PROBES AND ACCESSORIES
WARNING:
ALWAYS use probes appropriate to your application.
NEVER use overhead probes in underground applications. Failure
to use the correct probe can result in arcing or electrical contact
and may cause serious injury or death. If you are not trained in
the particular operation or are not sure about the appropriate
probe for your application
DO NOT PROCEED.
OVERHEAD PROBES
• OLPS-5 brass hook probe
• OLPS-6 brass pigtail probe
UNDERGROUND DEAD FRONT BUSHING PROBES
• ASP-15/25 for use in 15kV and 25kV loadbreak bushings
• ASP-35U for use in 35kV loadbreak bushings
UNDERGROUND ELBOW PROBE
• EA-15/25 for insertion in loadbreak elbows.
NOTE:
The elbow must be firmly
supported when using this probe.
INSULATED UNDERGROUND PROBE
• GCP-1 for general underground
use on grounded terminals and
exposed high voltage terminals.
INSULATED UNDERGROUND PROBE
• GCP-1 for general underground use
on grounded terminals and exposed
high voltage terminals.
ADD-ON RESISTOR STICKS
• R-69 for use on voltages above 15kV up to 45kV
6
ASP-15/25
EA-15/25
ASP-35U
OLPS-6
OLPS-5
GCP-1
PROOF TESTER
The PT-5000B Proof Tester will produce 5kVDC at the test
leads to confirm proper operation of the phase rotation
meter. The PT-5000B operates from one 9V alkaline battery
and produces approximately 5kVDC at the connecting
leads. To use:
1) Connect both tester leads to the phase rotation meter
probes. Isolate the ground lead from ground or any
other conductor and do not touch it during the test.
2) Press and hold both TEST buttons.
3) Confirm a good battery by checking the red light on the Tester.
If the red light does not come on, replace the battery with a 9V alkaline only.
4) Verify the phase rotation meter reads approximately 5kV.
5) Release the TEST buttons and disconnect the Tester from the phase rotation meter.
WARNING:
Do not use the phase rotation meter if proper operation is not confirmed.
WARNING:
Do not use this tester except as directed. Do not use to test equipment
other than the phase rotation meter. Do not apply to energized circuits or equipment.
Refer all servicing to the factory. Failure to follow these instructions may lead to
electric shock, severe injury or death.
R-45
PT-5000B