background image

MAY, 2018

HD 287

PAGE 1 OF 4

HD FIRE PROTECT

PVT. LTD.

SPRINKLER  -  UPRIGHT,  PENDENT  AND        

RECESSED PENDENT 

(K FACTOR - 8)

TECHNICAL DATA

Style 

Upright, Pendent and  

 

 

Recessed Pendent

Temperature 

Standard Response - 5mm 

Response 

glass bulb 

 

Quick Response - 3mm glass bulb

Coverage 

Standard Coverage

K-Factor 

8.0 US (115 metric)

Nominal Thread Size  3/4” NPT 
Max. Working 

175 PSI (12 Bar) 

Pressure
Factory Hydrostatic  500 PSI (35 Bar) 

Test Pressure
Min. Operating 

7 PSI (0.5 Bar) 

Pressure
Temp. Rating 

57°C (135° F), 68°C (155° F), 

 

79°C (175° F), 93°C (200° F)

Approvals 

UL Listed

Finish 

Brass, Chrome Plated, 

 

White Painted  

.                                                                  White  shade  is  RAL9010.                                                                                                                                         

                                  For other shades, contact  

 

HD Sales.

Ordering 

Style, Temperature Rating &  

Information 

Response, Finish

SIN Number 

HD171 -  SR, Pendent &    

 

 

  Recessed Pendent  

 

HD172 -  SR, Upright 

 

HD271 -  QR, Pendent &    

 

 

  Recessed Pendent  

 

HD272 -  QR, Upright

DESCRIPTION 
Pendent & Upright Sprinklers

HD Pendent and Upright sprinklers are designed for 

use in light and ordinary hazards. The temperature 

response is standard response (5mm glass bulb) 

and quick response (3mm glass bulb). The sprinklers 

come with compact design, glass bulb type, available 

in several different finishes and temperature ratings. 

The pendent sprinklers must be installed in pendent 

position, and upright sprinklers are to be installed in 

the upright position. 
Pendent Recessed Sprinklers are installed with 

adjustable or non-adjustable Escutcheon plates (also 

termed as Rosette plates). These are intended to 

be installed with finished ceilings. Escutcheon plate 

adjustment provides convenience in Pendent Sprinkler 

installation in case of areas with finished ceilings or 

walls.

Sprinkler Operation

The Sprinkler operating device is state of the art heat 

responsive frangible glass bulb supplied by a world 

leader in this innovative technology. The glass bulb 

contains fluid which expands when exposed to heat.
When rated temperature is reached, the bulb shatters 

and water flows through the sprinkler and strikes 

deflector, forming a uniform water spray pattern to 

control or extinguish fire.

Care and Handling

Sprinklers must be handled with due care, they must 

be stored at ambient temprature for best results. 

Storage as well as any onward shipment is to be made 

in original packing only. Sprinklers must be visually 

inspected carefully before installation. Sprinklers 

visibly damaged, dropped or exposed to temperature 

in excess of the maximum ambient temperature 

permitted, should never be installed. Never install 

any glass blub sprinkler if the bulb is cracked or if 

there is a loss of liquid from the bulb. Sprinkler must 

be installed after the piping is in place to prevent 

mechanical damage.
Use Teflon Tape or soft thread sealent on male thread 

of the Sprinkler for the leak tight Sprinkler joint. Use 

proper wrench and appropriate torque. Excessive 

tightening torque may distort the Sprinkler inlet 

and cause leakage. Sprinkler must never be painted, 

plated or coated after they leave factory.
The HD Sprinkler described herein must be installed 

and maintained in accordance with the latest edition 

of HD technical data, the latest standard of National 

Fire protection Association (NFPA) and Factory Mutual 

(FM) or to the standard of any other authorities 

having jurisdiction. The owner is solely responsible for 

maintaining their fire protection system and device in 

proper operating condition.

Содержание K FACTOR-8

Страница 1: ... of areas with finished ceilings or walls Sprinkler Operation The Sprinkler operating device is state of the art heat responsive frangible glass bulb supplied by a world leader in this innovative technology The glass bulb contains fluid which expands when exposed to heat When rated temperature is reached the bulb shatters and water flows through the sprinkler and strikes deflector forming a unifor...

Страница 2: ...ing sprinkler temperature rating but the temperature rating is still stamped on the sprinkler deflector SPRINKLER RATINGS SPRINKLER TEMP CLASSIFICATION NORMAL SPRINKLER TEMP RATING NFPA MAX CEILING TEMP ALLOWED GLASS BULB COLOUR Ordinary 57 C 135 F 38 C 100 F Orange Ordinary 68 C 155 F 38 C 100 F Red Intermediate 79 C 175 F 66 C 150 F Yellow Intermediate 93 C 200 F 66 C 150 F Green Material Specif...

Страница 3: ... SPRINKLER 30 32 mm 16 5 mm 52 4 mm 34 35 mm 16 5 mm 51 6 mm TYPICAL WALL FINISHED SURFACE 38 08mm 18 58mm FINISHED SURFACE TYPICAL WALL MAXIMUM EXTENSION MAXIMUM RECESS MAX HOLE 0 60mm MAX HOLE 0 60mm MIN HOLE 0 54mm MIN HOLE 0 54mm PENDENT UPRIGHT Tolerance for all dimensions 0 5 mm ...

Страница 4: ...5 305 245 185 135 75 50 100 150 200 250 300 120 230 K8 0 PENDENT SPRINKLER DISTRIBUTION PATTERNS TRAJECTORY 175 psi 50 psi 100 psi 20 psi 275 Distribute the water distance cm Mounting height cm 215 165 1054 5 3052 45 185 135 75 45 105 1652 15 275 305 245 185 135 75 50 100 150 200 250 300 120 230 100 psi 175 psi 20 psi 50 psi K8 0 UPRIGHT SPRINKLER DISTRIBUTION PATTERNS TRAJECTORY ...

Страница 5: ...LPM PRESSURE IN PSI 0 51 5 2 53 5 4 55 5 6 5 7 7 5 8 8 5 9 71 52 03 03 54 55 05 56 57 08 08 59 5 100 105 115 120 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 60 21 26 16 31 37 42 48 53 58 63 69 74 79 85 90 95 100 106 DISCHARGE IN GPM NOMINAL K 8 0 NOMINAL K 114 TOOLS SPRINKLER WRENCH SPRINKLER KEY ...

Страница 6: ...ed by HD FIRE HD FIRE shall not be liable for any damages or labour charges or expense in making repair or adjustment to the product HD FIRE shall not be liable for any damages or charges sustained in the adaptation or use of its engineering data services In no event shall HD Fire s product liability exceed an amount equal to the sale price The foregoing warranty is exclusive and in lieu of all ot...