Healthy Climate Solutions HEPA-20 Скачать руководство пользователя страница 10

Preparation:

Here are some things to consider as you 

decide where to install the HEPA system 

with an HRV/ERV. 

Location:

Make sure there is room to open the 

HEPA filter access panel for filter 

changes/inspections.

Keep the HEPA system in a location 

where you can still access the air han-

dler/furnace filter.

Keep the HEPA system away from pos-

sible water damage

Vibration pads will reduce vibration for 

installations where the unit is placed on 

the floor.

Install HEPA System on floor or suspended platform.  

If the unit is suspended, screws must not penetrate 

through the cabinet.  Make sure that you have the 

proper chains/straps/joists and equipment to keep 

unit secure.

Inlet 

(Marked as ‘Air In’ on unit)

:

Most HRV/ERV systems will not move as much air 

as the HEPA system. For these systems, install an 

additional return from another treated air source 

into the HEPA system.

If using an additional return duct, it should be 

installed upstream of any humidifiers.  The fresh 

air outlet of the HRV/ERV should be “Y” connected 

to the additional return duct then connected to the 

inlet of the HEPA system.

The additional return duct (if any) should be 

installed at least 8 ft. away from the outlet duct on 

the main return.

Duct both the HRV/ERV and the additional return 

into the inlet of the HEPA system.

Outlet 

(Marked as ‘Clean Air Out’ on unit)

:

Outlet duct should be installed as close to the air 

handler/furnace inlet as possible but not directly into 

the return air elbow of the main return.

To reduce static pressure, install outlet with a 45 

degree takeoff directly up-line from the return air elbow 

of air handler/furnace.

Ducting:

If HEPA system is installed where inlet and outlet 

collars face down, metal elbows must be connected 

to both inlet and outlet collars.

Each connection must be sealed with aluminum 

tape or mastic, including all take offs.

Installed duct runs should be as straight as possible 

(if the duct runs are too long, reduced CFM may 

result).

If duct is exposed to unconditioned air, externally 

insulated flex duct is highly recommended.

Externally insulated flex duct can also be used for 

noise reduction purposes

For best indoor air quality, do not use ductboard or 

fiberglass inside of ducts.

Electricity:

The unit must be plugged into a grounded 120V, 

60Hz outlet.

Required Materials for Installation of Unit:

For Model: HEPA-20

8” diameter flex or rigid duct (as required)

6” diameter flex or rigid duct (as required)

6” diameter 45 degree takeoff

Aluminum tape or mastic

Misc. hanging materials - field provided

For Models: HEPA-40 & HEPA-60

10” diameter flex or rigid duct (as required)

8” diameter flex or rigid duct (as required)

10” diameter 45 degree takeoff

8” diameter 45 degree takeoff

Aluminum tape or mastic

Misc. hanging materials - field provided

NOTE:  Be sure to review ‘Rules for Safe Installation 

and Operation’ on page 1 of this document before 

start-up of this unit.

10

HRV/ERV

Figure 8.

Forced air handler/furnace system with an HRV/ERV

This application provides filtration of all Outdoor Air (OA) that is brought into the home through the HRV/ERV, 

thus reducing the introduction of dust, pollen and mold from the outdoor air.  For systems that have HRV/ERV 

units installed, we recommend ducting the ‘fresh air’ outlet from the HRV/ERV into the HEPA system.  If the 

HRV/ERV CFM (cubic feet per minute) rating is lower than that of the HEPA system, an additional return needs 

to be installed into the HEPA system (See figure 8.)  The output air from the HEPA system then needs to be 

installed into the main return of the air handler/furnace system.

 Healthy Climate® Dealer Installation Instructions

Example of Return 

to Return Installation 

with an HRV/ERV

For homes with a forced 

air handler/furnace sys-

tem and an HRV/ERV 

system.

Additional Return

Air Handler/Furnace

Air Handler/Furnace Filter

HEPA System

NOTE:  This filtration system is an ADDITIONAL filter, and does NOT 

replace the existing air handler/furnace system filter.

Содержание HEPA-20

Страница 1: ...aware of your indoor air quality situation and be familiar with your heating ventilation and air conditioning equipment 4 Remove HEPA cartridge packing materials before initial start up of this produc...

Страница 2: ...ay shorten the life of the carbon canister Under normal conditions the carbon canister will last up to 6 months Initially the HEPA filter s particulate removal efficiency improves with use However the...

Страница 3: ...and odors from the air OPTIONAL UPGRADE The stage 3 Inner Carbon Filter may be replaced by an optional heavy duty granulated coconut shell carbon canister The VOC Canister offers increased capacity r...

Страница 4: ...abinet Filter Section Optional Coconut Shell Carbon Canister HEPA Cartridge Parts figure 1 figure 3 figure 4 figure 2 Motor Impeller Filter Adapter threaded O Ring Specifications HEPA 20 HEPA 40 HEPA...

Страница 5: ...1 75 410 718 254 203 44 HEPA 60 16 13 28 25 10 0 8 0 1 75 410 718 254 203 44 F G H I J HEPA 20 2 0 1 0 9 0 15 25 1 4 51 25 229 387 36 HEPA 40 6 5 1 0 11 0 17 875 1 875 165 25 279 454 48 HEPA 60 6 5 1...

Страница 6: ...s of dust humidity or chemicals found in your ambient air Additionally people who are more sensitive to these air borne contaminates may desire more fre quent filter changes Filter Changing Guidelines...

Страница 7: ...other end of the clip once the carbon pre filter is stretched tight to lock the clip into place as shown in figure 15 Release clip it should hold tight on both ends of the carbon pre filter keeping it...

Страница 8: ...an cause injury or death Disconnect all electrical power supplies before servicing Do no operate equipment without access panels in place Do not use this fan with any solid state speed control device...

Страница 9: ...irectly into the return air elbow of the main return To reduce static pressure install outlet with a 45 degree takeoff directly up line from the return air elbow If the unit is being installed indepen...

Страница 10: ...s should be as straight as possible if the duct runs are too long reduced CFM may result If duct is exposed to unconditioned air externally insulated flex duct is highly recommended Externally insulat...

Страница 11: ...ers are recommended to help distribute airflow evenly in the occupied space Ducting If HEPA system is installed where inlet and outlet collars face down metal elbows must be connected to both inlet an...

Страница 12: ...8 15 for optimal VOC Aldehyde removal Other Recommeded HEALTHY CLIMATE Products Ventilation Control System LVCS X4141 Humiditrol Whole Home Dehumidification Systems EDA 024B 94M41 EDA 036C 94M42 EDA 0...

Отзывы: