 have snapped in place Tug slightly on the section to con rm it has completely locked into place Assemble Pipe Sections In...

Страница 7: ...an then be attached by tting another pipe section to it and snapping it together as normal Assemble Slip Sections The outer ue of the slip section should slide over the outer ue of the pipe section an...

Страница 8: ...e either section see Figure 2 14 so that the seams on both pipe sections are aligned see Figure 2 15 They can then be carefully pulled apart Figure 2 12 Securing Vertical Pipe Sections Figure 2 13 Sec...

Страница 9: ...e cap in the same manner See Figure 2 16 If the wall thickness does not allow the required 1 1 2 in heat shield overlap an extended heat shield must be used The extended heat shield will need to be cu...

Страница 10: ...17 Installing Firestop Spacer 3 fasteners per side Attic insulation shield installed below ceiling Attic insulation shield installed above ceiling Bend tabs in around pipe Figure 2 18 Installing the A...

Страница 11: ...rom roof to lowest discharge opening 24 in min 610 mm Roof Pitch H Min Ft Roof Pitch H Min Ft Flat to 6 12 1 0 Over 11 12 to 12 12 4 0 6 12 to 7 12 1 25 Over 12 12 to 14 12 5 0 Over 7 12 to 8 12 1 5 O...

Страница 12: ...ded through the brackets and tighten nut to complete the storm collar assembly see Figure 2 22 Make sure the collar is tight against the pipe section Slide the assembled storm collar down the pipe sec...

Отзывы: