Healthy Climate

® 

HRV/ERV Ventilators

Installing Drain Connection 

(HRV unit only)

During a defrost cycle, the HRV unit may produce some
condensation. This water should flow into a nearby drain,
or be taken away by a condensate pump.

CAUTION

Potential Freeze Conditions leading to Water Dam-
age.

Condensation can accumulate and cause water
damage to equipment, finished surfaces and struc-
tures.

Do not install HRV or route condensate drain lines
in areas that can be subjected to freezing.

Potential Water Damage.

Unit must be installed level to ensure proper con-
densation drainage. Avoid installing units above
areas or equipment that are sensitive to water dam-
age.

Connect condensate drains in accordance with na-
tional and local codes.

P−Trap and tubing must be located below the HRV
door with a minimum of ¼" per foot downward slope
away from unit.

The HRV cabinet has prepunched holes for the drain (see
figure 15). Insert the drain spout and its O−ring seal through
the hole in the drain pan. HAND TIGHTEN the washer and
lock nut which hold the drain spout in place.

TO DRAIN

ZIP TIE

TO DRAIN

DRAIN HOSE
PLUMBING

DRAIN PIPE
PLUMBING

TEE

CONNECTOR

1/2" I.D. DRAIN HOSE

DRAIN

SPOUT

DRAIN

SPOUT

PRE−PUNCHED HOLES

DRAIN PAN

DRAIN PAN

PRE−PUNCHED HOLES

DRAIN PAN

DRAIN PAN

1/2" I.D. PIPE

TEE

ELBOW

ELBOW

DRAIN

SPOUT

DRAIN

SPOUT

TRAP

Figure 15. P" Trap (HRV unit only)

Construct a P−Trap using the plastic tee connector (see
Drain Hose Plumbing, figure 15). Cut two lengths of hose
and connect each piece to an end of the ˆT˜ fitting, then
connect the other ends to the two drain spouts. Position

the "T" fitting to point upward, and connect the drain line.
Tape or fasten base to avoid any kinks. This creates a
ˆtrap˜ which will hold some condensate and prevent odors
from being drawn up the hose and into the fresh air supply
of the HRV unit. (Fig. 15 also shows Drain Pipe Plumbing.)

NOTE − Secondary drain pan may be required to protect
from condensate leakage, especially when unit is installed
above living space.

Installing Grilles

Use adjustable grilles or diffusers to balance the flow rates
into and out of various rooms. The grilles should not be ad-
justed after balancing the unit.

Install grilles or diffusers high on the wall or in the ceiling.
Kitchen grilles must never be connected to a range hood.
Install grilles at least 4 feet (1.2 m) horizontally away from
the stove.

Install field-supplied balancing dampers external to the
unit to balance the amount of stale air being exhausted
with the amount of fresh air being brought into the house.
(Refer to Air Flow Balancing on page 28.)

CAUTION

Potential equipment malfunction or damage.

May require repairs and/or void warranty.

Do not install intake grille within 4 feet (1.2 m) of a
kitchen stove or cooking surface that emit cooking
vapors.

Kitchen Grille

The kitchen grille includes a
removable grease filter. Most
building codes require that
kitchen grilles be equipped
with a washable grease filter.

6" (152 mm) x 10" (254 mm)

18N48

Round Diffuser

The round diffuser is a fully ad-
justable grille which provides
superior, quite air distribution.
These diffusers are available:

4" (102 mm) 

92E54

5" (127 mm) 

92E55

6" (152 mm) 

92E56

8" (203 mm) 

56N81

Figure 16. Kitchen Grille & Round Diffuser

REMOVABLE
GREASE FILTER

ROUND DIFFUSER

KITCHEN GRILLE

AIR FLOW

SUPPLY

AIR FLOW
EXHAUST

Содержание HEALTHY CLIMATE ERV3-150

Страница 1: ...bly containing 2 Drain spout assemblies HRV units only 1 Drain tee HRV units only 4 Hanging straps 1 Installation manual 1 Warranty card 1 Wall mounted remote control General Information These instruc...

Страница 2: ...sensible temperature and latent moisture heat from in coming fresh air to the stale air as it is being exhausted thus reducing the air conditioning load The ERV unit is not suitable for use in climate...

Страница 3: ...116 CFM 55 L s 69 Sensible Efficiency 13 F 25 C 76 CFM 31 L s 73 65 CFM 30 L s 56 61 CFM 29 L s 68 65 CFM 31 L s 73 64 CFM 30 L s 72 112 CFM 53 L s 72 132 CFM 62 L s 70 N A N A Latent Efficiency 95 F...

Страница 4: ...44 0 7 175 40 19 72 34 94 44 80 38 0 8 200 Speed 2 med low 0 1 25 62 29 87 41 127 60 115 54 170 79 73 34 112 53 0 2 50 81 38 81 38 54 25 74 35 116 55 107 50 163 76 67 31 107 50 0 3 75 70 33 70 33 42...

Страница 5: ...TS HRV3 300 MODEL HRV3 195 MOTOR IS AT TOP BLOWER DEFROST DAMPER DEFROST AIR FROM INSIDE FILTER CONDENSATE DRAINS FRESH AIR TO INSIDE STALE AIR FROM INSIDE BLOWER FRESH AIR FROM OUT SIDE MOTOR SEE NOT...

Страница 6: ...in ventilation for 15 minutes No remote device can override this defrost mode or se lected speed until the cycle is complete After the cycle is completed the HRV defaults to previous settings If the c...

Страница 7: ...ed see page 28 or 31 to prevent negative pressure in structure Negative pressure can cause back drafting of combustion gases in other household appliances such as Gas Furnaces Oil Furnaces Hot Water H...

Страница 8: ...ating season when outdoor temperatures are less than 59 F 15 C HRV controls include a dehumidistat function which can be set to achieve a dehumidification effect from the HRV dur ing the winter heatin...

Страница 9: ...ow voltage wire UNIT ON OFF Control Press and release the ON OFF button ON indicator light illuminates press again to turn OFF Humidity Control Unit will produce a dehumidifying ef fect when outdoor h...

Страница 10: ...se the UP DOWN arrows to adjust the Humidity Indi cator on the display screen to the number of degrees difference between your humidity measuring device Minus is indicated by flashing 4 Press MODE Dig...

Страница 11: ...o 4 events per day 8 ARRIVE flashes Repeat steps 4 to 6 to program up to 4 events per day 9 SLEEP flashes Repeat steps 4 to 6 to program up to 4 events per day 10 Weekend letters SS flash Press SET Re...

Страница 12: ...olding the SELECT button for 5 seconds Connect to 3 wire 20 gauge low voltage wire and is installed in a standard 2 x 4 electrical box 20 Minute Status Lights Select Button Figure 6 20 Minute Timer Y2...

Страница 13: ...kept short and have as few bends or elbows as possible to maximize airflow Forty five degree elbows are preferred to 90 elbows Use Y tees instead of straight tees whenever possible All duct joints mu...

Страница 14: ...cations S Unit is normally balanced on HIGH speed with the furnace blower ON S A minimum separation of 40 inches 1m is recommended between the two direct connections S The exhaust air connection shoul...

Страница 15: ...blower to evenly distribute the fresh air throughout the house S The duct configuration may change depending on the HRV ERV model See specifications for your unit S Check local codes and authority hav...

Страница 16: ...locating grilles if the floor is the only option available Areas such as under baseboard heaters will help to temper the air Optional inline duct heaters are available for mounting in the supply air...

Страница 17: ...close to the out side wall where the weather hoods will be mounted If a basement area is not convenient or does not exist a utility or laundry room may be used Attic installations are not normally rec...

Страница 18: ...ews Note This illustration of the unit may vary from the unit you are installing Step 3 Hook the bottom grommets of the straps through the S hooks Pull down vertically on the hand loops while lifting...

Страница 19: ...to the two drain spouts Position the T fitting to point upward and connect the drain line Tape or fasten base to avoid any kinks This creates a trap which will hold some condensate and prevent odors...

Страница 20: ...Exhaust Weatherhood Requirements Observe the following when installing the exhaust weatherhood 1 At least 6 2m from the ventilation air intake 2 At least 18 457mm above ground or above the depth of ex...

Страница 21: ...cfm See Note Compatible with Dual Hood 0 3 0 4 0 5 HRV3 150 TPD 115 104 95 Yes HRV3 150 TPF 120 107 100 Yes HRV3 095 66 60 n a Yes HRV4 150 90 80 72 Yes HRV4 200 120 107 100 Yes HRV3 195 125 114 107...

Страница 22: ...all using the 2 supplied screws and anchors 9 Attach the faceplate to the back plate detail B BE CAREFUL to correctly align the faceplate to avoid damaging the faceplate contact pins 10 Insert the Ope...

Страница 23: ...etween 2 ON and 6 HI initiates high speed ventilation Dehumidistat A dry contact for a dehumidistat is connected between 2 ON and 10 BLK 1 2 3 4 5 6 7 8 9 10 LOW ED R YEL GRN HI COM NO NC BLK LOW SPEE...

Страница 24: ...andler with a simplified return return installation and should be interlocked with a partially dedicated installation see figure 24 CAUTION Potential equipment malfunction or damage May require repair...

Страница 25: ...e 25 Residential Wiring Diagram HRV3 095 HRV4 150 HRV4 200 HRV3 195 HRV3 300 ERV3 150 ERV3 200 THERMISTOR Not on all units TERMINAL BLOCK GROUNDED PLUG SEE DEFROST DETAIL BELOW SEE AUTO TRANS FORMER D...

Страница 26: ...Page 26 12 12 Figure 26 Residential Wiring Diagram HRV3 150 TPD...

Страница 27: ...Page 27 Healthy Climate HRV ERV Ventilators Figure 27 Residential Wiring Diagram HRV3 150 TPF...

Страница 28: ...m the outside must equal the volume of air exhausted by the unit if the airflow is not properly balanced then 1 The HRV ERV unit may not operate at its maximum efficiency 2 A negative or positive air...

Страница 29: ...ut of the branch of the Pi tot is connected to the low pressure or reference side of the gauge 4 Insert the Pitot tube into the duct pointing the tip into the airflow 5 For general balancing it is suf...

Страница 30: ...itot tube a minimum of 18 from blower or elbows Place Pitot tube a minimum of 18 from blower or elbows Pitot tube Magnehelic Gauge High Pressure Side Low Pressure Side NOTE Duct connections will vary...

Страница 31: ...nitiate power and operate the HRV on high speed Operate the forced air system on high speed if the HRV is connected to the forced air system 5 Measure Stale air Insert the 2 rubber fittings from the g...

Страница 32: ...700 175 108 0 530 133 139 93 0 490 123 82 64 0 710 178 105 0 540 135 132 91 0 500 125 79 62 0 720 180 176 102 0 550 138 125 88 0 510 128 76 60 0 730 183 165 99 0 560 140 119 85 0 520 130 73 57 0 740 1...

Страница 33: ...165 41 103 164 0 160 40 110 142 0 220 55 128 173 0 170 42 105 170 0 165 41 112 145 0 225 56 129 176 0 175 44 111 176 0 170 42 115 149 0 230 57 130 179 0 180 45 113 182 0 175 44 118 152 0 235 58 132 18...

Страница 34: ...0 0 195 49 114 170 0 180 45 104 178 0 180 45 106 163 0 200 50 116 173 0 185 46 106 183 0 185 46 108 167 0 205 51 117 176 0 190 47 109 189 0 190 47 110 171 0 210 52 119 178 0 195 49 111 194 0 195 49 11...

Страница 35: ...ED ON NO LED SYSTEM POWER ON Press ON OFF fan button Failed wall control LED OFF LED ON NONE Normal operation LOW SPEED FAN OFF FAN ON ON OFF LED status Wall control ON OFF LED flashes to indicate rev...

Страница 36: ...Operational Flowchart 2 Failed HRV ERV controller NO YES NO Refer to interface operation instructions Fan may operate based on interface settings Interface control with ON OFF connected Jumper ON to R...

Страница 37: ...ode damper closed to outdoor air 3 Recirculation mode is only available on recirculating defrost models HRV3 095 HRV3 150 TPD HRV4 150 HRV4 200 Dehumidistat Disable Four consecutive temperature readin...

Страница 38: ...the home from an unvented or unheated crawl space Moisture remaining in washroom and or kitchen areas Condensation seems to form in the spring and fall seasons HRV ERV is set at too low a speed Set d...

Страница 39: ...300 Y2144 ERV3 150 Y2138 ERV3 200 Y2139 Motor Capacitor Y5438 Y5438 Y2146 Y5436 Y5437 Y2145 Y2147 Y2145 Y2145 Blower Housing Set N A N A Y2149 Y5439 Y5439 Y2150 Y2150 Y2148 Y2148 Blower Wheel CW red...

Страница 40: ...ck and white wire from cir cuit board leading to the motor and pull wires to re move from the electrical box 7 Remove assembly blower motor blower panel by sliding left and down To Assemble Blower Ass...

Страница 41: ...ishwasher pressure wash F Install clean filters G Wipe down the inside of the cabinet with a damp cloth to remove dirt bugs and any debris 4 Install clean core as follows A Install the bottom flange o...

Страница 42: ...nit Recommended Arid Zone Dry Climate HRV Unit Required ERV unit not recommended where temperatures fall below 25 F 4 C continuously for more than 5 days ERV units are recommended in regions where hig...

Отзывы: