background image

MAY, 2018

HD 287

PAGE 3 OF 4

HD FIRE PROTECT

PVT. LTD.

RECESSED PENDENT

 PENDENT & UPRIGHT SPRINKLER

30.32 mm

16.5 m

m

52.4 m

m

34.35 mm

16.5 m

m

51.6 m

m

TY

PICA

WA

LL

FINISHED SURFACE

38.08m

m

18.58m

m

FINISHED SURFACE

TY

PICA

WA

LL

MAXIMUM EXTENSION

MAXIMUM RECES

S

MAX.HOLE 

60mm

MAX.HOLE 

60mm

MIN..HOLE

 

54mm

MIN..HOLE

 

54mm

PENDENT

UPRIGHT

Tolerance for all dimensions ± 0.5 mm

Содержание K FACTOR-8

Страница 1: ... of areas with finished ceilings or walls Sprinkler Operation The Sprinkler operating device is state of the art heat responsive frangible glass bulb supplied by a world leader in this innovative technology The glass bulb contains fluid which expands when exposed to heat When rated temperature is reached the bulb shatters and water flows through the sprinkler and strikes deflector forming a unifor...

Страница 2: ...ing sprinkler temperature rating but the temperature rating is still stamped on the sprinkler deflector SPRINKLER RATINGS SPRINKLER TEMP CLASSIFICATION NORMAL SPRINKLER TEMP RATING NFPA MAX CEILING TEMP ALLOWED GLASS BULB COLOUR Ordinary 57 C 135 F 38 C 100 F Orange Ordinary 68 C 155 F 38 C 100 F Red Intermediate 79 C 175 F 66 C 150 F Yellow Intermediate 93 C 200 F 66 C 150 F Green Material Specif...

Страница 3: ... SPRINKLER 30 32 mm 16 5 mm 52 4 mm 34 35 mm 16 5 mm 51 6 mm TYPICAL WALL FINISHED SURFACE 38 08mm 18 58mm FINISHED SURFACE TYPICAL WALL MAXIMUM EXTENSION MAXIMUM RECESS MAX HOLE 0 60mm MAX HOLE 0 60mm MIN HOLE 0 54mm MIN HOLE 0 54mm PENDENT UPRIGHT Tolerance for all dimensions 0 5 mm ...

Страница 4: ...5 305 245 185 135 75 50 100 150 200 250 300 120 230 K8 0 PENDENT SPRINKLER DISTRIBUTION PATTERNS TRAJECTORY 175 psi 50 psi 100 psi 20 psi 275 Distribute the water distance cm Mounting height cm 215 165 1054 5 3052 45 185 135 75 45 105 1652 15 275 305 245 185 135 75 50 100 150 200 250 300 120 230 100 psi 175 psi 20 psi 50 psi K8 0 UPRIGHT SPRINKLER DISTRIBUTION PATTERNS TRAJECTORY ...

Страница 5: ...LPM PRESSURE IN PSI 0 51 5 2 53 5 4 55 5 6 5 7 7 5 8 8 5 9 71 52 03 03 54 55 05 56 57 08 08 59 5 100 105 115 120 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 60 21 26 16 31 37 42 48 53 58 63 69 74 79 85 90 95 100 106 DISCHARGE IN GPM NOMINAL K 8 0 NOMINAL K 114 TOOLS SPRINKLER WRENCH SPRINKLER KEY ...

Страница 6: ...ed by HD FIRE HD FIRE shall not be liable for any damages or labour charges or expense in making repair or adjustment to the product HD FIRE shall not be liable for any damages or charges sustained in the adaptation or use of its engineering data services In no event shall HD Fire s product liability exceed an amount equal to the sale price The foregoing warranty is exclusive and in lieu of all ot...

Отзывы: